UL SUBJECT 347D-2017 UL Outline of Investigation for Medium Voltage Stator Switching Assemblies for Wind Applications Up to 15KV (Issue 1).pdf
《UL SUBJECT 347D-2017 UL Outline of Investigation for Medium Voltage Stator Switching Assemblies for Wind Applications Up to 15KV (Issue 1).pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 347D-2017 UL Outline of Investigation for Medium Voltage Stator Switching Assemblies for Wind Applications Up to 15KV (Issue 1).pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 30, 20171UL 347DOutline of Investigation for Medium Voltage Stator Switching Assembliesfor Wind Applications, Up to 15KVIssue Number: 1August 30, 2017Summary of TopicsThis First Issue of t
2、he Outline of Investigation for Medium Voltage StatorSwitching Assemblies for Wind Applications, Up to 15KV, UL 347DC,covers requirements for stator switching assemblies for windapplications.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of In
3、vestigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2017 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
4、DISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 30, 2017UL 347D2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .41.1 General .41.2 Normative references, component standards, and general requiremen
5、ts 42 Normal and Special Service Conditions 53 Definitions 54 Ratings and Characteristics 55 Design and Construction .56 Enclosures .67 Grounding and Bonding 68 Protective Devices 69 Isolating Means .710 Interlocking 710.1 Isolating means interlocks 710.2 Drawout element interlocks .810.3 Door inter
6、locks 811 Automatic Restarting .912 Wiring and Connections 913 Insulating Materials .1014 Field Installed Accessories .1015 Spacings 1015.1 General .1015.2 Circuits and parts operating at 1500 V or less to ground 1116 Current Carrying Parts 1217 Performance .1218 Temperature-Rise Tests .1319 Resista
7、nce Measurement 1320 Make and Break Test .1321 Overload Test 1422 Mechanical Tests .1423 Switching Capacity Test - Isolating Means .1424 Dielectric Tests .1425 Fault Interruption Test .1426 Short-time, Momentary and Peak Withstand Current Bus Tests 1427 Driven Rain Test 1428 Mechanical Tests of View
8、ing Panes .1429 Enclosure Ground Integrity Test 1430 Shutter Integrity Test 1531 Rod Entry Test .1532 Rating .15MARKING33 General 1534 General Markings for Equipment 1635 Additional Markings for Control Centers .1636 Conditional Markings 1737 Additional Equipment Information .19AUGUST 30, 2017 UL 34
9、7D 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 General1.1.1 These requirements cover equipment having ac voltage ratings above 1500 V, up to 15 kV, thatincorporates switching elements intended for making and breakin
10、g the stator circuit of wind turbinesinvestigated to the Standard for Safety for Wind Turbines Permitting Entry of Personnel, UL 6141.1.1.2 The requirements do not cover variable speed motor controllers (power conversion equipment).1.1.3 These requirements cover equipment intended for use in ordinar
11、y locations in accordance with theNational Electrical Code.1.1.4 These requirements do not cover equipment intended for starting, stopping, regulating, controllingor protecting electric motors or other electrical loads including refrigeration equipment. Such equipment iscovered by the requirements t
12、he Standard for Medium-Voltage AC Contactors, Controllers, and ControlCenters, UL 347.1.1.5 These requirements are not intended to replace the requirements of IEEE 1547.1, StandardConformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric PowerSystems. When this eq
13、uipment is used as part of an interconnected system, it is anticipated that the entiresystem will be investigated to the requirements of IEEE 1547.1 as appropriate.1.2 Normative references, component standards, and general requirements1.2.1 Products covered by this outline shall comply with the refe
14、rence installation codes and standardsnoted in Annex A of UL 347.1.2.2 Where noted in this Outline, requirements specified in the Standard for Medium-Voltage ACContactors, Controllers, and Control Centers, UL 347, sixth edition, apply to these products.1.2.3 For undated references to standards, such
15、 reference shall be considered to refer to the latestedition and all revisions to that edition up to the time when the standard was approved. For datedreferences to standards, such reference shall be considered to refer to the dated edition and all revisionspublished to that edition up to the time t
16、he standard was approved.1.2.4 Components utilized in the products covered by this outline shall comply with the appropriatestandards for these components and shall be used in accordance with their recognized ratings and otherlimitations of use. Annex D of UL 347 provides a partial listing of standa
17、rds applicable to componentstypically used in this equipment.1.2.5 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered in this outline, orb) Is superseded by a requirement in this ou
18、tline.AUGUST 30, 2017UL 347D4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1.2.6 The units of measurement given in SI (metric) units shall be normative. Any other values given shallbe for information purposes only.2 Normal and Special Servic
19、e Conditions2.1 Clause 2 of UL 347 applies, as modified by 2.2.2.2 Equipment may be investigated for a normal service condition with a maximum ambient temperatureexceeding 40C. In such cases, the equipment is to be tested at the higher ambient temperature, and allcomponents are to be determined to b
20、e suitable for use in the higher temperature environment.3 Definitions3.1 The definitions in Clause 3 of the Standard for Medium-Voltage AC Contactors, Controllers, andControl Centers, UL 347 apply.3.2 ELECTRIC POWER SYSTEM (EPS) Equipment or facilities that deliver electric power to a load(s).The m
21、ost common example of an EPS is an electric utility.3.3 WIND TURBINE (WT) A device or system of subassemblies that convert wind energy to electricpower and typically consists of an overall structure including; tower, nacelle, hub and blades as well asthe associated internal equipment.3.4 WIND TURBIN
22、E OUTPUT CIRCUIT The circuit conductors or equipment connected to the turbineoutput terminals or conductors where the turbine is intended to be connected to the electric power system(EPS).4 Ratings and Characteristics4.1 Clause 4 of UL 347 applies, with the following additions.4.2 The rated overload
23、 current is the maximum operating overcurrent that the contactor is expected tointerrupt.5 Design and Construction5.1 Equipment as covered by this outline shall:a) Be so constructed as to provide for compliance with the rules for installation and use of suchequipment as given in the National Electri
24、cal Code, ANSI/NFPA 70; andb) Employ materials that are acceptable for the particular use.AUGUST 30, 2017 UL 347D 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL6 Enclosures6.1 Equipment shall comply with the requirements in Clause 5.102 of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT347D2017ULOUTLINEOFINVESTIGATIONFORMEDIUMVOLTAGESTATORSWITCHINGASSEMBLIESFORWINDAPPLICATIONSUPTO15KVISSUE1PDF

链接地址:http://www.mydoc123.com/p-1069413.html