1、09-10 26 29 11 - 1 SECTION 26 29 11 MOTOR STARTERS SPEC WRITER NOTE: Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION All motor starters and variable speed motor cont
2、rollers, including installation and connection (whether furnished with the equipment specified in other Divisions or otherwise), shall meet these specifications. 1.2 RELATED WORK A. Other sections which specify motor driven equipment, except elevator motor controllers. /B. Section 13 05 41, SEISMIC
3、RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirements for seismic restraint for nonstructural components./ /C. Section 25 10 10, ADVANCED UTILITY METERING: For electricity metering installed in motor starters./ D. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General elec
4、trical requirements and items that are common to more than one Section of Division 26. E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. F. Section 26 24 19, MOTOR-CONTROL CENTE
5、RS and Section 26 24 21, MOTOR-CONTROL PANELBOARDS: For multiple motor control assemblies, which include motor starters. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05
6、 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, weights, mounting details, materials, running over current protection
7、, size of enclosure, over Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 29 11 - 2 current protection, wiring diagrams, starting characteristics, interlocking and accessories. C. Manuals: 1. Submit, simultaneously with the shop drawings, co
8、mpanion copies of complete maintenance and operating manuals, including technical data sheets, wiring diagrams and information for ordering replacement parts. a. Wiring diagrams shall have their terminals identified to facilitate installation, maintenance and operation. b. Wiring diagrams shall indi
9、cate internal wiring for each item of equipment and interconnections between the items of equipment. c. Elementary schematic diagrams shall be provided for clarity of operation. 2. Two weeks prior to the project final inspection, submit four copies of the final updated maintenance and operating manu
10、al to the Resident Engineer. D. Certification: Two weeks prior to final inspection, unless otherwise noted, submit four copies of the following certifications to the Resident Engineer: 1. Certification that the equipment has been properly installed, adjusted, and tested. 2. Certification by the manu
11、facturer that medium voltage motor controller(s) conforms to the requirements of the drawings and specifications. This certification must be furnished to the Resident Engineer prior to shipping the controller(s) to the job site. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including ame
12、ndments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation only. B. Institute of Electrical and Electronic Engineers (IEEE): 519 Recommended Practices and Requirements for Harmonic Cont
13、rol in Electrical Power Systems C37.90.1 . Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems C. National Electrical Manufacturers Association (NEMA): ICS 1 Industrial Control and Systems General Requirements ICS 1.1 Safety Guidelines for the Application, Install
14、ation and Maintenance of Solid State Control Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 29 11 - 3 ICS 2 Industrial Control and Systems, Controllers, Contactors and Overload Relays Rated 600 Volts DC ICS 6 Industrial Control and Systems
15、Enclosures ICS 7 Industrial Control and Systems Adjustable-Speed Drives ICS 7.1 Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems D. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) E. Underwriters
16、Laboratories Inc. (UL): 508 Industrial Control Equipment PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. 2.1 MOTOR STARTERS, GENERAL A. Sh
17、all be in accordance with the requirements of the IEEE, NEC, NEMA (ICS 1, ICS 1.1, ICS 2, ICS 6, ICS 7 and ICS 7.1) and UL. B. Shall have the following features: 1. Separately enclosed unless part of another assembly. 2. Circuit breakers and safety switches within the motor controller enclosures sha
18、ll have external operating handles with lock-open padlocking provisions and shall indicate the ON and OFF positions. 3. Motor control circuits: a. Shall operate at not more than 120 volts. b. Shall be grounded except as follows: 1) Where isolated control circuits are shown. 2) Where manufacturers of
19、 equipment assemblies recommend that the control circuits be isolated. c. Incorporate a separate, heavy duty, control transformer within each motor controller enclosure to provide the control voltage for each motor operating over 120 volts. d. Incorporate over current protection for both primary and
20、 secondary windings of the control power transformers in accordance with the NEC. 4. Overload current protective devices: /a. Overload relay (thermal or induction type. / Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 29 11 - 4 /b. Overload
21、 relay (solid state type. / c. One for each pole. d. Manual reset on the door of each motor controller enclosure. e. Correctly sized for the associated motors rated full load current. f. Check every motor controller after installation and verify that correct sizes of protective devices have been ins
22、talled. g. Deliver four copies of a summarized list to the Resident Engineer, which indicates and adequately identifies every motor controller installed. Include the catalog numbers for the correct sizes of protective devices for the motor controllers. 5. Hand-Off-Automatic (H-O-A) switch is require
23、d unless specifically stated on the drawings as not required for a particular starter. H-O-A switch is not required for manual motor starters. 6. Incorporate into each control circuit a 120-volt, solid state time delay relay (ON delay), minimum adjustable range from 0.3 to 10 minutes, with transient
24、 protection. Time delay relay is not required where H-O-A switch is not required. 7. Unless noted otherwise, equip with not less than two normally open and two normally closed auxiliary contacts. Provide green run pilot lights and H-O-A control devices as indicated, operable at front of enclosure wi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2629112010MOTORSTARTERSPDF