VA 26 05 39-2009 UNDERFLOOR RACEWAYS FOR ELECTRICAL SYSTEMS.pdf
《VA 26 05 39-2009 UNDERFLOOR RACEWAYS FOR ELECTRICAL SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 26 05 39-2009 UNDERFLOOR RACEWAYS FOR ELECTRICAL SYSTEMS.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、4-09 26 05 39 - 1 SECTION 26 05 39 UNDERFLOOR RACEWAYS FOR ELECTRICAL SYSTEMS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies
2、the furnishing, installation, and connection of the underfloor ducts to form a complete, coordinated, grounded raceway system. 1.2 RELATED WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section of Division 26. B.
3、Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Wiring installed in the underfloor raceway system. C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path to ground for possib
4、le ground fault currents. D. Section 26 27 26, WIRING DEVICES: Wiring devices, installed as part of the underfloor raceway system. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. In accordance with Section 26
5、 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Identify components and accessories such as expansion-joint assemblies, straight raceway lengths, preset and afterset inserts, and service fittings. 2. Provide dimensions locating raceway header and distrib
6、ution elements. Include spacing between preset inserts and between preset inserts and ends of duct runs, walls, columns, junction boxes, and header duct connections. 3. Show connections between raceway elements and relationships between components and adjacent structural and architectural elements i
7、ncluding slab reinforcement, floor finish work, permanent partitions, and pre-tensioning or post-tensioning components. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 05 39 - 2 4. Indicate height of preset inserts, junction boxes, and racewa
8、ys coordinated with depth of concrete slab and floor fill. 5. Indicate thickening of slabs where required for adequate encasement of raceway components. 6. Show details of connections and terminations of underfloor raceways to conduits. C. As-built Drawings: 1. Deliver four sets of drawings to the R
9、esident Engineer /COTR/ showing the exact location of all underfloor ducts and junction boxes dimensioned from the centerline of columns. 2. Show the location and circuiting of all power service outlet fittings. 3. Show the location of all telephone and data service fittings. D. Manuals: 1. Provide
10、a complete description of the system and instructions as to allow additions to, and proper maintenance of the system. Instructions shall include information on locating and installing inserts of preset and afterset types. 2. Two weeks prior to final inspection, submit four copies of the manuals to t
11、he Resident Engineer. E. Certifications: 1. Two weeks prior to final inspection, submit four copies of the following to the Resident Engineer: 2. Certification that the materials are in accordance with the drawings specifications. 3. Certification that all materials have been properly installed. 1.5
12、 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. B. Underwriters Laboratories, Inc. (UL): 884 Un
13、derfloor Raceways and Fittings C. National Fire Protection Association (NFPA): 70 . National Electrical Code (NEC) PART 2 - PRODUCTS 2.1 RACEWAYS, UNDERFLOOR A. UL 884 shall apply. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-4-09 26 05 39 - 3 B.
14、Raceways: SPEC WRITER NOTE: Specify the physical size of the underfloor raceway. Include specifications for radiology suite trench duct. Raceway in MRI suites should be non-ferrous. 1. The duct shall have outside dimensions of / 3-1/8 inch 79mm x 1-1/4 inch 32mm x 6-1/2 inch 165mm x 1 1/2 inch 38mm
15、/ / /. 2. Preset inserts shall be spaced 24 inches 600mm on centers and shall not be less than 2-1/4 inches 58mm in diameter. 3. Shall not be less than No. 14 gage steel, continuously welded with corrosion resistant coating, inside and outside. 4. Shall have rounded corners. 5. Shall have vertical 9
16、0 degree elbows for upwall extension. 6. Shall have horizontal 90 degree and 45 degree elbows for turning corners. 7. Shall have all appurtenance for complete installation, such as blank washers, terminal bushings, end caps, etc. 8 Power and telecommunications raceways shall be separate, and shall h
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2605392009UNDERFLOORRACEWAYSFORELECTRICALSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074947.html