1、05-11 14 24 00-1 SECTION 14 24 00 HYDRAULIC ELEVATORS SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Delete items or paragraphs content not applicable and write “not used“ after title. PART 1 GENERAL 1.1 DESCRIPTION A. This section specifies the engineering, furnishing, and insta
2、llation of the complete electric hydraulic elevator system as described herein and as indicated on the contract drawings. B. Items listed in the singular apply to each and every elevator in this specification except where noted. SPEC WRITER NOTE: Edit Subparagraphs C, D and E to suit the project. C.
3、 Passenger Elevators No. P-_, P-_, shall be oil hydraulic type with microprocessor based control, / two stop automatic operation / single car selective collective automatic operation / duplex selective collective automatic operation / and power-operated / single-speed / two-speed / side opening / ce
4、nter opening / car and hoistway doors. Elevators shall have Class “A” loading. D. Service Elevators No. S-_, S-_, shall be oil hydraulic type with microprocessor based control, / two stop automatic operation / single car selective collective automatic operation / duplex selective collective automati
5、c / and power operated / single-speed / two speed / side opening / center opening / car and hoistway doors. Elevators shall have Class / “A” / “C1” / “C2” / “C3” / loading. E. Freight Elevators number F-_, F-_, shall be oil hydraulic type with microprocessor based control, / two stop automatic opera
6、tion / single car selective collective automatic operation / duplex selective collective automatic operation / and / manually operated / power operated / vertical bi-parting hoistway doors and car gate. Elevator shall have Class / “C1” / “C2” / “C3” / loading. 1.2 RELATED WORK A. Section 01 33 23 SP
7、ECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR 52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL CONDITIONS. B. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-rated construction. Provided by IHSNot for ResaleNo reproduction or networking perm
8、itted without license from IHS-,-,-05-11 14 24 00-2 C. SECTION 09 06 00, SCHEDULE FOR FINISHES: As a master format for construction projects, to identify interior and exterior material finishes for type, texture, patterns, color and placement. D. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR
9、NON-STRUCTURAL COMPONENTS: Requirements for seismic restraint of non-structural components. E. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section. F. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLE
10、S (600 VOLTS AND BELOW): Low Voltage power and lighting wiring. G. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: Requirements for personnel safety and to provide a low impedance path for possible ground fault currents. H. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS:
11、Conduits for cables and wiring. I. Section 26 05 71, ELECTRICAL SYSTEM PROTECTIVE DEVICE STUDY: Requirements for installing the over-current protective devices to ensure proper equipment and personnel protection. J. Section 26 22 00, LOW-VOLTAGE TRANSFORMERS: Low voltage transformers. K. Section 26
12、24 16, PANELBOARDS: Low voltage panelboards. L. Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION: Surge suppressors installed in panelboards. M. Section 26 51 00, INTERIOR LIGHTING: Fixture and ballast type for interior lighting. N. VA Barrier Free Design Handbook (H-18-13) 1.3 QUALIFICATIONS A
13、. Approval by the Contracting Officer is required for products or services of proposed manufacturers, suppliers and installers and shall be contingent upon submission by Contractor of a certificate stating the following: 1. Elevator contractor is currently and regularly engaged in the installation o
14、f elevator equipment as one of his principal products. 2. Elevator contractor shall have three years of successful experience, trained supervisory personnel, and facilities to install elevator equipment specified herein. 3. The installers shall be Certified Elevator Mechanics with technical qualific
15、ations of at least five years of successful experience and Apprentices actively pursuing certified mechanic status. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 14 24 00-3 Certificates are required for all workers employed in this capacity.
16、4. Elevator contractor shall submit a list of two or more prior hospital installations where all the elevator equipment he proposes to furnish for this project functioned satisfactorily to serve varying hospital traffic and material handling demands. Provide a list of hospitals that have the equipme
17、nt in operation for two years preceding the date of this specification. Provide the names and addresses of the Medical Centers and the names and telephone numbers of the Medical Center Administrators. B. Approval of Elevator Contractors equipment will be contingent upon their identifying an elevator
18、 maintenance service provider that shall render services within / one hour / two hours / four hours / of receipt of notification, together with certification that the quantity and quality of replacement parts stock is sufficient to warranty continued operation of the elevator installation. C. Approv
19、al will not be given to elevator contractors and manufacturers who have established on prior projects, either government, municipal, or commercial, a record for unsatisfactory elevator installations, have failed to complete awarded contracts within the contract period, and does not have the requisit
20、e record of satisfactorily performing elevator installations of similar type and magnitude. D. All hydraulic elevators shall be the product of the same manufacturer. E. The Contractor shall provide and install only those types of safety devices that have been subjected to tests witnessed and certifi
21、ed by an independent professional testing laboratory that is not a subsidiary of the firm that manufactures supplies or installs the equipment. F. Welding at the project site shall be made by welders and welding operators who have previously qualified by test as prescribed in American Welding Societ
22、y Publications AWS Dl.1 to perform the type of work required. VAMC shall require welding certificates be submitted for all workers employed in this capacity. A welding or hot work permit is required for each day and shall be obtained from the COTR of safety department. Request permit one day in adva
23、nce. 1.4 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification. Elevator installation shall meet the requirements of the latest editions published and adopted by the United States Department of Veterans Affairs on the date contract is signed. Provided by IHSNot f
24、or ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 14 24 00-4 B. Federal Specifications (Fed. Spec.): J-C-30B Cable and Wire, Electrical (Power, Fixed Installation) W-C-596F . Connector, Plug, Electrical; Connector, Receptacle, Electrical W-F-406E . Fittings for Cabl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1424002011HYDRAULICELEVATORSPDF