VA 14 24 11-2011 HYDRAULIC CARTLIFT.pdf
《VA 14 24 11-2011 HYDRAULIC CARTLIFT.pdf》由会员分享,可在线阅读,更多相关《VA 14 24 11-2011 HYDRAULIC CARTLIFT.pdf(36页珍藏版)》请在麦多课文档分享上搜索。
1、06-11 14 24 11-1 SECTION 14 24 11 HYDRAULIC CARTLIFT SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Delete items or paragraphs content not applicable and write “not used“ after title. PART 1-GENERAL 1.1 DESCRIPTION A. This section of the specification includes the engineering, fu
2、rnishing and installation of the complete hydraulic cartlift system as described herein and indicated on the Contract drawings. B. Items listed in the singular apply to each and every cartlift in this specification except where noted. C. Hydraulic Cartlift No. C- shall be oil hydraulic type with cen
3、tral station dispatching, signal system, car leveling device, power operated car and hoistway doors. 1.2 RELATED WORK A. Section 01 33 23 SPECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR 52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL CONDITIONS. B. Section 07 84 00, FIRESTOPPING: Seali
4、ng around penetrations to maintain the integrity of fire-rated construction. C. SECTION 09 06 00, SCHEDULE FOR FINISHES: As a master format for construction projects, to identify interior and exterior material finishes for type, texture, patterns, color and placement. D. Section 13 05 41, SEISMIC RE
5、STRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Requirements for seismic restraint of non-structural components. E. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section. F. Section 26 05 21, LOW-VOLTAGE ELECTRICAL P
6、OWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Low Voltage power and lighting wiring. G. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. H. Section 26 05 33, RACEWAY AND BOXES
7、 FOR ELECTRICAL SYSTEMS: Conduits for cables and wiring. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-06-11 14 24 11-2 I. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Requirements for installing the over-current protective devices
8、to ensure proper equipment and personnel protection. J. Section 26 22 00, LOW-VOLTAGE TRANSFORMERS: Low voltage transformers. K. Section 26 24 16, PANELBOARDS: Low voltage panelboards. L. Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION: Surge suppressors installed in panelboards. M. Section 26
9、 51 00, INTERIOR LIGHTING: Fixture and ballast type for interior lighting. 1.3 QUALIFICATIONS A. Approval by the Contracting Officer is required for products or services of proposed manufacturers, suppliers and installers and shall be contingent upon submission by Contractor of a certificate stating
10、 the following: 1. Elevator contractor is currently and regularly engaged in the installation of elevator equipment as one of his principal products. 2. Elevator contractor shall have three years of successful experience, trained supervisory personnel, and facilities to install elevator equipment sp
11、ecified herein. 3. The installers shall be Certified Elevator Mechanics with technical qualifications of at least five years of successful experience and Apprentices actively pursuing certified mechanic status. Certificates shall be submitted for all workers employed in this capacity. 4. Elevator co
12、ntractor shall submit a list of two or more prior hospital installations where all the cartlift equipment he proposes to furnish for this project has performed satisfactorily under conditions of normal hospital use. Provide a list of hospitals that have the equipment in operation for two years prece
13、ding the date of this specification. Provide the names and addresses of the Medical Centers and the names and telephone numbers of the Medical Center Administrators. B. Approval of Elevator Contractors equipment will be contingent upon their identifying an elevator maintenance service provider that
14、shall render services within / one hour / two hours / four hours / of receipt of notification, together with certification that the quantity and quality of replacement parts stock is sufficient to warranty continued operation of the elevator installation. Provided by IHSNot for ResaleNo reproduction
15、 or networking permitted without license from IHS-,-,-06-11 14 24 11-3 C. Approval will not be given to elevator contractors and manufacturers who have established on prior projects, either government, municipal, or commercial, a record for unsatisfactory elevator installations, have failed to compl
16、ete awarded contracts within the contract period, and does not have the requisite record of satisfactorily performing cartlift installations of similar type and magnitude. D. All hydraulic cartlifts shall be the product of the same manufacturer. E. The Contractor shall provide and install only those
17、 types of safety devices that have been subjected to tests witnessed and certified by an independent professional testing laboratory that is not a subsidiary of the firm that manufactures supplies or installs the equipment. F. Welding at the project site shall be made by welders and welding operator
18、s who have previously qualified by test as prescribed in American Welding Society Publications AWS Dl.1 to perform the type of work required. VAMC shall require welding certificates be submitted for all workers employed in this capacity. A welding or hot work permit is required for each day and shal
19、l be obtained from the COTR of safety department. Request permit one day in advance. G. Electrical work shall be performed by Licensed Electricians as requirements by NEC. Certificates shall be submitted for all workers employed in this capacity. 1.4 APPLICABLE PUBLICATIONS A. The publications liste
20、d below form a part of this specification. Cartlift installation shall meet the requirements of the latest editions published and adopted by the United States Department of Veterans Affairs on the date contract is signed. B. Federal Specifications (Fed. Spec.): J-C-30B Cable and Wire, Electrical (Po
21、wer, Fixed Installation) W-C-596F . Connector, Plug, Electrical; Connector, Receptacle, Electrical W-F-406E . Fittings for Cable, Power, Electrical and Conduit, Metal, Flexible HH-I-558C Insulation, Blankets, Thermal (Mineral Fiber, Industrial Type) W-F-408E . Fittings for Conduit, Metal, Rigid (Thi
22、ck- Wall and Thin-wall (EMT) Type) RR-W-410 . Wire Rope and Strand Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-06-11 14 24 11-4 TT-E-489J Enamel, Alkyd, Gloss, Low VOC Content QQ-S-766 Steel, Stainless and Heat Resisting, Alloys, Plate, Sheet and
23、 Strip C. International Building Code (IBC) D. American Society of Mechanical Engineers (ASME): A17.1 Safety Code for Elevators and Escalators A17.2 Inspectors Manual for Electric Elevators and Escalators E. National Fire Protection Association: NFPA 13Standard for the Installation of Sprinkler Syst
24、ems NFPA 70National Electrical Code (NEC) NFPA 72National Fire Alarm and Signaling Code NFPA 101.Life Safety Code NFPA 252.Fire Test of Door Assemblies F. Manufacturers Standardization Society of the Valve and Fittings Industry (MSS): SP-58 Pipe Hangers and Supports G. Society of Automotive Engineer
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1424112011HYDRAULICCARTLIFTPDF