1、11-11 11 40 21 - 1 SECTION 11 40 21 FOOD SERVICE EQUIPMENT-UTILITY DISTRIBUTION SYSTEM SPEC WRITER NOTES: 1. Delete between / _ / if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber the paragraphs. 3. Select utility distribution syste
2、ms according to usage requirements and codes. PART 1 GENERAL 1.1 DESCRIPTION A. Utility Distribution Systems: /1. Island style./ /2. Wall mounted./ /3. With tray makeup conveyor. / /4. With tray slide. / 1.2 RELATED WORK A. Equipment Supports: Section 05 50 00, METAL FABRICATIONS. SPEC WRITER NOTE:
3、Retain paragraph below if required for project location. B. Seismic Restraint of Equipment: Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. C. Cooking Equipment: Section 11 44 00, FOOD COOKING EQUIPMENT. D. Ventilating Hoods: E. Plumbing Connections: Section 22 11 00,
4、 FACILITY WATER DISTRIBUTION and Section 22 13 00, FACILITY SANITARY SEWERAGE. F. Building Fire-Protection Systems: /Section 21 10 00, WATER-BASED FIRE-SUPPRESSION SYSTEMS / Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS. G. Electrical Connections: Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUC
5、TORS AND CABLES (600 VOLTS AND BELOW). 1.3 QUALITY CONTROL A. Installer Qualifications: Experienced in food service equipment installation or supervised by an experienced food service equipment installer: 1. Where required to complete equipment installation, electrician and plumber shall be licensed
6、 in jurisdiction where project is located. SPEC WRITER NOTE: UL Environmental and Public Health (EPH) Classification Mark is currently used to certify compliance Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 11 40 21 - 2 with NSF/ANSI standar
7、ds. Equipment evaluated by UL before 2001 may bear the UL Food Service Product Certification Mark. B. NSF Compliance: Equipment bears NSF Certification Mark or UL Classification Mark indicating compliance with NSF/ANSI 2 and NSF 2-Supplement. C. UL Listing: Equipment is a “Commercial Appliance Outle
8、t Center“ listed by UL and labeled for intended use. D. Fire-Protection Systems: Comply with NFPA 96. E. Welding: Perform welding according to AWS D9.1. SPEC WRITER NOTE: Retain paragraph and subparagraphs below if required for project location. F. Seismic Restraint: 1. Comply with requirements in S
9、ection 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. 2. Comply with applicable guidelines for seismic restraint of kitchen equipment contained in SMACNAs “Kitchen Ventilation Systems and Food Service Equipment Guidelines,“ Appendix A. G. In-Use Service: At least one factory
10、-authorized service agency for equipment shall be located in the geographical area of the installation and shall have the ability to provide service within 24 hours after receiving a service call. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
11、 B. Manufacturers Literature and Data: 1. Include manufacturers address and telephone number. 2. Include catalog or model numbers and illustrations and descriptions of utility distribution systems. C. Installation Drawings: Show dimensions, details of installation, coordination with plumbing and ele
12、ctrical work, and other work required for a complete installation. D. Operating Instructions: In accordance with requirements in . 1.5 WARRANTY Warrant food service equipment to be free from defects in materials and workmanship in accordance with requirements of “Warranty of Construction“, FAR claus
13、e 52.246-21. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 11 40 21 - 3 1.6 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by th
14、e basic designation only. B. American Welding Society, Inc. (AWS): D9.1-2006 Sheet Metal Welding Code C. ASTM International (ASTM): A666-10 Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar D. National Association of Architectural Metal Manufacturers (NAAMM): AMP 5
15、00-06 . Metal Finishes Manual E. NFPA International (NFPA): 96-11 Ventilation Control and Fire Protection of Commercial Cooking Operations F. NSF International/American National Standards Institute (NSF/ANSI): 2-2010 . Food Equipment 2-Supplement . Descriptive Details for Food Service Equipment Stan
16、dards G. Sheet Metal and Air Conditioning Contractors National Association (SMACNA): Kitchen Ventilation Systems and Food Service Equipment Fabrication and Installation Guidelines, 2001. PART 2 PRODUCTS 2.1 MATERIALS A. Stainless Steel: ASTM A 666, Type 304, stretcher leveled. 1. Finish: No. 4 finis
17、h (bright, directional polish) according to NAAMMs AMP 500-505, Metal Finishes Manual. SPEC WRITER NOTES: 1. Symbols below correspond with “Room Equipment Guide“ identification system. Verify project requirements before specifying equipment that deviates from “Room Equipment Guide.“ 2. Edit symbols
18、to coordinate with identification shown on drawings. 2.2 UTILITY DISTRIBUTION SYSTEMS SPEC WRITER NOTE: Size accessories and utilities using utility chart supplied by manufacturer. A. Island-Style Utility Distribution System: Floor mounted, to supply the utilities to operate cooking equipment, with
19、floor-to-ceiling risers at Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 11 40 21 - 4 each end to house reset switches, / controls for gas, steam, and water / gas shutoff with manual reset station / fire fuel shutoff for gas and electric / an
20、d other components indicated. B. Wall-Mounted Utility Distribution System: Supplies utilities to operate tray-line equipment, with wall-mounted reset switches, / controls for gas, steam, and water / gas shutoff with manual reset station / fire fuel shutoff for gas and electric /, and other component
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA1140212011FOODSERVICEEQUIPMENTUTILITYDISTRIBUTIONSYSTEMPDF

链接地址:http://www.mydoc123.com/p-1074817.html