UL SUBJECT 971A-2006 OUTLINE OF INVESTIGATION FOR METALLIC UNDERGROUND FUEL PIPE (Issue 1)《金属制地下燃料管道调查大纲 发布编号 1 1》.pdf
《UL SUBJECT 971A-2006 OUTLINE OF INVESTIGATION FOR METALLIC UNDERGROUND FUEL PIPE (Issue 1)《金属制地下燃料管道调查大纲 发布编号 1 1》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 971A-2006 OUTLINE OF INVESTIGATION FOR METALLIC UNDERGROUND FUEL PIPE (Issue 1)《金属制地下燃料管道调查大纲 发布编号 1 1》.pdf(32页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOctober 18, 20061SUBJECT 971AOUTLINE OF INVESTIGATIONFORMETALLIC UNDERGROUND FUEL PIPEIssue Number: 1OCTOBER 18, 2006Summary of TopicsThis is the First Issue of Subject 971A, Outline of Investiga
2、tion for MetallicUnderground Fuel Pipe, covering metallic and composite primary carrier,secondary containment, and integral primary/secondary pipe systems(pipe and fittings) intended for underground use in distribution andventing applications of petroleum-base flammable and combustibleliquids, alcoh
3、ols, and alcohol-blended fuels.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2006 UNDERWRITERS LABORATORIE
4、S INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOCTOBER 18, 2006SUBJECT 971A2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Uni
5、ts of Measurement .53 Undated References 54 Glossary .5CONSTRUCTION5 General 7PERFORMANCE6 General 87 Short Term Pressure Tests .117.1 General 117.2 Leakage test 127.3 Hydrostatic test .127.4 Breakdown test .128 Long Term Pressure Tests 128.1 General 128.2 Sustained pressure test 138.3 Cyclic pressu
6、re test 139 Vacuum Tests .139.1 General 139.2 Static vacuum test .149.3 Cyclic vacuum test 1410 Fitting Torque Test 1411 Fitting Bending Test .1512 Pipe Bending Test 1513 Drop Test .1614 Drop Test After Conditioning 1615 Ball Impact Test .1716 Ball Impact Test After Conditioning .1717 Pipe Burial Te
7、sts .1817.1 General .1817.2 Pull strength test .1817.3 Puncture resistance test 1917.4 Crush resistance test .1918 Long Term Compatibility Test 1919 Interstitial Communication Test .2520 UV Compatibility Test .2521 Nonmetallic Fitting Stress Crack Test .2622 Metallic Fitting Stress Crack Test .2623
8、Permeation Test 26MANUFACTURING AND PRODUCTION TESTS24 General 2825 Leakage Test 28OCTOBER 18, 2006 SUBJECT 971A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMARKING26 General .28INSTRUCTIONS27 General .30OCTOBER 18, 2006SUBJECT 971A4UL CO
9、PYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover metallic and composite primary carrier, secondary containment, andintegral primary/secondary pipe systems (pipe and fittings) intended for underground u
10、se in distributionand venting applications of petroleum-base flammable and combustible liquids, alcohols, andalcohol-blended fuels as identified in this outline.1.2 The piping covered by these requirements is intended to be installed and used in accordance with theFlammable and Combustible Liquids C
11、ode, NFPA 30, Code for Motor Fuel Dispensing Facilities andRepair Garages, NFPA 30A, and applicable Federal and State regulations for underground piping.1.3 These requirements cover completely metallic and composite metallic/nonmetallic pipe constructionswith manufacturer-supplied fittings for under
12、ground use only. The products covered by this outline havebeen evaluated for assembly in normal soil applications by qualified persons in accordance with themanufacturers instructions.1.4 The products covered by this outline have not been evaluated for applications in sumps (more than12 inches (30.5
13、 cm) from sump walls), as connector pipe (between underground pipe and dispensingdevice), aboveground or marine use, or other applications exceeding ambient temperatures of 75F(23C).2 Units of Measurement2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory
14、 orapproximate information.3 Undated References3.1 Any undated reference to a code or standard appearing in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.4 Glossary4.1 For the purposes of this outline the following definitions apply.
15、4.2 BARRIER LINER The thin inner or outer layer of a composite pipe that contains internal fuels,provides permeation resistance, and protects the outer structural pipe wall from exposure to fuels orexternal fluids.4.3 CHASE PIPE An underground pipe that is used to route primary carrier, secondary co
16、ntainment,or integral primary/secondary pipe between storage tanks and containment sumps. Typically used toextract pipe without excavation and is not considered secondary containment.4.4 CLOSED SECONDARY CONTAINMENT PIPING SYSTEM A secondary piping system with endsnormally closed at the tank and sum
17、p with a minimum rated pressure of 50 psig (350 kPa).4.5 COMPOSITE PIPE SYSTEM An underground piping system in which the pipe design containsboth metallic and nonmetallic major, critical components.OCTOBER 18, 2006 SUBJECT 971A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTR
18、IBUTION WITHOUT PERMISSION FROM UL4.6 FITTING A manufacturer-supplied component designed to connect, branch, or terminate pipesections and contain liquids. Connections may be threaded, welded, crimped, clamped, compressed,thermo fused, solvent welded, or adhesive joined. Sump boots are not considere
19、d fittings.4.7 FLEXIBLE PIPING Pipe with a manufacturers recommended minimum bend radius less than orequal to 6 feet (1.8 m). Typically constructed from thermoplastic materials.4.8 INTEGRAL Two or more separate components physically joined together or combined to form asingle part at the manufacture
20、r. Primary and secondary pipe joined in the field with a common fitting isnot considered integral.4.9 INTEGRAL PRIMARY/SECONDARY PIPE A single pipe, constructed at the manufacturer, thatcombines both primary carrier and secondary containment with an interstitial space that can bemonitored for leakag
21、e.4.10 METALLIC Pipe, fittings, or components primarily consisting of metals (typically corrosion-resistant malleable types such as steel, aluminum, copper, and brass) with or without minor nonmetalliccomponents (such as gaskets, seals, sleeves or bushings).4.11 METALLIC PIPE SYSTEM An underground p
22、iping system in which the pipe design containsmajor critical components that are formed from metals.4.12 NON-INTEGRAL PRIMARY/SECONDARY PIPE A pipe system with independent primary carrierand secondary containment connected in the field with an interstitial space that can be monitored forleakage.4.13
23、 NONMETALLIC Pipe, fittings, or components primarily consisting of nonmetals (typicallypolymeric thermoplastics, thermosets or composites) with or without minor metallic components (suchas foils, braids, tapes, sleeves, or bushings).4.14 NONMETALLIC PIPE SYSTEM An underground piping system in which
24、the pipe designcontains major critical components that are not formed from metals.4.15 NORMAL VENT PIPE A pipe system intended to transfer displaced gases (air and fluid vapors)from the top of an underground tank to grade during filling and provide atmospheric pressureequalization.4.16 OPEN SECONDAR
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT971A2006OUTLINEOFINVESTIGATIONFORMETALLICUNDERGROUNDFUELPIPEISSUE1 金属 地下 燃料 管道 调查 大纲 发布 编号 11

链接地址:http://www.mydoc123.com/p-1069520.html