VA 26 05 36-2010 WIREWAYS FOR RADIOLOGY EQUIPMENT.pdf
《VA 26 05 36-2010 WIREWAYS FOR RADIOLOGY EQUIPMENT.pdf》由会员分享,可在线阅读,更多相关《VA 26 05 36-2010 WIREWAYS FOR RADIOLOGY EQUIPMENT.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 05 36 - 1 SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1- GENERAL 1.1 DESCRIPTION A. This section specifies the fur
2、nishing, installation, and connection of wireway systems for the radiology equipment. B. Radiology equipment and high voltage cables will be furnished by the Government. 1.2 RELATED WORK A. Section 13 49 00, RADIATION PROTECTION: Requirements for lead radiation shielding. B. Section 26 05 11, REQUIR
3、EMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section of Division 26. C. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits, fittings, and boxes for raceway systems. D. Section 26 05 39, UNDERFLOOR RACEWAYS FOR ELECTRICAL SYST
4、EMS: Under-floor raceway systems. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. B. Shop Drawings: 1. Clearly present su
5、fficient information to determine compliance with the drawings and specifications. 2. Show size and location of wireway components, feeders, panels and pullboxes, ductwork, and equipment provided by other trades, and radiology equipment items. Carefully coordinate with manufacturers shop drawings. S
6、hop drawing approval is required by the radiology equipment manufacturers technical representative prior to fabrication and installation of the wireway. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 36 - 2 C. Certifications: Two weeks p
7、rior to final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/: 1. Certification that the materials are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installation has been properly installed and tested. 3. Ce
8、rtification by the contractor that the radiology equipment manufacturers representative has approved the complete wireway installation. 1.5 APPLICABLE PUBLICATIONS Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by designa
9、tion only. A. National Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) 99-2005 Health Care Facilities B. Underwriters Laboratories, Inc. (UL): 884-2005 Underfloor Raceways and Fittings PART 2 - PRODUCTS 2.1 WIREWAY A. General 1. Factory fabricate, assemble, and fit. 2. Mater
10、ial shall be steel. SPEC WRITER NOTE: Edit paragraph below to conform with project requirements. 3. Size shall be /6 in 150 mm/ /12 in 305 mm/ /18 in 460 mm/ x 3.5 in 90 mm. 4. Coordinate dimensions of the straight lengths, elbows, junction boxes, and other components. 5. Hot-dipped galvanized steel
11、 connections joiner plates on floor and ceiling cable wireway. 6. Wireway bushings: a. Cast aluminum. b. Install when the radiology equipment is installed. c. Split ring-type bushed nipples for the high voltage cables. d. Smooth edges of the openings in the wireways for the bushings. Provided by IHS
12、Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 36 - 3 7. Provide chase nipples, dividers, elbows, tees, conduit entry fittings, and other accessories, fittings, and components, as required for a complete installation. 8. Protect cables at their egress
13、from the wireways by mechanically securing them with fittings to the wireways. 9. Provide 45 degrees sweep e1bow at every 90 degrees change in direction. Elbows shall have partitions. 10. Where gasketed openings are required in floor wall or ceiling wireways, provide split covers with fastening devi
14、ces on both sides of the cover. SPEC WRITER NOTE: Coordinate with other disciplines as to floor wireway covers needed. 2.2 FLOOR WIREWAY A. Wireways recessed in the floors or surface-mounted on the floors shall be watertight in accordance with UL 884. B. Sides and bottoms, 0.0747 in 2 mm minimum thi
15、ckness. C. Covers, 0.25 in 6 mm minimum thickness. Covers shall be bare, carpet-insert, or tile-insert to match the floor covering. D. Wireway covers shall be fully gasketed with screw fasteners. 2.3 WALL WIREWAY A. Wall wireway shall be recessed in the walls or surface-mounted on the walls, as requ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2605362010WIREWAYSFORRADIOLOGYEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-1074946.html