1、06-01-12 07 21 23 - 1 SECTION 07 21 23 LOOSE-FILL INSULATION MODIFICATION 06-01-12 UPDATE OF STANDARDS Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-06-01-12 07 21 23 - 2 SECTION 07 21 23 LOOSE-FILL INSULATION SPEC WRITER NOTE: Delete between /-/if
2、 not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. This section covers loose fill insulation, / vapor barrier / and all necessary blocking to install insulation / over ceilings / and / in
3、attic spaces / where shown. B. Insulation shall be installed in sufficient thickness to provide thermal resistance “R“ valves of / “R“_ above ceilings / and / “R“_ in attics / “R“_ as shown. 1.2 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Sa
4、mples: 1. Loose fill insulation in pint size containers 2. Blocking: 150 mm (6-inch) long strips 3. Vapor Retarder: 150 mm x 150 mm (6-inch by 6-inch) pieces C. Manufactures Literature: 1. Submit current copies of the insulation manufacturers printed fact sheet literature, including descriptive data
5、, insulation characteristics, and instructions for installation and protection of insulation. 2. Submit copy of “Bag Label“. 1.3 DELIVERY A. Deliver materials to the site in the original sealed containers or packages bearing the manufacturers name and brand designation. B. The containers or packages
6、 of insulation shall bear the referenced specification number, type and class as applicable, recommended method of installation (pneumatic or pouring), minimum net weight of insulation, coverage charts, “R“ values, and required warning statements. 1.4 STORAGE A. Inspect materials delivered to the si
7、te for damage and unload and store with a minimum of handling. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-06-01-12 07 21 23 - 3 B. Storage spaces shall be dry locations, not subject to open flames or sparks, and permitting easy access for inspec
8、tion and handling. SPEC WRITER NOTE: Update the applicable publications at the time of the project specification preparation. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the ba
9、sic designation only. B. American Society of Testing and Materials (ASTM): C612-10 Mineral Fiber Block and Board Thermal Insulation C728-05 (R2010) Perlite Thermal Insulation Board C739-08 Cellulosic Fiber (Wood-Base) Loose-Fill Thermal Insulation C764-07 Mineral Fiber Loose Fill Thermal Insulation
10、C1015-06 . Installation of Cellulosic and Mineral Fiber Loose-Fill Thermal Insulation D4397-10 . Polyethylene Sheeting for Construction, Industrial, and Agriculture Applications E84-10 . Surface Burning Characteristics of Building Materials C. Federal Regulations: Code of Federal Regulations 29 CFR
11、1910, Occupational Safety and Health Act (OSHA). D. National Fire Protection Associations (NFPA): 211-10 . Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances PART 2 - PRODUCTS SPEC WRITER NOTE: Update material requirements to agree with the applicable requirements (types, grades, classes
12、) specified in the referenced Applicable Publications. 2.1 LOOSE FILL INSULATION A. Cellulosic or Wood Fiber Loose Fill: ASTM C739. B. Mineral Fiber Loose Fill: ASTM C764, Type I or II. 2.2 BLOCKING A. Wood, metal, mineral fiber or perlite boards or other materials approved by the Resident Engineer.
13、 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-06-01-12 07 21 23 - 4 B. Mineral Fiber Board: ASTM C612, Type IB. C. Perlite Board: ASTM C728. 2.3 VAPOR RETARDER A. Six mil thick polyethylene sheeting conforming to ASTM D4397. B. Self adhesive tape
14、having a perm rating equal to the polyethylene. 2.4 RECOVERED MATERIAL A. Insulation products shall comply with following minimum content standards for recovered materials: Material Type Percent by Weight Cellulose Loose-fill and spray-on 75 percent post-consumer recovered paper Perlite composite bo
15、ard 23 percent post-consumer Rock wool material 75 percent recovered material B. The minimum-content standards are based on the weight (not the volume) of the material in the insulating core only. PART 3 - EXECUTION 3.1 INSPECTION A. Where possible, inspect / attic(s) / and / ceiling(s) / to receive
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0721232012LOOSEFILLINSULATIONPDF