VA 07 40 00-2011 ROOFING AND SIDING PANELS.pdf
《VA 07 40 00-2011 ROOFING AND SIDING PANELS.pdf》由会员分享,可在线阅读,更多相关《VA 07 40 00-2011 ROOFING AND SIDING PANELS.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、10-11 07 40 00 - 1 SECTION 07 40 00 ROOFING AND SIDING PANELS SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies / insulated / un
2、insulated / metal wall and roof panels / and fire rated composite metal wall and roof systems / as shown. 1.2 RELATED WORK A. Sealant: Section 07 92 00, JOINT SEALANTS. B. Color and texture of finish: Section 09 06 00, SCHEDULE FOR FINISHES. 1.3 MANUFACTURERS QUALIFICATIONS Metal wall and roof panel
3、s / and composite metal wall and roof systems / shall be products of a manufacturer regularly engaged in the fabrication and erection of metal panels / and composite metal wall and roof systems / of the type and design shown and specified. 1.4 FIRE RATING Composite metal wall / and roof / systems sh
4、all have a fire rating of _ hours when tested in accordance with ASTM E119. 1.5 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Samples: Metal panel, 150 mm (six inch) square, showing finish, each color and texture. C. Shop Drawings: Wall and ro
5、of panels, showing details of construction and installation. / Collateral steel framing / U value / thickness and kind of material, closures, flashing, fastenings and related components and accessories. D. Manufacturers Literature and Data: Wall and roof panels E. Fire Test Report: Report of fire te
6、st by recognized testing laboratory for fire rating specified, showing details of construction. 1.6 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extend referenced. The publications are referenced in the text by the basic designation only. Provided
7、 by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-11 07 40 00 - 2 B. American Society for Testing and Materials (ASTM): A653/A653M-10 Steel Sheet, Zinc-Coated (Galvanized), or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process. A463-10 Steel Sheet
8、, Cold-Rolled, Aluminum-Coated, by the Hot-Dip Process A924/A924M-10 Steel Sheet, Metallic Coated by the Hot-Dip Process A1008/A1008M-10 Steel, Sheet, Cold-Rolled, Carbon, Structural, High Strength Low Alloy B209/209M-07 . Aluminum and Aluminum Alloy Sheet and Plate C1396-11 . Standard Specification
9、 for Gypsum Board C553-08 Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications C591-09. . Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation C612-10 Mineral Fiber Block and Board Thermal Insulation E119-10 Fire Test of Building Construction and Materi
10、als PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. 2.1 SHEET STEEL A. Minimum 0.8mm thick for wall and roof panels. B. Steel, Sheet, Galv
11、anized: ASTM A653/A653M, Structural. 1. Grade 40, galvanized coating conforming to ASTM A924/A924M, Class Z 275 G-90. C. Steel, Sheet, Commercial: ASTM A1008, Type C. D. Steel, Sheet, Aluminized: ASTM A463. Steel shall be coated on both sides with 0.5 ounce of aluminum per square foot (0.15 Kg/sm ).
12、 2.2 ALUMINUM PLATE AND SHEET ASTM B209/209M 2.3 FASTENERS /Fasteners for steel panels shall be galvanized or cadmium plated steel. / /Fasteners for aluminum panels shall be aluminum or stainless steel. / Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,
13、-,-10-11 07 40 00 - 3 / Fasteners of size, type and holding strength as recommended by manufacturer. / 2.4 GYPSUM BACKING BOARD ASTM C1396, Type X, Plain face, Square edge. 2.5 THERMAL INSULATING MATERIALS A. Urethane or isocyanurate Board: ASTM C591, Type I. B. Mineral Fiber Blankets: ASTM C553, Ty
14、pe I. C. Mineral Fiber Board: ASTM C612, Class I. 2.6 FABRICATION A. Insulated metal wall and roof panels shall consist of an insulating core enclosed between two metal face sheets, of configuration shown on drawings. Construct panels by pressing members together to form a structural unit with close
15、d ends. Furnish Wall panels in one continuous length for full height, or at least one story height with no horizontal joints, except at openings. Overall thickness of panels is shown on drawings. Connection between panels shall be by / interlocking male and female joints / interlocking joints filled
16、 with sealant. / Work shall include / collateral steel framing / metal and bituminous closures, fastenings, flashing, clip, caulking, / panel reinforcements for support of mechanical and electrical work shown on drawings, / and related components and accessories. Construct panels as follows: 1. Exte
17、rior face of wall or roof sheet: a. / 0.8 / 1.0 / 1.25 / mm (/ 0.032 / 0.040 / 0.050 / inch) thick aluminum. b. / 1.2 / 0.9 / 0.6 / 0.5 / mm (/ 0.0478 / 0.0359 / 0.0229 / 0.0239 / inch) thick uncoated steel. c. / 1.3 / 1.0 / 0.85 / 0.7 / 0.6 / mm (/ 0.0516 / 0.0396 / 0.0336 / 0.0276 / 0.0247 / inch)
18、 thick galvanized steel. d. 0.8 mm (0.032 inch) thick aluminized steel. 2. Interior liner face of wall or roof sheet: a. / 0.8 / 1.0 / 1.25 / mm (/ 0.032 / 0.040 / 0.050 / inch) thick aluminum. b. / 1.3 / 1.0 / 0.85 / 0.7 / 0.6 / mm (/ 0.0516 / 0.0396 / 0.0336 / 0.0276 / 0.0247 / inch) thick galvani
19、zed steel. c. / 1.2 / 0.9 / 0.6 / 0.5 / mm (/ 0.0478 / 0.0359 / 0.0229 / 0.0239 / inch) thick uncoated steel. SPEC WRITER NOTE: Verify use of urethane or isocyanurate insulation in VA hospital patient and other public areas. Provided by IHSNot for ResaleNo reproduction or networking permitted withou
20、t license from IHS-,-,-10-11 07 40 00 - 4 3. Insulation shall be / urethane board / isocyanurate / mineral fiber blanket / having a “U“ value of / 0.85 / 1.2 / _ / W/(m K) (/ 0.15 / 0.21 / _ / Btu/h ft F). 4. / Sub-girts shall be 1.0 mm (0.0396 inches) thick galvanized steel hat channels designed to
21、 receive panel fasteners or clips. / 5. Accessories and fastenings shall be the same material and finish as the panels. Thickness and installation of accessories and flashing shall be as recommended by panel manufacturer. B. Uninsulated metal wall and roof panels shall be single sheets, of approxima
22、te overall depth and configuration shown on drawings. Connection between panels shall be by interlocking joints filled with sealing compound as specified in Section 07 92 00, JOINT SEALANTS. Furnish wall panels in one continuous length for full height or at least one story height with no horizontal
23、joints, except at openings. Furnish roof panels in one continuous length of roof span and provide cut-outs as required for passage of pipes, conduits, vents and the like. Construct panels as follows: 1. Wall panels: a. / 0.8 / 1.0 / mm (/ 0.032 / 0.040 / inch) thick aluminum. b. / 1.3 / 1.0 / 0.85 /
24、 0.7 / mm (/ 0.0516 / 0.0396 / 0.0336 / 0.0276 / inch) thick galvanized steel. c. / 1.2 / 0.9 / 0.6 / mm (/ 0.0478 / 0.0359 / 0.0229 / inch) thick uncoated steel. d. / 0.8 / 1.0 / mm (/ 0.032 / 0.040 / inch) thick aluminized steel. 2. Roof Panels: a. / 0.8 / 1.0 / mm (/ 0.032 / 0.040 / inch) thick a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0740002011ROOFINGANDSIDINGPANELSPDF