VA 23 82 00-2011 CONVECTION HEATING AND COOLING UNITS.pdf
《VA 23 82 00-2011 CONVECTION HEATING AND COOLING UNITS.pdf》由会员分享,可在线阅读,更多相关《VA 23 82 00-2011 CONVECTION HEATING AND COOLING UNITS.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、04-11 23 82 00 - 1 SECTION 23 82 00 CONVECTION HEATING AND COOLING UNITS SPEC WRITER NOTES: 1. Delete between/-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraph. 2. References to pressure in this section are gage pressure
2、 unless otherwise noted. PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Edit each of the following paragraphs as necessary to agree with products being used. Induction units, fan-coil units, radiant ceiling panels (for bathrooms), unit heaters, cabinet unit heaters, convectors and finned-tube ra
3、diation 1.2 RELATED WORK A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Seismic restraints for equipment. B. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General mechanical requirements and items, which are common to more than one section of Division 23. C. Sec
4、tion 23 05 41, NOISE and VIBRATION CONTROL FOR HVAC PIPING and EQUIPMENT: Noise requirements. D. Section 23 21 13, HYDRONIC PIPING: Heating hot water and chilled water piping. E. Section 23 31 00, HVAC DUCTS and CASINGS: Ducts and flexible connectors. F. Section 23 09 23, DIRECT-DIGITAL CONTROL SYST
5、EM FOR HVAC: Valve operators. G. Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC: Flow rates adjusting and balancing. H. Section 23 82 16, AIR COILS: Additional coil requirements. I. Section 23 08 00 COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checkl
6、ists, and training. J. Section 01 09 00 GENERAL COMMISSIONING REQUIREMENTS Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-04-11 23 82 00 - 2 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HV
7、AC. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Induction units. 2. Fan-Coil units. 3. Unit heaters. 4. Cabinet unit heaters. 5. Convectors. 6. Finned-tube radiation. 7. Radiant ceiling panels. C. Ce
8、rtificates: 1. Compliance with paragraph, QUALITY ASSURANCE. 2. Compliance with specified standards. D. Operation and Maintenance Manuals: Submit in accordance with paragraph, INSTRUCTIONS, in Section 01 00 00, GENERAL REQUIREMENTS. E. Completed System Readiness Checklists provided by the Commission
9、ing Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 23 08 00 COMMISSIONING OF HVAC SYSTEMS. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to th
10、e extent referenced. The publications are referenced in the text by the basic designation only. B. American National Standards Institute / Air Conditioning, Heating and Refrigeration Institute (ANSI/AHRI): 440-08 . Performance Rating of Room Fan Coils National Fire Protection Association (NFPA): 90A
11、-09 . Standard for the Installation of Air Conditioning and Ventilating Systems 70-11 National Electrical Code C. Underwriters Laboratories, Inc. (UL): 181-08 . Standard for Factory-Made Air Ducts and Air Connectors 1995-05 Heating and Cooling Equipment Provided by IHSNot for ResaleNo reproduction o
12、r networking permitted without license from IHS-,-,-04-11 23 82 00 - 3 1.6 GUARANTY In accordance with FAR clause 52.246-21 PART 2 - PRODUCTS 2.1 INDUCTION UNITS A. General: Induction units shall include an enclosure for cabinet models and casing for concealed models. Base unit shall include air ple
13、nums, air-discharge nozzles, air discharge grilles, recirculation grilles, water coil assembly, valve and piping package, condensate drain pan, and an adjustable air-balancing damper. Each unit shall be selected to produce the capacity shown on the drawings, without exceeding the specified static pr
14、essure. SPEC WRITER NOTE: Enclosure color to be selected and specified in consultation with the interior finish. B. Enclosure: Construct of galvanized steel minimum 1.3 mm (l8 gage), reinforced and braced. Front panel of enclosure shall be removable. Discharge grilles shall be adjustable and shall b
15、e of such design as to distribute air throughout the conditioned space. Plastic discharge and return grilles are not acceptable. Provide access doors for all piping and control compartments. Color of the enclosure shall be / /. C. Air Plenums: Construct air plenums of galvanized steel with interior
16、acoustically baffled and lined with sound absorbing materials that will attenuate the sound power from the primary air supply to the room. Lining shall be 13 mm (0.5 inch) thick (2.5 lb/ft3) density neoprene coates glass fiber. Heat-resistant nozzles shall be integral with or attached airtight to th
17、e plenum. Where coil induction units are supplied with vertical runouts, provide a streamlined, vaned, mitered elbow transition piece for connection between the unit and ductwork. Provide an adjustable air-balancing damper in each unit. DESIGNERS NOTE: See HVAC Design Manual Appendix 7-A Table 7-A1
18、for high humidity areas. D. Water Coils: Provide / single water coil. / dual water coils for heating and cooling. / Seamless copper tubing, with copper or aluminum fins, mechanically bonded or soldered to the tubes, suitable for 1378 kPa (200 psig) working pressure. Provide coil connections with no
19、less than 11 mm (7/16-inch) outside diameter flare or sweat connectors, accessory piping package with shut-off valves and terminal connections suitable for connection to the type of control valve supplied, and Provided by IHSNot for ResaleNo reproduction or networking permitted without license from
20、IHS-,-,-04-11 23 82 00 - 4 manual air vent. Test coils hydrostatically at 2067 kPa (300 psig) or under water at 1722 kPa (250 psig) air pressure. For all induction units in high humidity areas, provide factory-coated coils for protection from corrosion by using multiple stage electro-deposition coat
21、ing process. Refer to Drawings and Section 23 82 16, AIR COILS, for additional coil requirements. E. Provide easily accessible 25 mm (1 inch) thick throwaway type MERV 7 filters for each unit. F. Drain or Auxiliary Pans: Galvanized steel, watertight, and properly sized and located to collect all con
22、densed water dripping from any item within the unit enclosure. Provide drain connection when a condensate drain system is indicated. Connection shall be minimum 15 mm (l/2-inch) NPT. 2.2 ROOM FAN-COIL UNITS A. Capacity Certification: AHRI 440. B. Safety Compliance: NEC compliant and UL listed. C. No
23、ise Levels: Operating at full cooling capacity, sound power level shall not exceed by more than 5 dB the numerical value of sound pressure levels associated with noise criteria specified in Section 23 05 51, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. Select units at intermediate spee
24、d, for compliance with the noise criteria. D. Chassis: Galvanized steel, acoustically and thermally insulated to attenuate noise and prevent condensation. E. Cabinet: Minimum 1.3 mm (l8 gage) steel reinforced and braced. Arrange components and provide adequate space for installation of piping packag
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2382002011CONVECTIONHEATINGANDCOOLINGUNITSPDF

链接地址:http://www.mydoc123.com/p-1074937.html