VA 03 37 13-2011 SHOTCRETE.pdf
《VA 03 37 13-2011 SHOTCRETE.pdf》由会员分享,可在线阅读,更多相关《VA 03 37 13-2011 SHOTCRETE.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、07-11 03 37 13 - 1 SECTION 03 37 13 SHOTCRETE SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the requirements for materials,
2、proportioning, and application of shotcrete using either dry-mix or wet-mix process. 1.2 DEFINITION Mortar or concrete pneumatically projected at high velocity onto a surface; also known as air-blown mortar; also pneumatically applied mortar or concrete, sprayed mortar and gunned concrete. 1.3 RELAT
3、ED WORK A. Materials testing and inspection during construction: Section 01 45 29, TESTING LABORATORY SERVICES. B. Formwork and reinforcement: Section 03 30 00, CAST-IN-PLACE CONCRETE. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Design M
4、ix: Test Reports and Proportions. C. Shop Drawings: Reinforcing Steel. D. Two 300 mm x 300 mm x 25 mm (12 inch by 12 inch by 1 inch) sample panels showing required finish. Submit panels within 30 days after receipt of notice to proceed. E. Aggregate gradation. F. Certificates: Contractors qualificat
5、ions as specified. 1.5 QUALITY CONTROL A. Contractor Qualifications. 1. Work in this section shall be provided only by a Contractor specializing in and possessing the equipment, knowledge, and skilled operators for application of shotcrete. 2. Furnish evidence to Resident Engineer that Contractor co
6、nforms to above requirements, has been specializing in this work for a period of at least five years, and will use only experienced shotcrete foremen, nozzlemen and delivery equipment operators on the work. 3. Conform to ACI 506R, Paragraphs 4.2 and 4.3, for qualifications and duties of craftsmen. B
7、. Tolerances: 1. Cover of reinforcement: ACI 506.2, Paragraph 3.6.2. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-07-11 03 37 13 - 2 2. Alignment and thickness of shotcrete shall be controlled by installing ground wires. Alignment and thickness co
8、ntrol shall conform to ACI 506R Section 5.6. 1.6 PRECONSTRUCTION TESTING A. Conform to the requirements of ACI 506R, Paragraph 6.4. B. Testing laboratory approved by the Resident Engineer and reimbursed by Contractor shall design dry or wet mix, as applicable, to produce compressive strengths indica
9、ted on drawings. C. Make 2 test panels for each mix design, 450 mm (18 inches) square and 75 mm (3 inch) minimum thickness. Take 5 cores or cubes from each 75 mm (3 inch) panel for compressive strength testing in accordance with ACI 506R, Paragraph 6.4. SPEC WRITER NOTE: Tests of modulus of rupture,
10、 absorption, drying shrinkage, resistance to freeze-thawing along with others may also be specified depending on the application. Using the proposed mix design make at least two job-site sample panels approximately 2400 mm (8 feet) high and 1800 mm (6 feet) wide with thicknesses shown. The job-site
11、panels shall contain reinforcing typical of the work to be installed and other details to simulate actual job conditions. Finish sample panels as required for work to be installed. Sample panels must be approved by the V.A. before any work can begin. 1.7 CONSTRUCTION TESTING A. Make one test panel 4
12、50 mm (18 inches) square and 75 mm (3 inches) thick for each half-days work or portion thereof. Provide test panels to a testing laboratory approved by Resident Engineer and reimbursed by the contractor. Five compressive strength specimens will be obtained from each panel and tested for compressive
13、strength in accordance with ASTMC42. Two (2) samples are to be tested at 7 days and 28 days after application. The fifth sample should be retained for 56 days should additional testing be required. Strength test results are to be reported to the Resident Engineer 24 hours after completion of test. 1
14、.8 DELIVERY, HANDLING, AND STORAGE A. Properly deliver and handle materials to prevent contamination, segregation, or damage to materials. B. Store cement in weathertight enclosures to protect against dampness and contamination. C. Prevent segregation and contamination of aggregates by proper arrang
15、ement and use of stockpiles. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-07-11 03 37 13 - 3 D. Store admixtures properly to prevent contamination, evaporation, freezing, or other damage. 1.9 APPLICABLE PUBLICATIONS A. Publications listed below fo
16、rm a part of this specification to extent referenced. Publications are referenced in text by basic designation only. B. American Concrete Institute (ACI): 304R-00(2009) Guide for Measuring, Mixing, Transporting, and Placing Concrete 506R-05 Guide to Shotcrete 506.2-95 . Specification for Shotcrete 5
17、06.4R(R2004) Guide for the Evaluation of Shotcrete C. American Society for Testing and Materials (ASTM): A185/A185M-07 Steel Welded Wire Reinforcement, Plain, for Concrete A615/A615M-09 Deformed and Plain Carbon Steel Bars for Concrete Reinforcement C33/C33M-11 Concrete Aggregates C94/C94M-10 Ready-
18、Mixed Concrete C150/C150M-09 Portland Cement C260/C260M-10 Air-Entraining Admixtures for Concrete C494/C494-10 . Chemical Admixtures for Concrete PART 2 - PRODUCTS SPEC WRITER NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Upd
19、ate and specify only that which applies to the project. 2.1 MATERIALS A. Portland Cement: ASTM C150, Type I or II. B. Aggregate: ASTM C33, Gradation Table 2.1 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-07-11 03 37 13 - 4 TABLE 2.1 - GRADATION LI
20、MIT FOR COMBINED AGGREGATES Sieve Size, U.S. standard square mesh Percent by Weight Passing Individual Sieves Gradation No. 1 Gradation No. 2 Gradation No. 3 20 mm 3/4 inch - - 100 13 mm 1/2 inch - 100 80-95 10 mm 3/8 inch 100 90-100 70-90 No. 4 95-100 70-85 50-70 No. 8 80-100 50-70 35-55 No. 16 50-
21、85 35-55 20-40 No. 30 25-60 20-35 10-30 No. 50 10-30 8-20 5-17 No. 100 2-10 2-10 2-10 C. Chemical Admixtures: ASTM C494. D. Air-entraining Admixture: ASTM C260. E. Water: Fresh, Clean, and Potable F. Reinforcing Steel: ASTM A615, grade as shown. G. Welded Wire Fabric: ASTM A185. PART 3 - EXECUTION 3
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA0337132011SHOTCRETEPDF