VA 28 05 26-2011 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY.pdf
《VA 28 05 26-2011 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY.pdf》由会员分享,可在线阅读,更多相关《VA 28 05 26-2011 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、09-11 28 05 26 - 1 SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete / _ / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. Insert additional provisions as required for th
2、is project. PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies the finishing, installation, connection, testing and certification of the grounding and bonding required for a fully functional Electronic Safety and Security (ESS) system. B. “Grounding electrode system” refers to all electrodes
3、 required by NEC, as well as including made, supplementary, grounding electrodes. C. The terms “connect” and “bond” are used interchangeably in this specification and have the same meaning 1.2 RELATED WORK SPECS WRITER NOTE: Delete any item or paragraph not applicable in the section. A. Section 01 0
4、0 00 - GENERAL REQUIREMENTS. For General Requirements. B. Section 26 41 00 - FACILITY LIGHTNING PROTECTION. Requirements for a lightning protection system. C. Section 28 05 00 - REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY INSTALLATIONS. For general electrical requirements, quality assurance, coo
5、rdination, and project conditions that are common to more than one section in Division 28. D. Section 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY. Requirements for low voltage power and lighting wiring. E. Section 28 08 00 - COMMISIONING OF ELECTRONIC SAFETY AND SECURITY SYST
6、EMS. Requirements for commissioning. 1.3 SUBMITTALS A. Submit in accordance with Section 28 05 00, COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY. B. Shop Drawings: 1. Clearly present enough information to determine compliance with drawings and specifications. 2. Include the location of syst
7、em grounding electrode connections and the routing of aboveground and underground grounding electrode conductors. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 28 05 26 - 2 C. Test Reports: Provide certified test reports of ground resistance.
8、 D. Certifications: Two weeks prior to final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/: 1. Certification that the materials and installation are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installati
9、on has been properly installed and tested. 1.4 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. American
10、 Society for Testing and Materials (ASTM): B1-07 Standard Specification for Hard-Drawn Copper Wire B3-07 Standard Specification for Soft or Annealed Copper Wire B8-04 Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft C. Institute of Electrical and Elect
11、ronics Engineers, Inc. (IEEE): 81-1983 IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System C2-07 National Electrical Safety Code D. National Fire Protection Association (NFPA): 70-11 National Electrical Code (NEC) 99-2005 Health Care Faciliti
12、es E. Underwriters Laboratories, Inc. (UL): 44-05 . Thermoset-Insulated Wires and Cables 83-08 . Thermoplastic-Insulated Wires and Cables 467-07 Grounding and Bonding Equipment 486A-486B-03 Wire Connectors PART 2 - PRODUCTS 2.1 GROUNDING AND BONDING CONDUCTORS A. Equipment grounding conductors shall
13、 be UL 83 insulated stranded copper, except that sizes 6 mm (10 AWG) and smaller shall be solid copper. Insulation color shall be continuous green for all equipment Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 28 05 26 - 3 grounding conducto
14、rs, except that wire sizes 25 mm (4 AWG) and larger shall be permitted to be identified per NEC. B. Bonding conductors shall be ASTM B8 bare stranded copper, except that sizes 6 mm (10 AWG) and smaller shall be ASTM B1 solid bare copper wire. 2.2 GROUND RODS A. Copper clad steel, 19 mm (3/4-inch) di
15、ameter by 3000 mm (10 feet) long, conforming to UL 467. B. Quantity of rods shall be as required to obtain the specified ground resistance. 2.3 SPLICES AND TERMINATION COMPONENTS A. Components shall meet or exceed UL 467 and be clearly marked with the manufacturer, catalog number, and permitted cond
16、uctor size(s).2.4 ground connections B. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected. C. Below Grade: Exothermic-welded type connectors. D. Above Grad
17、e: 1. Bonding Jumpers: Compression-type connectors, using zinc-plated fasteners and external tooth lockwashers. 2. Connection to Building Steel: Exothermic-welded type connectors. 3. Ground Busbars: Two-hole compression type lugs, using tin-plated copper or copper alloy bolts and nuts. 4. Rack and C
18、abinet Ground Bars: One-hole compression-type lugs, using zinc-plated or copper alloy fasteners. 5. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, pressure type with at least two bolts. a) Pipe Connectors: Clamp type, sized for pipe. 6. Welded Connectors: Exothermic-welding kits
19、 of types recommended by kit manufacturer for materials being joined and installation conditions. 2.4 EQUIPMENT RACK AND CABINET GROUND BARS A. Provide solid copper ground bars designed for mounting on the framework of open or cabinet-enclosed equipment racks with minimum dimensions of 4 mm thick by
20、 19 mm wide (3/8 inch x inch). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 28 05 26 - 4 2.5 GROUND TERMINAL BLOCKS A. At any equipment mounting location (e.g., backboards and hinged cover enclosures) where rack-type ground bars cannot be mo
21、unted, provide screw lug-type terminal blocks. SPEC WRITER NOTE: Include Standard Detail on drawings. Edit detail to suit project requirements. 2.6 SPLICE CASE GROUND ACCESSORIES A. Splice case grounding and bonding accessories shall be supplied by the splice case manufacturer when available. Otherw
22、ise, use 16 mm (6 AWG) insulated ground wire with shield bonding connectors. 2.7 COMPUTER ROOM GROUND A. Provide 50mm2 (1/0 AWG) bare copper grounding conductors bolted at mesh intersections to form an equipotential grounding grid. The equipotential grounding grid shall form a 600mm (24 inch) mesh p
23、attern. The grid shall be bonded to each of the access floor pedestals. 2.8 SECURITY CONTROL ROOM GROUND A. Provide 50mm2 (1/0 AWG) stranded copper grounding conductor(s) color coded with a green jacket, bolted at the Rooms Communications System Grounding Electrode Cooper Plate and circulate to each
24、 equipment rack ground buss bar through the wire management system. Connect each equipment rack, wire management systems cable tray, ladder, etc. to the circulating ground wire with a minimum 25mm2 (4AWG) stranded Cooper Wire, color coded with a green jacket. 1. Connect each equipment rack ground bu
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2805262011GROUNDINGANDBONDINGFORELECTRONICSAFETYANDSECURITYPDF

链接地址:http://www.mydoc123.com/p-1074998.html