1、4-09 26 27 26 - 1 SECTION 26 27 26 WIRING DEVICES SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation
2、 and connection of wiring devices. 1.2 RELATED WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section of Division 26. B. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits and outlets boxes. C. S
3、ection 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and wiring. D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents. 1.3 QUA
4、LITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Sufficient information, clearly presented, s
5、hall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, construction materials, grade and termination information. C. Manuals: Two weeks prior to final inspection, deliver four copies of the following to the Resident Eng
6、ineer: Technical data sheets and information for ordering replacement units. D. Certifications: Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: Certification by the Contractor that the devices comply with the drawings and specifications, and have be
7、en properly installed, aligned, and tested. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 27 26 - 2 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of t
8、his specification to the extent referenced. Publications are referenced in the text by basic designation only. B. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) C. National Electrical Manufacturers Association (NEMA): WD 1 . General Color Requirements for Wiring Dev
9、ices WD 6 Wiring Devices Dimensional Requirements D. Underwriters Laboratories, Inc. (UL): 5 Surface Metal Raceways and Fittings 20 . General-Use Snap Switches 231 Power Outlets 467 Grounding and Bonding Equipment 498 Attachment Plugs and Receptacles 943 Ground-Fault Circuit-Interrupters PART 2 - PR
10、ODUCTS SPEC WRITER NOTE: Refer to the Electrical Design Manual for locations in which to install hospital-grade receptacles, and standard receptacles. Clearly indicate the requirements on the drawings. 2.1 RECEPTACLES A. General: All receptacles shall be listed by Underwriters Laboratories, Inc., an
11、d conform to NEMA WD 6. 1. Mounting straps shall be plated steel, with break-off plaster ears and shall include a self-grounding feature. Terminal screws shall be brass, brass plated or a copper alloy metal. 2. Receptacles shall have provisions for back wiring with separate metal clamp type terminal
12、s (four min.) and side wiring from four captively held binding screws. B. Duplex Receptacles: Hospital-grade, single phase, 20 ampere, 120 volts, 2-pole, 3-wire, and conform to the NEMA 5-20R configuration in NEMA WD 6. The duplex type shall have break-off feature for two-circuit operation. The ungr
13、ounded pole of each receptacle shall be provided with a separate terminal. 1. Bodies shall be ivory in color. 2. Switched duplex receptacles shall be wired so that only the top receptacle is switched. The remaining receptacle shall be unswitched. 3. Duplex Receptacles on Emergency Circuit: Provided
14、by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 27 26 - 3 a. In rooms without emergency powered general lighting, the emergency receptacles shall be of the self-illuminated type. 4. Ground Fault Interrupter Duplex Receptacles: Shall be an integral uni
15、t, hospital-grade, suitable for mounting in a standard outlet box. a. Ground fault interrupter shall be consist of a differential current transformer, solid state sensing circuitry and a circuit interrupter switch. Device shall have nominal sensitivity to ground leakage current of five milliamperes
16、and shall function to interrupt the current supply for any value of ground leakage current above five milliamperes (+ or 1 milliamp) on the load side of the device. Device shall have a minimum nominal tripping time of 1/30th of a second. b. Ground Fault Interrupter Duplex Receptacles (not hospital-g
17、rade) shall be the same as ground fault interrupter hospital-grade receptacles except for the “hospital-grade” listing. 5. Safety Type Duplex Receptacles: a. Bodies shall be gray in color. 1) Shall permit current to flow only while a standard plug is in the proper position in the receptacle. 2) Scre
18、ws exposed while the wall plates are in place shall be the tamperproof type. 6. Duplex Receptacles (not hospital grade): Shall be the same as hospital grade duplex receptacles except for the “hospital grade“ listing and as follows. a. Bodies shall be brown phenolic compound supported by a plated ste
19、el mounting strap having plaster ears. C. Receptacles; 20, 30 and 50 ampere, 250 volts: Shall be complete with appropriate cord grip plug. Devices shall meet UL 231. SPEC WRITER NOTE: Specify type of receptacle. D. Weatherproof Receptacles: Shall consist of a duplex receptacle, mounted in box with a
20、 gasketed, weatherproof, cast metal cover plate and cap over each receptacle opening. The cap shall be permanently attached to the cover plate by a spring-hinged flap. The weatherproof integrity shall not be affected when heavy duty specification or hospital grade attachment plug caps are inserted.
21、Cover plates on outlet boxes mounted flush in the wall shall be gasketed to the wall in a watertight manner. E. TVSS Receptacles. Shall comply with NEMA WD 1, NEMA WD 6, UL 498, and UL 1449, with integral TVSS in line to ground, line to neutral, and neutral to ground. Provided by IHSNot for ResaleNo
22、 reproduction or networking permitted without license from IHS-,-,-4-09 26 27 26 - 4 1. TVSS Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 400 volts and minimum single transient pulse energy dissipation of 240 J, according to IEEE C62.41.2 and IEEE C62.45. 2. Activ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2627262009WIRINGDEVICESPDF