VA 21 10 00-2011 WATER-BASED FIRE-SUPPRESSION SYSTEMS.pdf
《VA 21 10 00-2011 WATER-BASED FIRE-SUPPRESSION SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 21 10 00-2011 WATER-BASED FIRE-SUPPRESSION SYSTEMS.pdf(22页珍藏版)》请在麦多课文档分享上搜索。
1、09-11 21 10 00 - 1 SECTION 21 10 00 WATER-BASED FIRE-SUPPRESSION SYSTEMS SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other items applicable in the section and renumber the paragraphs. 2. Use this section for fire pumps only. Use Section 21 12 00, FIRE-SUPPR
2、ESSION STANDPIPES / and / Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS for fire sprinklers. 3. The spec writer shall review the Physical Security Design Manual for VA Facilities to determine and include any Mission Critical or Life Safety requirements called out. PART 1 - GENERAL 1.1 DESCRIPTION A.
3、The design and installation of a hydraulically calculated automatic fire sprinkler system complete and ready for operation, for / the entire building / including the penthouse, mechanical equipment rooms, attic space, elevator machine rooms, elevator pits, linen and trash chutes, and accessible shaf
4、ts. B. The design and installation of a standpipe system combined with the sprinkler system. C. Installation of a new fire pump, / sized to meet the system flow and pressure per NFPA 14, NFPA 13 and NFPA 20 the latest editions / to provide / 430 kPa (65 psi) / 690 kPa (100 psi) / at the top of stand
5、pipe / and / sized to meet the sprinkler flow and pressure requirements./ D. Installation of new sectional valves in the sprinkler/standpipe system feed mains as indicated on the drawings. E. Modification of the existing / sprinkler / and /standpipe/ systems as indicated on the drawings./ Size syste
6、m by pipe schedule in accordance with NFPA 13 and NFPA 14 the latest editions./ F. Existing piping to be reused, replaced or removed as indicated on the drawings. Removal of piping to include all valves, flow switches, supervisory devices, hangers, supports, and associated fire alarm system conduit
7、and wire. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 21 10 00 - 2 G. Existing occupant-use hose racks, valves, and accessible piping to be disconnected from their supply, drained, removed, and all remaining inaccessible piping capped. H. R
8、eplacement of all existing sprinklers. Work to include all necessary piping modifications, new sprinklers and new sprinkler escutcheons. I. Provide access doors or panels where control or drain valves are located behind plaster or gypsum walls or ceilings as necessary to install piping above suspend
9、ed plaster or gypsum ceilings. J. Painting of exposed piping and supports to follow Section 09 91 00, PAINTING. 1.2 RELATED WORK A. Treatment of penetrations through rated enclosures: Section 07 84 00, FIRESTOPPING. B. Access panels for plaster ceilings: Section 08 31 13, ACCESS DOORS AND FRAMES. C.
10、 Painting of exposed pipe: Section 09 91 00, PAINTING. D. Section 21 05 11, COMMON WORK RESULTS FOR FIRE SUPPRESSION. E. Alarm Supervision: Section 28 31 00, FIRE DETECTION AND ALARM. F. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. 1.3 DESIGN CRITERIA A. The design, materials, equipme
11、nt, installation, inspection, and testing of the / automatic sprinkler system / standpipe system / and fire pump / shall be in accordance with the required advisory provisions of NFPA 13, 14, 20, 25, 75, 82, . / Exception to NFPA Fire Codes are as follows: 1. Standpipe system shall be sized to meet
12、volume requirements of NFPA 14 but not pressure requirements. 2. Sprinklers are not required in interstitial areas, except along AGV track systems if the vehicle is combustible. B. Base system design hydraulic calculations using the area/density method on the following criteria and in accordance wit
13、h NFPA 13 latest edition. 1. Sprinkler Protection: a. All patient care, sleeping, treatment, office, waiting areas, educational areas, dining areas, corridors and attics: Light hazard, (0.10 gpm/sq. ft.) over the hydraulically most remote 140 m2 (1500 sq. ft.). Provided by IHSNot for ResaleNo reprod
14、uction or networking permitted without license from IHS-,-,-09-11 21 10 00 - 3 b. Patient Sleeping Rooms/Areas: Sprinklers with a residential listing shall be installed in accordance with their listed flows and pressures. c. Kitchen, Mechanical Equipment Rooms, Transformer Rooms, Electrical Switchge
15、ar Rooms, Electric Closets, Elevator Shafts (if required), Elevator Machine Rooms, Refrigeration Service Rooms, and storage between 9 and 23 m (100 and 250 sq. ft.): Ordinary Hazard, Group 1, 6.1 L/minute/m (0.15 gpm/sq. ft.) over the hydraulically most remote 140 m (1500 sq. ft.). d. Clean and soil
16、ed linen rooms, trash rooms, clean and soiled utility rooms, laundry, laboratories, retail sales and storage rooms, storage room over 23 m (250 sq. ft.), boiler plants, loading docks, warehouse spaces, energy centers, Pharmacy and SPD areas: Ordinary Group 2, 8.1 L/minute/m (0.20 gpm/sq. ft.) over t
17、he hydraulically most remote 140 m (1500 sq. ft.). e. File Storage Areas with “Rolling Files” Racks: Ordinary Group 2 for the entire area of the space up to 140 m (1500 sq. ft.) area of sprinkler operation. f. Supply warehouse with storage height less than 3650 mm (12 ft. high): Ordinary Hazard Grou
18、p 2. Storage height exceeding 3650 mm (12 ft.), per NFPA 13 latest edition. g. Provide sprinklers in accessible shafts per NFPA 13 latest edition. h. Provide sprinklers in gravity type metal chutes per NFPA 82. 2. Add water allowance of 15 L/s (250 gpm) for inside and outside hose streams to the spr
19、inkler requirements at the connection to the distribution main. 3. Hydraulic Calculations: The calculated demand including hose stream requirements shall fall no less than 10 percent below the available supply curve. 4. Water Supply: a. Elevation of static and elevation of residual test gage: 600 mm
20、 (2 ft.) above site grade b. Static pressure: _ kPa (psi) c. Residual pressure: _ kPa (psi) d. Flow: _ L/s (gpm) e. Date:_ Time:_ Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 21 10 00 - 4 C. For each sprinkler zone provide a control valve, f
21、low switch, self-contained test, drain assembly and pressure gage. D. Provide a separate sprinkler valve for each traction elevator machine room and other areas as required by NFPA 13 latest edition. E. Provide a guard for each sprinkler in the janitors closets, the elevator machine room and sprinkl
22、ers within 2100 mm (7 ft.) of the floor and other areas as required by NFPA 13. F. Locate sprinklers in patient bedrooms assuming all privacy curtains have 13 mm (1/2 in.) openings in mesh extending 450 mm (18 in.) from ceiling. G. Seismic Protection: Seismically brace all new and existing piping sy
23、stems in accordance with Zone _ of NFPA 13 latest edition. 1.4 QUALIFICATIONS: A. Designers Qualifications: Design work and shop drawings shall be prepared by a licensed engineer practicing in the field of Fire Protection Engineering or a NICET (National Institute for Certification in Engineering Te
24、chnologies) Level III sprinkler technician. B. Installers Qualifications: The installer shall possess a valid State fire protection contractors license. The installer shall provide documentation of having successfully completed three projects of similar size and scope. C. On-site emergency service w
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2110002011WATERBASEDFIRESUPPRESSIONSYSTEMSPDF

链接地址:http://www.mydoc123.com/p-1074860.html