VA 33 63 00-2010 STEAM ENERGY DISTRIBUTION.pdf
《VA 33 63 00-2010 STEAM ENERGY DISTRIBUTION.pdf》由会员分享,可在线阅读,更多相关《VA 33 63 00-2010 STEAM ENERGY DISTRIBUTION.pdf(56页珍藏版)》请在麦多课文档分享上搜索。
1、02-10 33 63 00 - 1 SECTION 33 63 00 STEAM ENERGY DISTRIBUTION SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. References to pressure in this section are gage pressure unless o
2、therwise noted. 3. Include VA National CAD Standards as applicable to the project on the contract drawings: 02710-1.DWG Concrete Steam Manhole with Typical Piping. 15339-2.DWG Steam Trap Assembly and Steam Line Drip Pocket. 15339-4.DWG Steam Line Drip Trap Schedule. 15339-7.DWG High and Medium Press
3、ure Steam Trap Discharge into Pumped Condensate Return Line. 4. Refer to Appendices for site conditions that affect the choice of the type of underground system. PART 1 GENERAL: 1.1 DESCRIPTION: Underground steam distribution and condensate return piping system, including manholes. Type of system sh
4、all be: / walk-through concrete tunnels / concrete shallow trenches / pre-engineered direct-buried drainable-dryable-testable (DDT)/pre-engineered direct-buried water-spread-limiting (WSL) /. 1.2 DEFINITIONS: A. System: A complete underground steam and condensate distribution system including all co
5、mponents such as carrier piping, pipe supports, insulation, protective enclosures, anchors, corrosion protection and accessories. B. Pre-Engineered Direct-Buried System: System that is designed and factory-fabricated by a company specializing in these systems. The system includes pre-fabricated prot
6、ective enclosures and does not require a concrete trench or tunnel. The pre-engineered system shall include all piping and components to a point at least 150 mm (6 inches) inside the building and manhole walls. C. Drainable-Dryable-Testable (DDT) Pre-Engineered Direct-Buried System: A factory-fabric
7、ated system including an airtight and watertight outer protective casing, an insulated carrier pipe and an air space between the insulated carrier pipe and the casing. Drains and vents are provided in the ends of the system (in manholes or buildings). The drains allow Provided by IHSNot for ResaleNo
8、 reproduction or networking permitted without license from IHS-,-,-02-10 33 63 00 - 2 draining of ground water or condensate that may leak into the air space if there is a failure in the casing or the carrier pipe. The vents allow water vapor to escape and provide an indication of leakage. SPEC WRIT
9、ER NOTE: WSL systems are permitted only if the system design has successfully completed testing required by Unified Facilities Guide Spec (UFGS) 33 63 13, April 2006 or later, and the site is Class B, C or D (Appendix III). D. Water-Spread-Limiting (WSL) Pre-Engineered Direct-Buried System: A factor
10、y-fabricated system including an airtight and watertight outer protective casing and an insulated carrier pipe. It is fabricated in short sections (approximately 6 m (20 feet) long) which are independent from each other in that ground water or condensate which leaks from or into one section cannot t
11、ravel into the next section. Field-assembly of the sections requires no welding as the sections push together with a system of couplings and seals. Thermal expansion is absorbed in the clearance between carrier pipe ends in the couplings so that no expansion loops are required. E. Concrete Shallow T
12、rench: System with removable concrete covers located at grade. Carrier pipes are located within trench. Cross-section of trench is sufficient size only for piping, insulation, supports, air space and drainage. Designed by project engineer and field erected. Prefabricated concrete trench sections may
13、 be used. No equipment requiring access for operation or maintenance can be located in the trench because there is no access except by removing the heavy concrete covers. F. Walk-through Concrete Tunnels: System located below grade with sufficient space for carrier pipes, other services, and space t
14、o walk upright along the entire length of the system. Designed by project engineer and field erected. Prefabricated concrete tunnel sections may be used. G. Carrier Pipe: Pipe carrying the steam or condensate. H. Casing: Outer protective pipe on pre-engineered systems. Carrier pipe and insulation ar
15、e within the casing. The casing may also be referenced as the “conduit”. SPEC WRITER NOTE: Verify that the project drawings include the information listed below. I. Project Drawings: The “MS” project drawings accompanying this specification provide information on: 1. The size of carrier pipes, appro
16、ximate length, and site location of the system. 2. The elevation and routing of the piping on the site. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 33 63 00 - 3 3. Location and design of manholes and piping therein. 4. The obstacles located
17、 within approximately 25 m (8 feet) of the centerline of the system, including crossing utilities, that must be avoided or altered. 5. Type of system required - shallow concrete trench, walk-through tunnel, pre-engineered direct-buried. 6. Location of piping anchors. 7. Operating pressure and temper
18、ature of systems. 8. Details applicable to type of system specified. 9. Details of manhole and building entrances. 10. Other pertinent general information. J. Pressures: Pressures listed in this section are gage pressure unless otherwise noted. 1.3 RELATED WORK: A. Phasing of work: Section 01 00 00,
19、 GENERAL REQUIREMENTS. B. Excavation, shoring and backfill: Section 31 20 00, EARTH MOVING / Section 31 20 11, EARTH MOVING (SHORT FORM) /. C. Concrete work: Section 03 30 00, CAST-IN-PLACE CONCRETE. D. Waterproofing of concrete structures: / Section 07 12 00, BUILT-UP BITUMINOUS WATERPROOFING / Sec
20、tion 07 13 52, MODIFIED BITUMINOUS SHEET WATERPROOFING /. E. Asbestos removal work: Section 02 82 11, TRADITIONAL ASBESTOS ABATEMENT. F. Painting exposed steel and other surfaces: Section 09 91 00, PAINTING. G. Steel for trench and tunnel pipe supports: Section 05 50 00, METAL FABRICATIONS. H. Catho
21、dic Protection of DDT Pre-Engineered Direct-Buried Systems: Section 26 42 00, CATHODIC PROTECTION 1.4 QUALITY ASSURANCE: A. Approval by Contracting Officer is required of products or services of proposed manufacturers, suppliers and installers. B. For pre-engineered direct-buried systems, expansion
22、joints and ball joints, submit certification that: 1. Manufacturers regularly and currently manufacture the product. 2. There is a permanent service organization trained by the manufacturer that will provide the required field supervision of the installation of the system or equipment. Submit name a
23、nd address of the service organization. C. The manufacturer of pre-engineered direct-buried distribution system shall design the system to comply with the requirements of these specifications and is responsible for the complete product to be supplied, fabrication, witnessing installation and testing
24、 of the system. The complete design of Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 33 63 00 - 4 the system shall be prepared, signed and sealed by a Professional Engineer employed by the system manufacturer. D. Products Experience Record: 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA3363002010STEAMENERGYDISTRIBUTIONPDF