1、10-10 07 22 00 - 1 SECTION 07 22 00 ROOF AND DECK INSULATION SPEC WRITER NOTES: 1. Delete text in / / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Follow the recommendations of the National Roofing Contractors Ass
2、ociation “Roofing and Waterproofing Manual“ for design criteria. 3. Comply with ASHRAE Standard 90.1-2007. Minimum acceptable average R value is 33. 4. Insure positive slope to drains occur; minimum of 1:50 (1/4 inch per foot) without any “gutters“ (no slopes) between drains. 5. Do not use on slopes
3、 over 1:12 (one inch per foot) unless text is edited for this. 6. Insure drains are located at points of maximum deflection; such as at midspans and at bottom of slopes. 7. This section is intended for use where insulation is under the roofing or waterproofing membrane. 8. Do not use polystyrene ins
4、ulation under bituminous roofing or waterproofing membrane. 9. Anchor insulation to the deck. Do not specify loose laid insulation. 10. Coordinate with electrical. Do not allow conduit to be run in the insulation. PART 1 - GENERAL 1.1 DESCRIPTION A. Roof and deck insulation, /substrate board,/ /vapo
5、r retarder,/ /and / /cover board/ on new construction ready to receive roofing or waterproofing membrane. B. Repairs and alteration work to existing roof insulation. 1.2 RELATED WORK SPEC WRITER NOTE: Edit Related Work to reflect other sections relating directly to this section or referenced in this
6、 section. A. General sustainable design documentation requirements: Section 01 81 13 SUSTAINABLE DESIGN REQUIREMENTS. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 07 22 00 - 2 B. Insulating Concrete Systems: Section 03 52 00, LIGHTWEIGHT CON
7、CRETE ROOF INSULATION. C. Wood cants, blocking, and edge strips: Section 06 10 00, ROUGH CARPENTRY. D. Perimeter, rigid, and batt or blanket insulation not part of roofing system: Section 07 21 13, THERMAL INSULATION. E. Sheet metal components and wind uplift requirements for roof-edge design: Secti
8、on 07 60 00, FLASHING AND SHEET METAL. 1.3 APPLICABLE PUBLICATIONS SPEC WRITER NOTES: 1. Update applicable publications to current issue at time of project specification preparation. 2. Update material requirements to agree with applicable requirements (types, grades, classes,) specified in the refe
9、renced Applicable Publications. A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. Editions of applicable publications current on date of issue of bidding documents apply unless otherwise ind
10、icated. B. American Society of Heating, Refrigeration and Air Conditioning (ASHRAE): 90.1-07.Energy Standard for Buildings Except Low-Rise Residential Buildings C. ASTM International (ASTM): C208-08.Cellulosic Fiber Insulating Board C552-07.Cellular Glass Thermal Insulation C726-05.Mineral Fiber Roo
11、f Insulation Board C728-05.Perlite Thermal Insulation Board C1177/C1177M-08.Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing C1278/C1278M-07.Standard Specification for Fiber-Reinforced Gypsum Panel C1289-10Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board C1396
12、/C1396M-09.Standard Specification for Gypsum Board D41-05Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 07 22 00 - 3 D312-06.Asphalt Used in Roofing D1970-09Standard Specification
13、 for Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection D2178-04Asphalt Glass Felt Used in Roofing and Waterproofing D2822-05Asphalt Roof Cement D4586-07Standard Specification for Asphalt Roof Cement, Asbestos-Free E84-09Standard Test
14、Method for Surface Burning Characteristics of Building Material F1667-05Driven Fasteners: Nails, Spikes, and Staples D. FM Approvals: RoofNav Approved Roofing Assemblies and Products. 4450-89.Approved Standard for Class 1 Insulated Steel Deck Roofs 4470-10.Approved Standard for Class 1 Roof Covering
15、s 1-28-09.Loss Prevention Data Sheet: Design Wind Loads. 1-29-09.Loss Prevention Data Sheet: Above-Deck Roof Components 1-49-09.Loss Prevention Data Sheet: Perimeter Flashing E. National Roofing Contractors Association: Roofing and Waterproofing Manual F. U.S. Department of Agriculture (USDA): USDA
16、BioPreferred Catalog, www.biopreferred.gov G. Underwriters Laboratories, Inc. (UL): Fire Resistance Directory (2009) H. U.S. Department of Commerce National Institute of Standards and Technology (NIST): DOC PS 1-09.U.S. Product Standard for Construction and Industrial Plywood DOC PS 2-04.Performance
17、 Standard for Wood-Based Structural-Use Panels. 1.4 PERFORMANCE REQUIREMENTS SPEC WRITER NOTE: Modify minimum R-value requirement in paragraph below to correspond to Project requirements. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 07 22 00
18、 - 4 A. Thermal Performance: Provide roof insulation meeting minimum overall average R-value of /33/, with minimum R-value at any location of /10/. B. FM Approvals: Provide roof insulation complying with requirements in FM Approvals 4450 and 4470 as part of specified roofing system, listed in FM App
19、rovals “RoofNav“ as part of roofing system meeting Fire/Windstorm Classification in Division 07 roofing section. 1.5 QUALITY CONTROL A. Requirements of Division 07 roofing section for qualifications of roofing system insulation Installer; Work of this Section shall be performed by same Installer. B.
20、 Requirements of Division 07 roofing section for inspection of Work of this Section and qualifications of Inspector. C. Unless specified otherwise, comply with the recommendations of the NRCA “Roofing and Waterproofing Manual“ applicable to insulation for storage, handling, and application. SPEC WRI
21、TER NOTE: Retain applicable coordinating paragraphs related to uplift pressure and wind design below. D. Requirements of roofing system uplift pressure design for specified roofing system. E. Requirements of applicable FM Approval for specified roofing system insulation attachment. F. Requirements o
22、f applicable Miami-Dade County approval for high-wind zone design. SPEC WRITER NOTES: 1. Retain paragraph below when it is appropriate to incorporate Federal Guiding Principles IV from Guiding Principles for Federal Leadership in High Performance and Sustainable Buildings incorporated in Executive O
23、rder 13423 “Strengthening Federal Environmental, Energy, and Transportation Management, dated January 24, 2007, www.ofee.gov/eo/eo13423_main.asp: Enhance Indoor Environmental Quality: Biobased Content Requirement. Requirement differs from related requirements in LEED definitions. 2. Projects General
24、 Requirements should indicate goals for percentages of bio-Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-10-10 07 22 00 - 5 based, rapidly-renewable, and certified sustainable wood products. G. Bio-Based Materials: Where applicable, provide product
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0722002010ROOFANDDECKINSULATIONPDF