VA 26 05 33-2010 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.pdf
《VA 26 05 33-2010 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 26 05 33-2010 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、09-10 26 05 33 - 1 SECTION 26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS SPEC WRITER NOTE: Delete between /-/if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies
2、 the furnishing, installation, and connection of conduit, fittings, and boxes, to form complete, coordinated, grounded raceway systems. Raceways are required for all wiring unless shown or specified otherwise. B. Definitions: The term conduit, as used in this specification, shall mean any or all of
3、the raceway types specified. 1.2 RELATED WORK A. Section 06 10 00, ROUGH CARPENTRY: Mounting board for telephone closets. B. Section 07 60 00, FLASHING AND SHEET METAL: Fabrications for the deflection of water away from the building envelope at penetrations. C. Section 07 84 00, FIRESTOPPING: Sealin
4、g around penetrations to maintain the integrity of fire rated construction. D. Section 07 92 00, JOINT SEALANTS: Sealing around conduit penetrations through the building envelope to prevent moisture migration into the building. E. Section 09 91 00, PAINTING: Identification and painting of conduit an
5、d other devices. F. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and items that are common to more than one section of Division 26. G. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a lo
6、w impedance path for possible ground fault currents. H. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Underground conduits. I. Section 31 20 00, EARTH MOVING: Bedding of conduits. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INST
7、ALLATIONS. 1.4 SUBMITTALS In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 33 - 2 A. Manufacturers Literature and Data: Showing each cabl
8、e type and rating. The specific item proposed and its area of application shall be identified on the catalog cuts. B. Shop Drawings: 1. Size and location of main feeders. 2. Size and location of panels and pull-boxes. 3. Layout of required conduit penetrations through structural elements. C. Certifi
9、cations: 1. Two weeks prior to the final inspection, submit four copies of the following certifications to the /Resident Engineer/ /COTR/: a. Certification by the manufacturer that the material conforms to the requirements of the drawings and specifications. b. Certification by the contractor that t
10、he material has been properly installed. 1.5 APPLICABLE PUBLICATIONS A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. B. American N
11、ational Standards Institute (ANSI): C80.1-05 . Electrical Rigid Steel Conduit C80.3-05 . Steel Electrical Metal Tubing C80.6-05 . Electrical Intermediate Metal Conduit C. National Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) D. Underwriters Laboratories, Inc. (UL): 1-05 .
12、 Flexible Metal Conduit 5-04 . Surface Metal Raceway and Fittings 6-07 . Electrical Rigid Metal Conduit - Steel 50-95 Enclosures for Electrical Equipment 360-093 Liquid-Tight Flexible Steel Conduit 467-07 . Grounding and Bonding Equipment 514A-04 Metallic Outlet Boxes 514B-04 Conduit, Tubing, and Ca
13、ble Fittings 514C-96 Nonmetallic Outlet Boxes, Flush-Device Boxes and Covers 651-05 . Schedule 40 and 80 Rigid PVC Conduit and Fittings 651A-00 Type EB and A Rigid PVC Conduit and HDPE Conduit 797-07 . Electrical Metallic Tubing 1242-06 Electrical Intermediate Metal Conduit - Steel E. National Elect
14、rical Manufacturers Association (NEMA): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 33 - 3 TC-2-03 Electrical Polyvinyl Chloride (PVC) Tubing and Conduit TC-3-04 PVC Fittings for Use with Rigid PVC Conduit and Tubing FB1-07 . Fittings
15、, Cast Metal Boxes and Conduit Bodies for Conduit, Electrical Metallic Tubing and Cable PART 2 - PRODUCTS 2.1 MATERIAL A. Conduit Size: In accordance with the NEC, but not less than 0.5 in 13 mm unless otherwise shown. Where permitted by the NEC, 0.5 in 13 mm flexible conduit may be used for tap con
16、nections to recessed lighting fixtures. B. Conduit: 1. Rigid steel: Shall conform to UL 6 and ANSI C80.1. SPEC WRITER NOTE: Show on drawings the location that aluminum conduit is to be used. Remove if not required by project. /2. Rigid aluminum: Shall conform to UL 6A and ANSI C80.5./ 3. Rigid inter
17、mediate steel conduit (IMC): Shall conform to UL 1242 and ANSI C80.6. 4. Electrical metallic tubing (EMT): Shall conform to UL 797 and ANSI C80.3. Maximum size not to exceed 4 in 105 mm and shall be permitted only with cable rated 600 V or less. 5. Flexible galvanized steel conduit: Shall conform to
18、 UL 1. 6. Liquid-tight flexible metal conduit: Shall conform to UL 360. 7. Direct burial plastic conduit: Shall conform to UL 651 and UL 651A, heavy wall PVC or high density polyethylene (PE). 8. Surface metal raceway: Shall conform to UL 5. C. Conduit Fittings: 1. Rigid steel and IMC conduit fittin
19、gs: a. Fittings shall meet the requirements of UL 514B and NEMA FB1. b. Standard threaded couplings, locknuts, bushings, conduit bodies, and elbows: Only steel or malleable iron materials are acceptable. Integral retractable type IMC couplings are also acceptable. c. Locknuts: Bonding type with shar
20、p edges for digging into the metal wall of an enclosure. d. Bushings: Metallic insulating type, consisting of an insulating insert, molded or locked into the metallic body of the fitting. Bushings made entirely of metal or nonmetallic material are not permitted. Provided by IHSNot for ResaleNo repro
21、duction or networking permitted without license from IHS-,-,-09-10 26 05 33 - 4 e. Erickson (union-type) and set screw type couplings: Approved for use in concrete are permitted for use to complete a conduit run where conduit is installed in concrete. Use set screws of case-hardened steel with hex h
22、ead and cup point to firmly seat in conduit wall for positive ground. Tightening of set screws with pliers is prohibited. f. Sealing fittings: Threaded cast iron type. Use continuous drain-type sealing fittings to prevent passage of water vapor. In concealed work, install fittings in flush steel box
23、es with blank cover plates having the same finishes as that of other electrical plates in the room. SPEC WRITER NOTE: Edit paragraph below per project requirements. /2. Rigid aluminum conduit fittings: a. Standard threaded couplings, locknuts, bushings, conduit bodies, and elbows: Malleable iron, st
24、eel or aluminum alloy materials; Zinc or cadmium plate iron or steel fittings. Aluminum fittings containing more than 0.4% copper are prohibited. b. Locknuts and bushings: As specified for rigid steel and IMC conduit. c. Set screw fittings: Not permitted for use with aluminum conduit./ 3. Electrical
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2605332010RACEWAYANDBOXESFORELECTRICALSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074945.html