VA 26 29 21-2010 DISCONNECT SWITCHES.pdf
《VA 26 29 21-2010 DISCONNECT SWITCHES.pdf》由会员分享,可在线阅读,更多相关《VA 26 29 21-2010 DISCONNECT SWITCHES.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 29 21 - 1 SECTION 26 29 21 DISCONNECT SWITCHES SPEC WRITE NOTE: Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, install
2、ation, and connection of low voltage disconnect switches. 1.2 RELATED WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. B. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS A
3、ND CABLES 600 VOLTS AND BELOW: Cables and wiring. C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground faults. D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for cables an
4、d wiring. E. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS: Motor rated toggle switches. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL
5、INSTALLATIONS. B. Shop Drawings: 1. Clearly present sufficient information to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, materials, enclosure types, and fuse types and classes. 3. Show the specific switch and fuse proposed for
6、each specific piece of equipment or circuit. C. Manuals: 1. Provide complete maintenance and operating manuals for disconnect switches, including technical data sheets, wiring diagrams, and information for ordering replacement parts. Deliver four copies to Provided by IHSNot for ResaleNo reproductio
7、n or networking permitted without license from IHS-,-,-09-10 26 29 21 - 2 the / Resident Engineer / COTR / two weeks prior to final inspection. 2. Terminals on wiring diagrams shall be identified to facilitate maintenance and operation. 3. Wiring diagrams shall indicate internal wiring and any inter
8、locking. D. Certifications: Two weeks prior to the final inspection, submit four copies of the following certifications to the /Resident Engineer/ /COTR/: 1. Certification by the manufacturer that the materials conform to the requirements of the drawings and specifications. 2. Certification by the c
9、ontractor that the materials have been properly installed, connected, and tested. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in th
10、e text by designation only. B. National Electrical Manufacturers Association (NEMA): FU l-07 Low Voltage Cartridge Fuses KS l-06 Enclosed and Miscellaneous Distribution Equipment Switches (600 Volts Maximum) C. National Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) D. Unde
11、rwriters Laboratories, Inc. (UL): 98-04 Enclosed and Dead-Front Switches 248-00 . Low Voltage Fuses 977-94 . Fused Power-Circuit Devices PART 2 - PRODUCTS 2.1 LOW VOLTAGE FUSIBLE SWITCHES RATED 600 AMPERES AND LESS A. In accordance with UL 98, NEMA KS1, and NEC. B. Shall have NEMA classification Gen
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2629212010DISCONNECTSWITCHESPDF