VA 13 21 29-2011 CONSTANT TEMPERATURE ROOMS.pdf
《VA 13 21 29-2011 CONSTANT TEMPERATURE ROOMS.pdf》由会员分享,可在线阅读,更多相关《VA 13 21 29-2011 CONSTANT TEMPERATURE ROOMS.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、11-11 13 21 29 - 1 SECTION 13 21 29 CONSTANT TEMPERATURE ROOMS SPEC WRITER NOTE: 1. Delete between / _ / if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies labor
2、atory controlled temperature rooms. 1.2 RELATED WORK A. Walk-in Refrigerators and Freezers: Section 11 41 21, WALK-IN COOLERS AND FREEZERS. B. Refrigerant Piping: Section 23 23 00, REFRIGERANT PIPING. C. Controls: Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. 1.3 QUALITY CONTROL A. Manuf
3、acturer Qualifications: Manufacturer regularly and presently manufacturers prefabricated controlled temperature rooms. B. Safety Standard: Units comply with ASHRAE 15 requirements for factory testing and nameplate. C. Electrical Components and Devices: UL listed and labeled for intended use. 1.4 SUB
4、MITTALS A. Furnish submittals in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: Include the following: 1. Illustrations and descriptions of prefabricated controlled temperature rooms and factory-installed devices. 2. Catalog or model
5、 numbers for each item incorporated into the work. 3. Assembly instructions. 4. Diagrams and details of piping, wiring, and controls. 5. Operating-test data. C. Performance Testing Reports: Indicate dates and times of tests and certify test results. D. Operating Instructions: Comply with requirement
6、s in Section 01 00 00, GENERAL REQUIREMENTS. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 13 21 29 - 2 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications
7、are referenced in the text by the basic designation only. B. American National Standards Institute/National Electrical Manufacturers Association (ANSI/NEMA): WD 6-2002(R2008) . Wiring Devices-Dimensional Requirements C. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRA
8、E): 15-2010 Safety Code for Mechanical Refrigeration PART 2 - PRODUCTS 2.1 WALK-IN CONTROLLED TEMPERATURE ROOM SPEC WRITER NOTE: Show room dimensions on drawings. A. General: Furnish and install prefabricated, sectional, all-metal clad, modular, controlled temperature rooms that are designed for fie
9、ld assembly, to establish temperature specified within two hours, and to maintain that temperature without further attention. B. Case: Include modular panels for walls, floor, ceiling, and door(s). 1. Panel Construction: Double-wall construction, prewired, and insulated and vapor-sealed sections mec
10、hanically locked in place from interior of room without the use of special tools. Each panel passes through a 1829 mm (6 feet) wide corridor and 813 by 2032 mm (32 by 80 inch) doorway. Panel construction does not incorporate wood. 2. Door: a. Not less than 864 mm (34 inches) wide by 1905 mm (75 inch
11、es) high; construction matching that of panels; with observation panel of sealed multipane glass not less than 305 mm (12 inches) square. b. Door handle and latch permits exterior locking with safety release to allow door to be opened from inside when locked on outside. Safety release will not distu
12、rb vapor seal when operated nor require tools to reactivate. c. Equip door jambs of rooms capable of attaining a temperature of 4 degrees C (39 degrees F) or colder with concealed heater to prevent frost formation or condensation. Provided by IHSNot for ResaleNo reproduction or networking permitted
13、without license from IHS-,-,-11-11 13 21 29 - 3 3. Access Ports: Equip units with PVC or neoprene sleeves or gaskets for service entrances. Vapor seal access ports at interior and exterior of panels. 4. Finishes: a. Interior Walls and Ceiling: Chemical-resistant nontoxic odorless epoxy, not less tha
14、n 0.0254 mm (1 mil) thick. b. Exterior: Baked enamel or matching interior. 5. Pressure Relief Port: Equip freezers that will operate at minus 18 degrees C (0 degrees F), or lower with 2-way type ports that allow for an increase or decrease of air pressure on the interior of the freezer to equalize w
15、ith air pressure on the exterior. C. Condensing Units: 1. / Air-cooled / Water-cooled / Combination air-/water-cooled / type. Do not locate compressors on top of refrigerator or freezers. 2. Provide positive oil lubrication and oil-level indicating device for each compressor. Equip water-cooled unit
16、s with water regulating valve. 3. Pressure Switches: Automatic-reset low-pressure switch, and automatic- or manual-reset high-pressure cutout. D. Controls: 1. Mount regulating and indicating devices in console or panel adjacent to and no higher than door. Calibrate controls, thermometer, and recorde
17、r in increments of 1 degree C (1.8 degrees F). 2. Operating Temperature Control: Self-contained remote bulb, liquid filled, reverse acting, adjustable, and sealed mercury-bulb-type thermostat, with three-degree differential. /Rooms specified to maintain single temperature do not have temperature sel
18、ection adjustable by operator./ /3. Humidity: Electric control capable of maintaining selected relative humidity within plus or minus 5 percent./ 4. Alarm and Override Temperature Control: Equip with sensing devices and circuits that take over control, initiate corrective action, and activate an aud
19、ible signal device in event of temperature variation in room of more than 3 degrees C (5 degrees F) from set temperature. Signal automatically resets on return of room to set operating temperature. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1321292011CONSTANTTEMPERATUREROOMSPDF