VA 26 25 11-2009 BUSWAYS.pdf
《VA 26 25 11-2009 BUSWAYS.pdf》由会员分享,可在线阅读,更多相关《VA 26 25 11-2009 BUSWAYS.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、4-09 26 25 11 - 1 SECTION 26 25 11 BUSWAYS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation and co
2、nnection of the busways to form a complete coordinated system. 1.2 RELATED WORK A. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of time rated construction. /B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirement for sei
3、smic restraint for nonstructural components./ C. Section 07 92 00, JOINT SEALANTS: Sealing around busway penetrations through the building envelope to prevent moisture migration into the building. D. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that ar
4、e common to more than one section of Division 26. E. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Sectio
5、n 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance with drawings and s
6、pecifications. 2. Include electrical ratings, dimensions, mounting details and position, mounting method, vertical supports, materials, fire stops, weather stops, and layout of the busway runs. 3. Show the detailed coordinated connections to equipment terminations such as switchgear, switchboards, t
7、ransformers and panelboards. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 25 11 - 2 4. Coordination Drawings: Submit floor plans and sections, drawn to scale. Include bus-assembly layouts and relationships between components and adjacent s
8、tructural, mechanical, and electrical elements. Indicate the following: a. Vertical and horizontal enclosed bus-assembly runs, offsets, and transitions. b. Clearances for access above and to the side of enclosed bus assemblies. Indicate sufficient clearance for tightening connections c. Vertical ele
9、vation of enclosed bus assemblies above the floor or bottom of structure. d. Support locations, type of support, and weight on each support. C. Manuals: 1. Provide complete maintenance and operating manuals including technical data sheets, and information for ordering replacement parts. 2. Two weeks
10、 prior to the final inspection, submit four copies of the manuals to the Resident Engineer. D. Certifications: Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: 1. Certification that the equipment has been properly installed, adjusted, and tested. 1.5
11、 APPLICABLE PUBLICATIONS Publications listed below (including amendments, addenda, revisions, supplement and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. A. Underwriters Laboratories Inc. (UL): 857 Busways
12、B. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) C. National Electrical Manufacturers Association (NEMA): BU 1 . Busways BU 1.1 . General Instructions for Handling, Installation, Operation and Maintenance of Busway Rated 600 Volts or Less BU 1.2 . Application Infor
13、mation for Busway Rated 600 Volts or Less Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 25 11 - 3 PART 2 - PRODUCTS 2.1 MATERIAL A. Busway shall be in accordance with UL 857 and NEMA BU 1, BU 1.1 and BU 1.2. B. Busway shall be rated as show
14、n on the drawings for the positions in which they are being installed, and have the following features: SPEC WRITER NOTE: Insure that the drawings show the type of busway desired for indoor use, feeder type or plug-in type. 1. For indoor locations, they shall be totally enclosed, low impedance type
15、and moisture resistant. 2. For outdoor locations, they shall be totally enclosed, low impedance, weatherproof, outdoor feeder type only. 3. Ratings shall not be less than required by the NEC and NEMA BU 1 and not less than shown on the drawings. Short circuit current ratings shall not be less than 4
16、2,000 amps, as required by NEMA BU 1 or as required for the available fault current shown on the drawings, whichever is higher. 4. Busway shall be 3-phase, 4-wire, full neutral except where 3-phase, 3-wire is shown on the drawings. 5. Busway shall include an internal ground bus bar, not less than 50
17、 percent of the phase bus. 6. All bus bars for each busway shall be within a single housing. Paralleled or multiple busways will not be accepted. 7. Bus Bars: a. Shall be full round edge rectangular 98% IACS (International Annealed Copper Standard) copper of sufficient cross-section to provide full
18、current rating without exceeding a hot spot temperature rise of 65 C in a 40 C ambient. b. Bus bar and interconnection joints shall be silver plated, constant high-pressure type with high strength, copper silicon alloy bolts, nuts and washers. c. Shall be completely insulated with flame-retardant, t
19、rack-resistant, self-extinguishing insulation. d. Temperature rises shall not exceed NEMA Standards. 8. Housings: a. Shall be /steel/ /aluminum/ with continuous mounting rails. b. Bus bar assemblies and housing shall be products of the same manufacturer. c. Shall be thoroughly cleaned and painted at
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2625112009BUSWAYSPDF