VA 26 51 00-2009 INTERIOR LIGHTING.pdf
《VA 26 51 00-2009 INTERIOR LIGHTING.pdf》由会员分享,可在线阅读,更多相关《VA 26 51 00-2009 INTERIOR LIGHTING.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、4-09 26 51 00 - 1 SECTION 26 51 00 INTERIOR LIGHTING SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. Coordinate with drawing schedules. PART 1 - GENERAL 1.1 DESCRIPTION: This section
2、 specifies the furnishing, installation and connection of the interior lighting systems. 1.2 RELATED WORK /A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirement for seismic restraint for nonstructural Components./ B. Section 26 05 11, REQUIREMENTS FOR ELECTRI
3、CAL INSTALLATIONS: General requirements that are common to more than one section of Division 26. C. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and wiring. D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for perso
4、nnel safety and to provide a low impedance path to ground for possible ground fault currents. E. Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTA
5、LLATIONS. 1.4 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Product Data: For each type of lighting fixture (luminaire) designated on the LIGHTING FIXTURE SCHEDULE, arranged in order of fixture designation, submit the following
6、 information. 1. Material and construction details include information on housing, optics system and lens/diffuser. 2. Physical dimensions and description. 3. Wiring schematic and connection diagram. 4. Installation details. 5. Energy efficiency data. 6. Photometric data based on laboratory tests co
7、mplying with IESNA Lighting Measurements, testing and calculation guides. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 51 00 - 2 7. Lamp data including lumen output (initial and mean), color rendition index (CRI), rated life (hours) and co
8、lor temperature (degrees Kelvin). 8. Ballast data including ballast type, starting method, ambient temperature, ballast factor, sound rating, system watts and total harmonic distortion (THD). C. Manuals: 1. Submit, simultaneously with the shop drawings companion copies of complete maintenance and op
9、erating manuals including technical data sheets, and information for ordering replacement parts. 2. Two weeks prior to the final inspection, submit four copies of the final updated maintenance and operating manuals, including any changes, to the Resident Engineer. D. Certifications: 1. Two weeks pri
10、or to final inspection, submit four copies of the following certifications to the Resident Engineer: a. Certification by the Contractor that the equipment has been properly installed, adjusted, and tested. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revis
11、ions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. Institute of Electrical and Electronic Engineers (IEEE): C62.41-91 Guide on the Surge Environment in Low Voltage (1000V and less) AC Power Circui
12、ts C. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) 101 Life Safety Code D. National Electrical Manufacturers Association (NEMA): C82.1-97 . Ballasts for Fluorescent Lamps - Specifications C82.2-02 . Method of Measurement of Fluorescent Lamp Ballasts C82.4-02 . Bal
13、lasts for High-Intensity-Discharge and Low-Pressure Sodium Lamps C82.11-02 High Frequency Fluorescent Lamp Ballasts E. Underwriters Laboratories, Inc. (UL): 496-96 . Edison-Base Lampholders 542-99 . Lampholders, Starters, and Starter Holders for Fluorescent Lamps 844-95 . Electric Lighting Fixtures
14、for Use in Hazardous (Classified) Locations Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 51 00 - 3 924-95 . Emergency Lighting and Power Equipment 935-01 . Fluorescent-Lamp Ballasts 1029-94 High-Intensity-Discharge Lamp Ballasts 1029A-06Ig
15、nitors and Related Auxiliaries for HID Lamp Ballasts 1598-00 Luminaires 1574-04.Standard for Track Lighting Systems 2108-04.Standard for Low-Voltage Lighting Systems 8750-08.Light Emitting Diode (LED) Light Sources for Use in Lighting Products F. Federal Communications Commission (FCC): Code of Fede
16、ral Regulations (CFR), Title 47, Part 18 PART 2 - PRODUCTS 2.1 LIGHTING FIXTURES (LUMINAIRES) A. Shall be in accordance with NFPA 70 and UL 1598, as shown on drawings, and as specified. B. Sheet Metal: 1. Shall be formed to prevent warping and sagging. Housing, trim and lens frame shall be true, str
17、aight (unless intentionally curved) and parallel to each other as designed. 2. Wireways and fittings shall be free of burrs and sharp edges and shall accommodate internal and branch circuit wiring without damage to the wiring. 3. When installed, any exposed fixture housing surface, trim frame, door
18、frame and lens frame shall be free of light leaks; lens doors shall close in a light tight manner. 4. Hinged door closure frames shall operate smoothly without binding when the fixture is in the installed position, latches shall function easily by finger action without the use of tools. C. Ballasts
19、shall be serviceable while the fixture is in its normally installed position, and shall not be mounted to removable reflectors or wireway covers unless so specified. D. Lamp Sockets: 1. Fluorescent: Lampholder contacts shall be the biting edge type or phosphorous-bronze with silver flash contact sur
20、face type and shall conform to the applicable requirements of UL 542. Lamp holders for bi-pin lamps shall be of the telescoping compression type, or of the single slot entry type requiring a one-quarter turn of the lamp after insertion. 2. High Intensity Discharge (H.I.D.): Shall have porcelain encl
21、osures. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 51 00 - 4 E. Recessed fixtures mounted in an insulated ceiling shall be listed for use in insulated ceilings. F. Mechanical Safety: Lighting fixture closures (lens doors, trim frame, hin
22、ged housings, etc.) shall be retained in a secure manner by captive screws, chains, captive hinges or fasteners such that they cannot be accidentally dislodged during normal operation or routine maintenance. G. Metal Finishes: 1. The manufacturer shall apply standard finish (unless otherwise specifi
23、ed) over a corrosion resistant primer, after cleaning to free the metal surfaces of rust, grease, dirt and other deposits. Edges of pre-finished sheet metal exposed during forming, stamping or shearing processes shall be finished in a similar corrosion resistant manner to match the adjacent surface(
24、s). Fixture finish shall be free of stains or evidence of rusting, blistering, or flaking, and shall be applied after fabrication. 2. Interior light reflecting finishes shall be white with not less than 85 percent reflectances, except where otherwise shown on the drawing. 3. Exterior finishes shall
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2651002009INTERIORLIGHTINGPDF