1、07-11 13 49 00 - 1 SECTION 13 49 00 RADIATION PROTECTION SPEC WRITER NOTE: Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies lead radiation s
2、hielding. B. Construction of products and assemblies used for radiation shielding complying with applicable requirements of NCRP Reports 147 and 102. C. This section includes the following items: 1. Lead Lined Wood Doors 2. Lead Lined Shields 3. Lead Glass 4. Lead Lined Frames 5. Thresholds 6. Casse
3、tte Transfer Cabinets 7. Lead Louvers 8. Lead Lined Concrete Masonry Units 9. Lead Sheet 10. Lead Lined Plywood 11. Lead Lined Gypsum Lath 12. Lead Lined Gypsum Wallboard 1.2 RELATED WORK A. Masonry mortar: Section 04 20 00, UNIT MASONRY. B. Structural steel: Section 05 50 00, METAL FABRICATIONS. C.
4、 Wood Veneer finish for doors: Section 08 14 00, WOOD DOORS, and Section 09 06 00, SCHEDULE FOR FINISHES. D. Steel door frames: Section 08 11 13, HOLLOW METAL DOORS AND FRAMES. E. Hardware for doors: Section 08 71 00, DOOR HARDWARE. F. Installation of Doors and Hardware: Section 08 11 13, HOLLOW MET
5、AL DOORS AND FRAMES / Section 08 14 00, WOOD DOORS / Section 08 71 00, DOOR HARDWARE / /. 1.3 MANUFACTURERS QUALIFICATIONS A. Approval by Contracting Officer is required of product or service of proposed manufacturer and suppliers, and will be based upon submission by Contractor of certification tha
6、t: 1. Manufacturer regularly and presently manufactures lead radiation shielding as specified as one of its principal products. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-07-11 13 49 00 - 2 2. Manufacturers product submitted has been in satisfac
7、tory and efficient operation or three installations similar and equivalent to this project for three years. 3. Manufacturer submits list of installations. 1.4 TESTS A. Lead radiation shielding will be tested at the expense of the Government after X-ray equipment is installed. B. Any additional testi
8、ng required due to correction and replacement of defective work will be done by the Government at Contractors expense. NOTE: Lead glass, lead lined concrete masonry units, lead lined gypsum lath, lead lined gypsum wallboard and lead lined plywood will not be tested prior to installation. 1.5 SUBMITT
9、ALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Shop Drawings: Each lead radiation shielding item specified showing thickness of lead, details of construction and installation. C. Samples: 1. Lead lined concrete masonry units, gypsum lath and gypsum wa
10、llboard. 2. Bottom corner section of lead lined door, 300 mm (12 inches) square showing bottom and side edge strips. D. Manufacturers Literature and Data: Each lead radiation shielding item specified. 1.6 WARRANTY A. Warranty lead lined doors against defects in workmanship and materials subject to t
11、erms of “Warranty of Construction“ Article in GENERAL CONDITIONS, except that warranty period shall be two years. B. Warp or twist of lead lined flush veneered doors may not exceed 6 mm (1/4 inch) in any face dimension of door (including full diagonal), measured not less than six months after doors
12、have been hung and finished. 1.7 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. Federal Specifications (Fed. Spec.): QQ-L-201F(2)Lead Sheet C. American
13、Society for Testing and Materials (ASTM): A167-99(2009) Stainless and Heat Resisting Chromium-Nickel Steel Plate, Sheet and Strip Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-07-11 13 49 00 - 3 C1396/C1396M-04 Gypsum Wallboard/Gypsum Lath C90-11 .
14、 Load-Bearing Concrete Masonry Units C1002-07 . Steel Drill Screws for the Application of Gypsum Board or Metal Plaster Bases D1187-97(R2002) Asphalt-Base Emulsions for Use as Protective Coatings for Metal D. United States Department of Commerce Product Standard (PS): FED PSI 83-84 Construction and
15、Industrial Plywood E. Military Specifications (Mil. Spec.): MIL-C-36373 Cabinet, Cassette Transfer, Wall Mounted F. National Council on Radiation Protection and Measurements (NCRP): Report 147 . Structural Shielding Design for Medical X-Ray Imaging Facilities (2004) Report 102 . Medical X-Ray, Elect
16、ron Beam and Gamma-Ray Protection for Energies up to 50 MeV (Equipment Design, Performance and Use), (1989) PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with application requirements specified in the referenced Applicable Publications. Update and specify only that which appli
17、es to the project. 2.1 MATERIALS A. Lead Sheet: Fed. Spec. QQ-L-201, Grade C, of thickness shown on drawings. B. Lead Lined Concrete Masonry Units: 1. ASTM C90. 2. Units shall have unpierced sheet lead through vertical centers arranged to provide effective lead insulation through all joints. 3. Secu
18、re sheet lead to masonry units either by latex bonding (vulcanizing) method, or by galvanized iron anchors soldered or cemented to lead. C. Lead Lined Gypsum Lath: 1. ASTM C1396, 9 mm (3/8 inch) thick. 2. Bond sheet lead to one side of lath using plastic adhesive which will not dry out, nor set up h
19、ard, nor allow sheet lead to pull loose. 3. Apply sheet lead in uniform thickness shown, unpierced and in one piece. 4. Extend lead one inch beyond edge of each piece of lath at top and at one end. D. Lead Lined Gypsum Wallboard: Provided by IHSNot for ResaleNo reproduction or networking permitted w
20、ithout license from IHS-,-,-07-11 13 49 00 - 4 1. ASTM C1396, Type X, 16 mm (5/8 inch) thick. 2. Factory bond sheet lead to one side of wallboard. 3. Apply sheet lead in thicknesses shown, unpierced and in one piece. E. Lead Lined Plywood Panels: 1. Prod. Std. PS1, Grade A-A interior type, 9 mm (3/8
21、 inch) thick. 2. Factory bond sheet lead to one side of plywood. 3. Apply sheet lead in thicknesses shown, unpierced and in one piece. 4. Make each panel in one piece and of width to fully sustain its own weight without requiring intermediate nailing between joints. F. Stainless Steel: ASTM A167. G.
22、 Lead Glass: Clear, X-ray proof, of sufficient thickness to provide X-ray protection equivalent to that provided by partition or door in which glass occurs. H. Lead Control Windows: Cast lead, rigid, single unit type without joints, with or without voice passage as shown and with lead stop beads and
23、 lead glass. I. Cassette Transfer Cabinets, MIL-C-36373: Sheet lead lining of cabinets shall provide X-ray protection equal to that provided by partition in which cabinets occur. J. Thresholds: /1. Lead lined stainless steel as detailed./ /2. Stainless steel thresholds over lead lining as detailed./
24、 K. Fasteners: 1. Cadmium or chromium plated steel screws for securing lead louvers. 2. Standard steel drill screws, ASTM C1002, with lead washers for application of lead lined sheet materials to metal studs and attach washers in accordance with shielding manufacturers instructions. 3. Nails: a. Use
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1349002011RADIATIONPROTECTIONPDF