1、04-11 23 81 43- 1 SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. This Section specifies electr
2、ically operated air-source unitary heat pumps. B. Definitions: 1. Coefficient of Performance (COP) - Cooling: The ratio of the rate of heat removed to the rate of energy input in consistent units, for a complete refrigerating system or some specific portion of that system under designated operating
3、conditions. 2. Coefficient of Performance (COP) - Heating: The ratio of the rate of heat delivered to the rate of energy input is consistent units for a complete heat pump system, including the compressor and, if applicable, auxiliary heat under designated operating conditions. 3. Energy Efficiency
4、Ratio (EER): The ratio of net cooling capacity is Btu/h to total rate of electricity input in watts under designated operating conditions. 4. Heating Seasonal Performance Factor (HSPF) - Total heating output of heat pump during its normal annual usage period for heating in Btu/h divided by total ele
5、ctric energy input in watts during the same period. 5. Seasonal Energy Efficiency Ratio (SEER) - Total cooling output of an air conditioner during its normal annual usage period for cooling in Btu/h divided by total electric energy input in watts during the same period. 6. Air-Source Unitary Heat Pu
6、mp: One or more factory made assemblies that normally include an indoor conditioning coil, compressor(s) and an outdoor refrigerant-to-air coil. These units provide both heating and cooling functions. 1.2 RELATED WORK A. Section 01 00 00, GENERAL REQUIREMENTS: For pre-test requirements. /B. Section
7、13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Seismic requirements for non-structural equipment./ Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-04-11 23 81 43- 2 C. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General m
8、echanical requirements and items, which are common to more than one section of Division 23. D. Section 23 23 00, REFRIGERANT PIPING: Requirements for field refrigerant piping. E. Section 23 31 00, HVAC DUCTS AND CASINGS: Requirements for sheet metal ductwork. F. Section 23 09 23, DIRECT-DIGITAL CONT
9、ROL SYSTEM FOR HVAC: Requirements for controls and instrumentation. G. Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC: Requirements for testing, adjusting and balancing of HVAC system. H. Section 23 08 00 COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness
10、checklists, and training. I. Section 01 91 00 GENERAL COMMISSIONING REQUIREMENTS 1.3 QUALITY ASSURANCE: A. Refer to specification Section 23 05 11, COMMON WORK RESULTS FOR HVAC B. Comply with ASHRAE Standard 15, Safety Code for Mechanical Refrigeration. C. Comply with ASHRAE Standard 90.1-2010, Ener
11、gy Standard for Buildings except Low-Rise Residential Buildings for cooling and heating performance requirements when tested in accordance with AHRI /210/240/AHRI 340/360/ and UL 1995. D. Heating Performance shall conform to ASHRAE requirements when tested in accordance with AHRI /210/240/AHRI 340/3
12、60/ and UL 1995. /E. Comply with requirements in Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS./ 1.4 SUBMITTALS A. Submit in accordance with specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data. 1. Air-Source
13、Unitary Heat pump: a. Packaged units b. Split system C. Certification: Submit, simultaneously with shop drawings, a proof of certification that this product has been certified by AHRI. D. Performance Rating: Submit catalog selection data showing equipment ratings and compliance with required cooling
14、 and heating capacities EER and COP values as applicable. E. Completed System Readiness Checklists provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-0
15、4-11 23 81 43- 3 and dated on the date of completion, in accordance with the requirements of Section 23 08 00 COMMISSIONING OF HVAC SYSTEMS. 1.5 APPLICABLE PUBLICATIONS: A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in th
16、e text by the basic designation only. B. Federal Specification (Fed. Spec.): A-A-50502-90 . Air-conditioner (UNITARY HEAT PUMP), AIR TO AIR (3000 TO 300,000 BTUH) C. Air-Conditioning Heating and Refrigeration Institute (AHRI) Standards: AHRI-DCPP Directory of Certified Product Performance - Applied
17、Directory of Certified Products 210/240-08 . Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment 270-08 . Sound Rating of Outdoor Unitary Equipment 310/380-04 . Standard for Packaged Terminal Air-Conditioners and Heat Pumps (CSA-C744-04) 340/360-07 . Commercial and Indu
18、strial Unitary Air-Conditioning and Heat Pump Equipment D. Air Movement and Control Association (AMCA): 210-07 . Laboratory Methods of Testing Fans for Aerodynamic Performance Rating (ANSI) 410-96 . Recommended Safety Practices for Users and Installers of Industrial and Commercial Fans E. American N
19、ational Standards Institute (ANSI): S12.51-02 (R2007) Acoustics - Determination of Sound Power Levels of Noise Sources Using Sound Pressure - Precision Method for Reverberation Rooms (same as ISO 3741:1999) F. American Society of Heating, Refrigerating and Air-Conditioning Engineers Inc (ASHRAE): 15
20、-10 Safety Standard for Refrigeration Systems (ANSI) 62.1-10 Ventilation for Acceptable Indoor Air Quality (ANSI) 90.1-07 Energy Standard for Buildings except Low-Rise Residential Buildings 2008 Handbook HVAC Systems and Equipment G. American Society of Testing and Materials (ASTM): B117-09 Standard
21、 Practice for Operating Salt Spray (Fog) Apparatus H. National Electrical Manufacturers Association (NEMA): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-04-11 23 81 43- 4 MG 1-09 (R2010) Motors and Generators (ANSI) ICS 1-00 (R2005) . Industrial C
22、ontrols and Systems: General Requirements I. National Fire Protection Association (NFPA): 90A-09 . Standard for the Installation of Air-Conditioning and Ventilating Systems J. Underwriters Laboratory (UL): 1995-05 Heating and Cooling Equipment PART II- PRODUCTS 2.1 UNITARY HEAT PUMPS, AIR TO AIR A.
23、Units shall comply with Fed Spec A-A-50502/Type I, having factory assembled refrigerant circuit or circuits (Packaged Unit), / Type II, (Split System) having remote outdoor section separate from indoor Section,/ Class 1, “Department of Energy“ (DOE) covered products (units with cooling capacity up t
24、o 65000 Btu/hr/ Class 2, NonDOE covered products (units with cooling capacity up to 300,000 Btu/hr /. 1. Unitary heat pumps shall bear the United States Environmental Protection Agency, Energy Star label and shall have a minimum Heating Season Performance Factor (HSPF) of /8 (Type I Packaged Unit),/
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2381432011AIRSOURCEUNITARYHEATPUMPSPDF