VA 11 53 53-2011 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS.pdf
《VA 11 53 53-2011 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS.pdf》由会员分享,可在线阅读,更多相关《VA 11 53 53-2011 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、01-11 11 53 53 - 1 SECTION 11 53 53 BIOLOGICAL SAFETY CABINETS AND LAMINAR AIRFLOW WORK STATIONS SPEC WRITER NOTES: 1. Delete between / _ / if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCR
2、IPTION This section specifies Biological Safety Cabinets: / Class I / Class II, Type A1 / Class II, Type A2 / Class II, Type B1 / Class II, Type B2 / and Laminar Airflow Work Stations (LAFW): / Vertical / Horizontal /. 1.2 DEFINITIONS A. Class I Biological Safety Cabinet: A ventilated cabinet for ex
3、posure protection of personnel and the environment, suitable for work involving low to moderate risk agents (BSL 1,2, and 3). Cabinet air is exhausted through a HEPA filter, either into the laboratory or to the outside. B. Class II Biological Safety Cabinet: A ventilated cabinet for exposure protect
4、ion of personnel, product and the environment, suitable for work involving low to moderate risk agents (BSL 1,2, and 3). Cabinet air is exhausted through a HEPA filter either into the laboratory or to the outside. Class II cabinets are available as two types (A and B) based on construction, air flow
5、 velocities and patterns, and exhaust systems. Refer to Table 1. C. Laminar Airflow Work Station(LAFW): A self-contained, positive pressure cabinet that provides an ISO 5/Class 100 clean air environment, designed to provide product protection when handling non-hazardous products. Streams of unidirec
6、tional air move in parallel lines through the cabinet, then through a HEPA filter, and into the laboratory. Both horizontal and vertical laminar flow work stations are available. 1.3 RELATED WORK A. Section 22 15 00, GENERAL SERVICE COMPRESSED-AIR SYSTEMS: Connections to Compressed Air System. B. Se
7、ction 22 11 00, FACILITY WATER DISTRIBUTION: Plumbing Connections. C. Section 22 13 00, FACILITY SANITARY SEWERAGE: Plumbing Connections. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-01-11 11 53 53 - 2 D. Section 22 62 00, VACUUM SYSTEMS FOR LABOR
8、ATORY and HEALTHCARE FACILITIES: Connections to Gas and Vacuum Systems. E. Section 22 63 00, GAS SYSTEMS FOR LABORATORY and HEALTHCARE FACILITIES: Connections to Gas and Vacuum Systems. F. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Pressure Switches. G. Section 23 31 00, HVAC DUCTS an
9、d CASINGS: Ductwork. H. Section 23 36 00, AIR TERMINAL UNITS: Airflow Control Valves. I. Section 23 40 00, HVAC AIR CLEANING DEVICES: HEPA Filters. J. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS and CABLES (600 VOLTS AND BELOW): Electrical Connections. K. Section 26 27 26, WIRING DEVIC
10、ES: Electrical Devices. 1.4 QUALITY CONTROL A. Mechanical, electrical and associated systems shall be safe, reliable, efficient, durable, easily and safely operable, maintainable, and accessible. B. Standard Products: Material and equipment shall be the standard products of the selected manufacturer
11、, and they should be regularly engaged in the manufacture of such products for at least 3 years. C. All items furnished shall be free from defects that would adversely affect the performance, maintainability and appearance of individual components and overall assembly. D. NSF Compliance: Equipment b
12、ears NSF (National Sanitation Foundation) Certification Mark indicating compliance with NSF 49. This certification applies only to Class 1 and 2 Biological Safety Cabinets, not LAFW. E. Electrical Components and Devices: UL listed and labeled for intended use. 1.5 SUBMITTALS A. Submit in accordance
13、with specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: Include the following: 1. Illustrations and descriptions of the unit and factory-installed devices associated with it. 2. Catalog or model numbers for each item incorporated into the
14、work. 3. Utility requirements. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-01-11 11 53 53 - 3 C. Shop Drawings: Show details of fabrication, installation, adjoining construction, coordination with mechanical and electrical work, anchorage, and ot
15、her work required for complete installation. D. Factory Testing: Provide manufacturers QC checklist or other reports that indicate comprehensive factory testing has been performed, and the results of these tests. E. Field Test Reports: Provide certification reports from accredited service technician
16、s or installers. F. Operating Instructions: Comply with requirements in specification Section 01 00 00, GENERAL REQUIREMENTS. SPEC WRITER NOTE: Edit the following requirements to coordinate with project sustainability goals. G. LEED Information: 1. LEED (v 3.0) MR Credit 4, Recycled Content: Product
17、 data indicating percentages, by weight of post-consumer and post-industrial recycled content for products having recycled content: a. Include statement indicating costs for each product having recycled content. 2. LEED (V 3.0) MR Credit 5, Regional Materials: Manufacturers data identifying point of
18、 origin for products procured within 500 mile radius of the project: a. Include statement indicating costs for each product submitted. 1.6 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text
19、by the basic designation only. B. American National Standards Institute / National Electrical Manufacturers Association (ANSI/NEMA): WD 6-2002 (R2008).Wiring Devices-Dimensional Specifications C. National Sanitation Foundation International / American National Standards Institute (NSF/ANSI): 49-2009
20、.Biosafety Cabinetry: Design, Construction, Performance and Field Certification D. Scientific Equipment and Furniture Association (SEFA): 2-1999Recommended Practices for Installation 7-2007Recommended Practices for Fixtures E. National Fire Protection Association (NFPA): Provided by IHSNot for Resal
21、eNo reproduction or networking permitted without license from IHS-,-,-01-11 11 53 53 - 4 45-2011.Standard on Fire Protection for Laboratories using Chemicals PART 2 - PRODUCTS 2.1 BIOLOGICAL SAFETY CABINETS SPEC WRITER NOTE: Edit the following requirements to coordinate with the equipment shown on d
22、rawings. A. General Specification for Biological Safety Cabinets SPEC WRITER NOTE: The following specifications apply to both Class I and Class II Biological Safety Cabinets. Furnish and install biological safety cabinets that have the following characteristics: 1. Cabinet Exterior: a. Class I: / Ep
23、oxy-coated aluminum / polycarbonate and steel / steel /. b. Class II: / Reinforced cold-rolled steel with acid-resistant painted finish / stainless steel /. 2. Cabinet Interior: a. Class I: / Epoxy-coated aluminum / polycarbonate and steel / steel /. b. Class II: / Reinforced cold-rolled steel with
24、acid-resistant painted finish / stainless steel /. 3. View Screen: Hinged, 6-mm- (1/4-inch-) minimum thick, laminated safety glass. 4. Motor/Blower System: To circulate filtered air into and/or through cabinet. 5. Duct: Stainless-steel duct to direct air from the recirculation blower cabinet to the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1153532011BIOLOGICALSAFETYCABINETSANDLAMINARAIRFLOWWORKSTATIONSPDF

链接地址:http://www.mydoc123.com/p-1074824.html