VA 26 26 00-2009 POWER DISTRIBUTION UNITS FOR UNINTERRUPTIBLE POWER SYSTEMS.pdf
《VA 26 26 00-2009 POWER DISTRIBUTION UNITS FOR UNINTERRUPTIBLE POWER SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 26 26 00-2009 POWER DISTRIBUTION UNITS FOR UNINTERRUPTIBLE POWER SYSTEMS.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、4-09 26 26 00 - 1 SECTION 26 26 00 POWER DISTRIBUTION UNITS FOR UNINTERRUPTIBLE POWER SYSTEMS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This se
2、ction specifies the furnishing, installation and connection of freestanding, prepackaged, power distribution units for transforming, conditioning, and distributing electrical power for a Central Uninterruptible Power Supply (UPS). 1.2 RELATED WORK /A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS
3、 FOR NON-STRUCTURAL COMPONENTS: Requirement for seismic restraint for nonstructural Components./ B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. C. Section 26 05 21, LOW-VOLTAGE ELECTRI
4、CAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and Wiring. D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible fault currents. E. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEM
5、S: Conduct and outlet boxes. F. Section 26 32 53, CENTRAL UNINTERRUPIBLE POWER SUPPY: Power source for power distribution units. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 FACTORY TESTS Power distribution units shall
6、be thoroughly tested at the factory to assure that there are no electrical or mechanical defects. Tests shall be conducted as per UL and ANSI Standards. Factory tests shall be certified. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 26 00 -
7、 2 1.5 SUBMITTALS Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: A. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and specifications. 2. Include electrical ratings, dimensions, mounting det
8、ails, materials, required clearances, terminations, weight, temperature rise, wiring and connection diagrams, plan, front, side, and rear elevations, accessories, and device nameplate data. B. Manuals: 1. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and ope
9、rating manuals including technical data sheets, wiring diagrams, and information for ordering replacement parts. a. Wiring diagrams shall have their terminals identified to facilitate installation, maintenance, and operation. b. Wiring diagrams shall indicate internal wiring for each item of equipme
10、nt and the interconnection between the items of equipment. c. Provide a clear and concise description of operation, which gives, in detail, the information required to properly operate the equipment. d. Approvals will be based on complete submissions of manuals together with shop drawings. 2. Two we
11、eks prior to final inspection, deliver four copies of the final updated maintenance and operating manuals to the Resident Engineer. a. The manuals shall be updated to include any information necessitated by shop drawing approval. b. Complete “As Installed“ wiring and schematic diagrams shall be incl
12、uded which show all items of equipment and their interconnecting wiring. c. Show all terminal identification. d. Include information for testing, repair, trouble shooting, assembly, disassembly, and recommended maintenance intervals. e. Provide a replacement parts list with current prices. Include a
13、 list of recommended spare parts, tools, and instruments for testing and maintenance purposes. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 26 00 - 3 f. Furnish manuals in loose-leaf binder or manufacturers standard binder. C. Certificatio
14、ns: 1. Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: a. Certification by the Contractor that the assemblies have been properly installed, adjusted and tested. b. Certified copies of all of the factory design and production tests, field test data s
15、heets and reports for the assemblies. 1.6 APPLICABLE PUBLICATIONS Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. A. National Fire Pro
16、tection Association (NFPA): 70 . National Electrical Code (NEC) 70E Standard for Electrical Life Safety in the Workplace B. National Electrical Manufacturers Association (NEMA): ST 20.Dry-Type Transformers for General Applications PB-1 . Panelboards AB-1 . Molded Case Circuit Breakers, Molded Case S
17、witches and Circuit Breaker Enclosures C. Underwriters Laboratories, Inc. (UL): 50 . Enclosures for Electrical Equipment 67 . Panel boards 489 Molded Case Circuit Breakers and Circuit Breaker Enclosures PART 2 - PRODUCTS 2.1 GENERAL A. Assembly of power line-conditioning and distribution components
18、packaged in a single cabinet or modular assembly of cabinets. Include the following components: 1. Input-power, circuit-breaker section. 2. Isolation transformer. 3. TVSS system. 4. Output panelboard(s). 5. Alarm, monitoring, and control system. Provided by IHSNot for ResaleNo reproduction or networ
19、king permitted without license from IHS-,-,-4-09 26 26 00 - 4 B. Unit shall carry indicated rms kilovolt-ampere load continuously without exceeding rated insulation temperature for the following input voltage and load current: 1. Input Voltage: Within rated input-voltage tolerance band of unit. 2. L
20、oad Current: Maximum of 3.0 crest factor. 2.2 INPUT CIRCUIT BREAKER SECTION A. 3-pole, shunt-tripped, /thermal-magnetic-type / /electronic-trip /circuit breaker, rated for indicated interrupting capacity and 125 percent of input current of unit at 100 percent rated load. 1. Dual-Input Units: a. Two
21、input circuit breakers arranged to provide transfer between two input-voltage sources. b. Controls and interfaces to allow both open- and closed-transition transfer between two input-voltage sources. 2.3 ISOLATION TRANSFORMER SECTION A. Dry-type, electrostatically shielded, three-phase, common-core,
22、 convection-air-cooled isolation transformer. 1. Comply with UL 1561. 2. Cores: Grain-oriented, non-aging silicon steel, one leg per phase. 3. Coil Material and Insulation: Copper windings with a 220 deg C insulation class. 4. Temperature Rise: Designed for 80 deg C rise above 40 deg C ambient. 5. O
23、utput Impedance: 3.5 plus or minus 0.5 percent. 6. Regulation: 2 to 4 percent maximum, at full-resistive load; 5 percent maximum, at rated nonlinear load. 7. K-factor: /K1/ /K13/ /K20/. 8. Taps: 6 full-capacity compensation taps at 2.5 percent increments; 2 above and 4 below nominal voltage. 9. Full
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2626002009POWERDISTRIBUTIONUNITSFORUNINTERRUPTIBLEPOWERSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074965.html