1、09-10 26 05 26 - 1 SECTION 26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS SPEC WRITER NOTE: Delete / _ / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. Insert additional provisions as required for this project.
2、PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies the general grounding and bonding requirements for electrical equipment and operations to provide a low impedance path for possible ground fault currents. B. “Grounding electrode system” refers to all electrodes required by NEC, as well as m
3、ade, supplementary, and lightning protection system grounding electrodes. C. The terms “connect” and “bond” are used interchangeably in this specification and have the same meaning. 1.2 RELATED WORK A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements and i
4、tems that are common to more than one section of Division 26. B. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Low Voltage power and lighting wiring. C. Section 26 13 00, MEDIUM-VOLTAGE SWITCHGEAR: Medium voltage distribution switchgear. D. Section 26 13
5、 13, GENERATOR PARALLELING CONTROLS: Generator paralleling controls. E. Section 26 18 41, MEDIUM-VOLTAGE SWITCHES: Medium voltage switches. F. Section 26 22 00, LOW-VOLTAGE TRANSFORMERS: Low voltage transformers. G. Section 26 23 00, LOW-VOLTAGE SWITCHGEAR: Low voltage switchgear. H. Section 26 24 1
6、1, DISTRIBUTION SWITCHBOARDS: Low voltage distribution switchboards. I. Section 26 24 16, PANELBOARDS: Low voltage panelboards. J. Section 26 24 19, MOTOR CONTROL CENTERS: Low voltage motor control centers. K. Section 26 24 21, MOTOR CONTROL PANELBOARDS: Low voltage motor control panelboards. L. Sec
7、tion 26 32 13, ENGINE-GENERATORS: Engine-generators. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 26 - 2 M. Section 26 36 23, AUTOMATIC TRANSFER SWITCHES: Automatic transfer switches. N. Section 26 41 00, FACILITY LIGHTNING PROTECTION:
8、 Requirements for lightning protection. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALIFICATIONS, in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. 1.4 SUBMITTALS A. Submit in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS. B. Shop Drawings: 1. Clearly pres
9、ent enough information to determine compliance with drawings and specifications. 2. Include the location of system grounding electrode connections and the routing of aboveground and underground grounding electrode conductors. C. Test Reports: Provide certified test reports of ground resistance. D. C
10、ertifications: Two weeks prior to final inspection, submit four copies of the following to the /Resident Engineer/ /COTR/: 1. Certification that the materials and installation are in accordance with the drawings and specifications. 2. Certification by the contractor that the complete installation ha
11、s been properly installed and tested. 1.5 APPLICABLE PUBLICATIONS Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by designation only. A. American Society
12、 for Testing and Materials (ASTM): B1-07 Standard Specification for Hard-Drawn Copper Wire B3-07 Standard Specification for Soft or Annealed Copper Wire B8-04 Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft B. Institute of Electrical and Electronics E
13、ngineers, Inc. (IEEE): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-10 26 05 26 - 3 81-1983 IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System C2-07 National Electrical Safety Code C. N
14、ational Fire Protection Association (NFPA): 70-08 National Electrical Code (NEC) 99-2005 Health Care Facilities D. Underwriters Laboratories, Inc. (UL): 44-05 . Thermoset-Insulated Wires and Cables 83-08 . Thermoplastic-Insulated Wires and Cables 467-07 Grounding and Bonding Equipment 486A-486B-03 W
15、ire Connectors PART 2 - PRODUCTS 2.1 GROUNDING AND BONDING CONDUCTORS A. Equipment grounding conductors shall be UL 44 or UL 83 insulated stranded copper, except that sizes No. 10 AWG 6 mm and smaller shall be solid copper. Insulation color shall be continuous green for all equipment grounding condu
16、ctors, except that wire sizes No. 4 AWG 25 mm and larger shall be identified per NEC. B. Bonding conductors shall be ASTM B8 bare stranded copper, except that sizes No. 10 AWG 6 mm and smaller shall be ASTM B1 solid bare copper wire. C. Conductor sizes shall not be less than shown on the drawings, o
17、r not less than required by the NEC, whichever is greater. SPEC WRITER NOTE: Remove the paragraph below if not required for the project. /D. Isolated Power System: Type XHHW-2 insulation with a dielectric constant of 3.5 or less./ 2.2 GROUND RODS A. Steel or copper clad steel, 0.75 in 19 mm diameter
18、 by 10 ft 30 M long, conforming to UL 467. B. Quantity of rods shall be as required to obtain the specified ground resistance, as shown on the drawings. 2.3 CONCRETE ENCASED ELECTRODE Concrete encased electrode shall be No. 4 AWG bare copper wire, installed per NEC. Provided by IHSNot for ResaleNo r
19、eproduction or networking permitted without license from IHS-,-,-09-10 26 05 26 - 4 2.4 MEDIUM VOLTAGE SPLICES AND TERMINATIONS Components shall meet or exceed UL 467 and be clearly marked with the manufacturer, catalog number, and permitted conductor size(s). 2.5 GROUND CONNECTIONS A. Below Grade:
20、Exothermic-welded type connectors. B. Above Grade: 1. Bonding Jumpers: Compression-type connectors, using zinc-plated fasteners and external tooth lockwashers. 2. Connection to Building Steel: Exothermic-welded type connectors. 3. Ground Busbars: Two-hole compression type lugs, using tin-plated copp
21、er or copper alloy bolts and nuts. 4. Rack and Cabinet Ground Bars: One-hole compression-type lugs, using zinc-plated or copper alloy fasteners. 2.6 EQUIPMENT RACK AND CABINET GROUND BARS Provide solid copper ground bars designed for mounting on the framework of open or cabinet-enclosed equipment ra
22、cks with minimum dimensions of 0.375 in 4 mm thick x 0.75 in 19 mm wide. 2.7 GROUND TERMINAL BLOCKS At any equipment mounting location (e.g., backboards and hinged cover enclosures) where rack-type ground bars cannot be mounted, provide screw lug-type terminal blocks. SPEC WRITER NOTE: Include Stand
23、ard Detail on drawings. Edit detail to suit project requirements. 2.8 GROUNDING BUS Pre-drilled rectangular copper bar with stand-off insulators, minimum 0.25 in 6.3 mm thick x 4 in 100 mm high in cross-section, length as shown on drawings, with 0.281 in 7.1 mm holes spaced 1.125 in 28 mm apart. PAR
24、T 3 - EXECUTION 3.1 GENERAL A. Ground in accordance with the NEC, as shown on drawings, and as specified herein. B. System Grounding: 1. Secondary service neutrals: Ground at the supply side of the secondary disconnecting means and at the related transformers. 2. Separately derived systems (transfor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2605262010GROUNDINGANDBONDINGFORELECTRICALSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074944.html