UL SUBJECT 3004-2018 Outline of Investigation for Medium Voltage Junction Boxes (Issue 1).pdf
《UL SUBJECT 3004-2018 Outline of Investigation for Medium Voltage Junction Boxes (Issue 1).pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 3004-2018 Outline of Investigation for Medium Voltage Junction Boxes (Issue 1).pdf(30页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 1, 20181UL 3004Outline of Investigation for Medium Voltage Junction BoxesIssue Number: 1August 1, 2018Summary of TopicsThis First Issue of UL 3004, the Outline of Investigation for MediumV
2、oltage Junction Boxes, covers requirements for junction boxes used fortermination of medium voltage conductors.ULs Outlines of Investigation are copyrighted by UL LLC. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigatio
3、n and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of ULLLC.COPYRIGHT 2018 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAUGUST 1, 2018UL 30042No Text on T
4、his PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Components 53 Units of Measurement .64 Undated References 65 Glossary .65.1 General .65.2 Equipment ratings 7CONSTRUCTION6 Enclosure 76.1 General .76.2 Ext
5、erior doors, covers, and similar parts of enclosures 86.3 Inspection windows .86.4 Enclosure category .97 Wire Bending Space 97.1 Wire-bending space for field-installed conductors .98 Wiring Terminals .108.1 Connection of current-carrying conductors 108.2 Connection of conductor shields .109 Bus Bar
6、s 1010 Insulating Materials .1111 Provisions for Bonding and Grounding 1111.1 Grounding of exposed metal parts 1111.2 Provision for ground termination 1112 Spacings 13PERFORMANCE13 Low Voltage Auxiliary and Control Equipment 13PERFORMANCE14 Short-Time Withstand Current and Peak Withstand Current Tes
7、ts 1414.1 General .1414.2 Short-time withstand current test .1414.3 Short-time withstand current test on ground bus .1614.4 Short-time withstand current test on neutral bus 1714.5 Peak withstand current test 1815 Dielectric Tests .1915.1 General .1915.2 Impulse withstand tests .2015.3 Power-frequenc
8、y voltage withstand test .2215.4 Test for bus bar insulation .2316 Driven Rain Test 2316.1 General .2316.2 Test method .2316.3 Evaluation .24AUGUST 1, 2018 UL 3004 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL17 Mechanical Tests of Viewing
9、 Panes .2417.1 General .2417.2 Pressure test 2417.3 Impact test 25RATINGS18 General 25MARKINGS AND INSTRUCTIONS19 General 2520 External Conditions .2621 Terminals 2622 Special Openings .27APPENDIX AA.1 Standards for Components or Standards Referenced A1AUGUST 1, 2018UL 30044UL COPYRIGHTED MATERIAL N
10、OT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirements cover medium voltage junction boxes. Medium voltage junction boxes are ratedover 1000 V ac, up to 38,000 V ac, contain insulators, and bus bars or other means, such as separablei
11、nsulated connector systems, to connect medium voltage conductors. These boxes may also include otherassociated junction boxes such as mechanical supports, ground bus for cable shields, for the purpose ofconnecting medium voltage conductors. These junction boxes are intended to be used in accordance
12、withthe National Electrical Code, NFPA 70.1.2 The conductors may be routed through knockouts or openings in the enclosure for cable, conduit, orelectrical metallic tubing. These junction boxes may also have special openings to match with similaropenings in other equipment such as medium voltage moto
13、r controllers, switchgear, switch or circuitbreaker enclosures, wireways, and the like.1.3 Medium voltage junction boxes are not intended to be used as pull boxes, where cables pass throughthe enclosure without terminating within the enclosure.2 Components2.1 Except as indicated in 2.2, a component
14、of a product covered by this outline shall comply with therequirements for that component. See Appendix A for a list of standards covering components generallyused in the products covered by this outline.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature
15、 or characteristic not required in the application of the component in theproduct covered by this outline, orb) Is superseded by a requirement in this outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incompl
16、ete in construction features or restricted in performance capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.AUGUST 1, 2018 UL 3004 5UL COPYRIGHTED MATERIA
17、L NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appe
18、aring in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.5 GlossaryFor the purpose of this outline, the following definitions apply.5.1 General5.1.1 CLEARANCE The distance between two conductive parts along a string stretched the short
19、estway between these conductive parts.5.1.2 COVER An unhinged portion of an enclosure that covers an opening.5.1.3 CREEPAGE DISTANCE The shortest distance along the surface of an insulating materialbetween two conductive parts.5.1.4 DISRUPTIVE DISCHARGE The phenomena associated with the failure of i
20、nsulation underelectric stress; these include a collapse of voltage and the passage of current. The term applies toelectrical breakdown in solid, liquid, and gaseous dielectrics, and combinations of these dielectrics.5.1.5 DOOR A hinged portion of an enclosure that covers an opening.5.1.6 ENCLOSURE
21、A surrounding case constructed to provide a degree of protection to personnelagainst incidental contact with the enclosed equipment and to provide a degree of protection to theenclosed equipment against specified environmental conditions.5.1.7 PROSPECTIVE CURRENT The current that would flow in the c
22、ircuit if each pole of the circuitwere replaced by a conductor of negligible impedance.NOTE: For testing, the prospective current is determined by calibrating the test circuit with a short circuit placed directly across thetest station terminals. During the actual test, the sample is allowed to be w
23、ired using a maximum of 8 ft of cable connected to boththe line and load side terminals.AUGUST 1, 2018UL 30046UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.2 Equipment ratings5.2.1 RATED CONTINUOUS CURRENT (Ith) The rated continuous curren
24、t is the maximum currentcarried on a continuous basis.5.2.2 RATED DURATION OF SHORT-TIME (tk) The rated duration of short-time withstand current isthe interval of time for which the equipment can carry a current equal to its rated short-time withstandcurrent (Ik). The preferred rated duration is 2 s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT30042018OUTLINEOFINVESTIGATIONFORMEDIUMVOLTAGEJUNCTIONBOXESISSUE1PDF

链接地址:http://www.mydoc123.com/p-1069392.html