1、09-10 26 09 23 - 1 SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. Coordinate with drawing schedules. 2. Provide a room control, room illuminati
2、on, and controlled-time schedule on the drawings, indicating photo- and occupancy-sensor detection coverage and light levels, as well as on and off periods for zones of lighting controlled. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation and connection of the lig
3、hting controls. 1.2 RELATED WORK A. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Interface of lighting controls with HVAC control systems. B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General requirements that are common to more than one section of Division 26. C. Sec
4、tion 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Cables and wiring. D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents. E. Sectio
5、n 24 26 16, PANELBOARDS: panelboard enclosure and interior bussing used for lighting control panels. F. Section 26 27 26, WIRING DEVICES: Wiring devices used for control of the lighting systems. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICA
6、L INSTALLATIONS. 1.4 SUBMITTALS A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Product Data: For each type of lighting control, submit the following information. 1. Manufacturers catalog data. 2. Wiring schematic and connection diagram. Pr
7、ovided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 09 23 - 2 3. Installation details. C. Manuals: 1. Submit, simultaneously with the shop drawings companion copies of complete maintenance and operating manuals including technical data sheets, and
8、 information for ordering replacement parts. 2. Two weeks prior to the final inspection, submit four copies of the final updated maintenance and operating manuals, including any changes, to the Resident Engineer. D. Certifications: 1. Two weeks prior to final inspection, submit four copies of the fo
9、llowing certifications to the Resident Engineer: a. Certification by the Contractor that the equipment has been properly installed, adjusted, and tested. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this s
10、pecification to the extent referenced. Publications are referenced in the text by designation only. B. Green Seal (GS): GC-12 Occupancy Sensors C. Illuminating Engineering Society of North America (IESNA): IESNA LM-48 . Guide for Calibration of Photoelectric Control Devices D. National Electrical Ma
11、nufacturers Association (NEMA) C136.10 American National Standard for Roadway Lighting Equipment-Locking-Type Photocontrol Devices and Mating Receptacles - Physical and Electrical Interchangeability and Testing ICS-1 Standard for Industrial Control and Systems General Requirements ICS-2 Standard for
12、 Industrial Control and Systems: Controllers, Contractors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment ICS-6 Standard for Industrial Controls and Systems Enclosures E. Underwriters Laboratories, Inc. (UL):
13、 20 . Standard for General-Use Snap Switches 773 Standard for Plug-In Locking Type Photocontrols for Use with Area Lighting Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 09 23 - 3 773A . Nonindustrial Photoelectric Switches for Lighting Co
14、ntrol 98 . Enclosed and Dead-Front Switches 917.Clock Operated Switches PART 2 - PRODUCTS 2.1 ELECTRONIC TIME SWITCHES A. Electronic, solid-state programmable units with alphanumeric display; complying with UL 917. 1. Contact Configuration: /SPST/ /DPST/ /DPDT/. 2. Contact Rating: /30-A inductive or
15、 resistive, 240-V ac/ /20-A ballast load, 120/240-V ac/. 3. Astronomical Clock: Capable of switching a load on at sunset and off at sunrise, and automatically changing the settings each day in accordance with seasonal changes of sunset and sunrise. Additionally, it shall be programmable to a fixed o
16、n/off weekly schedule. 4. Battery Backup: For schedules and time clock. 2.2 ELECTROMECHANICAL-DIAL TIME SWITCHES A. Electromechanical-dial time switches; complying with UL 917. 1. Contact Configuration: /SPST/ /DPST/ /DPDT/. 2. Contact Rating: /30-A inductive or resistive, 240-V ac/ /20-A ballast lo
17、ad, 120/240-V ac/. 3. Wound-spring reserve carryover mechanism to keep time during power failures. 2.3 OUTDOOR PHOTOELECTRIC SWITCHES A. Solid state, with /SPST/ /DPST/ dry contacts rated for 1800 VA tungsten or 1000 VA inductive, complying with UL 773A. 1. Light-Level Monitoring Range: 1.5 to 10 fc
18、 16.14 to 108 lx, with adjustable turn-on and turn-off levels. 2. Time Delay: 15-second minimum. 3. Surge Protection: Metal-oxide varistor. 4. Mounting: Twist lock, with base-and-stem mounting or stem-and-swivel mounting accessories as required. 2.4 TIMER SWITCHES A. Digital switches with backlit LC
19、D display, 120/277 volt rated, fitting as a replacement for standard wall switches. 1. Compatibility: Compatible with all ballasts. 2. Warning: Audible warning to sound during the last minute of “on” operation. 3. Time-out: Adjustable from 5 minutes to 12 hours. Provided by IHSNot for ResaleNo repro
20、duction or networking permitted without license from IHS-,-,-09-10 26 09 23 - 4 4. Faceplate: Refer to wall plate material and color requirements for toggle switches, as specified in Section 26 27 26, WIRING DEVICES. 2.5 CEILING-MOUNTED PHOTOELECTRIC SWITCHES A. Solid-state, light-level sensor unit,
21、 with separate relay unit. 1. Sensor Output: Contacts rated to operate the associated relay. Sensor shall be powered from the relay unit. 2. Relay Unit: Dry contacts rated for 20A ballast load at 120V and 277V, for 13A tungsten at 120V, and for 1 hp at 120V. 3. Monitoring Range: /10 to 200 fc 108 to
22、 2152 lx/ /100 to 1000 fc 1080 to 10 800 lx/, with an adjustment for turn-on and turn-off levels. 4. Time Delay: Adjustable from 5 to 300 seconds, with deadband adjustment. 5. Indicator: Two LEDs to indicate the beginning of on-off cycles. 2.6 SKYLIGHT PHOTOELECTRIC SENSORS A. Solid-state, light-lev
23、el sensor; housed in a threaded, plastic fitting for mounting under skylight; with separate relay unit. 1. Sensor Output: Contacts rated to operate the associated relay, complying with UL 773A. Sensor shall be powered from the relay unit. 2. Relay Unit: Dry contacts rated for 20A ballast load at 120
24、V and 277V, for 13A tungsten at 120V, and for 1 hp at 120V. 3. Monitoring Range: 1000 to 10,000 fc 10,800 to 108,000 lx, with an adjustment for turn-on and turn-off levels. 4. Time Delay: Adjustable from 5 to 300 seconds, with deadband adjustment. 5. Indicator: Two LEDs to indicate the beginning of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2609232010LIGHTINGCONTROLSPDF