UL SUBJECT 299C-2016 Outline of Investigation for Fire Extinguishing Dry Chemical for Special Applications (Issue 3).pdf
《UL SUBJECT 299C-2016 Outline of Investigation for Fire Extinguishing Dry Chemical for Special Applications (Issue 3).pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 299C-2016 Outline of Investigation for Fire Extinguishing Dry Chemical for Special Applications (Issue 3).pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMay 6, 20161UL 299COutline of Investigation for Fire Extinguishing Dry Chemical for SpecialApplicationsIssue Number: 3May 6, 2016Summary of TopicsThis third issue of the Outline of Investigation
2、for Fire Extinguishing DryChemical For Special Applications, UL 299C, includes labelingrequirements and editorial revisions.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Inv
3、estigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2016 UL LLCUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULMAY 6, 2016UL 299C2No Text o
4、n This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .44 Undated References 55 Glossary .5CONSTRUCTION6 General 5PERFORMANCE7 General 58 Elevated Temperature Test 69 Hygr
5、oscopicity Test .610 Packed Chamber Test 611 Application Density Test 7MARKING12 General .713 Identification of Contents 8INSTRUCTIONS14 Installation and Design Instructions 8Annex AMAY 6, 2016 UL 299C 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION
6、 FROM ULINTRODUCTION1 Scope1.1 These requirements cover evaluation of dry chemical for physical properties and for fire fightingcapabilities intended for Class B hazards for application in extinguishers and extinguishing systems thatare outside the scope of current installation standards due to spec
7、ial hazard characteristics.1.2 The dry chemical covered by this outline is intended to be applied to extinguish special hazard firesthat are outside the scope of current installation standards. The dry chemical may be distributed throughfixed piping and nozzles, portable fire extinguishers, or other
8、 methods suitable to the Authority HavingJurisdiction. The mass of the dry chemical applied over the area to be protected is to be determined andpublished.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this outline shall comply with therequirements for that component
9、.2.2 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the component in theproduct covered by this outline, orb) Is superseded by a requirement in this outline.2.3 A component shall be used in accordance with its rec
10、ognized rating established for the intendedconditions of use.2.4 Specific components are recognized as being incomplete in construction features or restricted inperformance capabilities. Such components are intended for use only under limited conditions, such ascertain temperatures not exceeding spe
11、cified limits, and shall be used only under those specific conditionsfor which they have been recognized.3 Units of Measurement3.1 When a value for measurement is followed by a value in other units in parentheses, the second valuemay be only approximate.MAY 6, 2016UL 299C4UL COPYRIGHTED MATERIAL NOT
12、 AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this outline shall beinterpreted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpos
13、es of these requirements, the following definitions shall apply.5.2 DESICCATOR A suitable airtight vessel used to dry samples.5.3 FRIABLE Dry Chemical that has agglomerated (formed lumps, hardened or caked) due to packingor moisture that is able to have the agglomerated broken into particles or the
14、unagglomerated state aftertesting.5.4 STRATIFIED Dry chemical that has formed layers of specific particle size(s).5.5 TUBULAR THIEF A multi-chambered tube with a pointed end used to obtain a representativesample dry chemical from a large quantity.CONSTRUCTION6 General6.1 The hand-portable extinguish
15、er used in the Application Density Test, Section 11, and PackedChamber Test, Section 10, shall consist of a cartridge-operated extinguisher.PERFORMANCE7 General7.1 Representative samples of dry chemical extinguishing agent are to be subjected to the testsdescribed in these requirements.7.2 When subj
16、ected to the tests specified in 7.3 and 7.4, the dry chemical shall be free flowing at alltemperatures in the range from the minimum storage and use temperature to 66C (140F), except thatshould there be any tendency to lump, harden, or cake, such portions shall be friable when dropped froma height o
17、f 100 5 mm (4 in) onto a smooth, hard surface.7.3 Prior to the tests, all dry chemical samples are to be conditioned in a desiccator containing sufficientanhydrous calcium chloride to cover the bottom of the desiccator, for 48 hours at room temperature.7.4 The samples required are to be taken from a
18、 container of dry chemical of approximately 23 kg (50 lb)size that has been rolled or tumbled vigorously through at least 20 revolutions in each of two differentdirections. The individual samples are to be taken using a tubular “thief” intended to prevent the caking ofa stratified sample.MAY 6, 2016
19、 UL 299C 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL8 Elevated Temperature Test8.1 The apparatus to be used in checking for caking in the elevated temperature test at 60C (140F) isto consist of seamless tinned steel cups approximately 75
20、 mm (3 in) in diameter and 50 mm (2 in) deep0.24 L (8 oz) capacity with closely fitting flanged covers, and a thermostatically controlled oven.8.2 A 100 25 g sample of the dry chemical is to be placed in the cup, completely filling the cup, and thenfitted with its cover. The sample is to be placed i
21、n an oven maintained at 60C (140F). After a minimumof 168 h (1 week), the sample is to be removed from the oven, allowed to cool for a minimum of 72 h (3days), and then examined for evidence of caking. Any lumps present are to be dropped from a height of100 mm (4 in) onto a smooth, hard surface to d
22、etermine whether they are friable.9 Hygroscopicity Test9.1 The apparatus for conducting the hygroscopicity test is to consist of 250 mL beakers, 65 mm watchglasses, a humidity jar, a desiccator jar, and an analytical balance.9.2 Hygroscopicity tests are to be conducted on a 100 g sample in a nominal
23、 250 mL beaker. The sampleis to be placed in a humidity jar with a domed top maintained at a temperature of 21 3C (70 5F) andat approximately 80 percent relative humidity for a minimum period of 48 hours (2 days). This relativehumidity can be obtained by maintaining a saturated solution of ammonium
24、chloride by adding and mixinguntil it contains an excess of undissolved crystals, at the bottom of the jar.9.3 After 2 days at 80 percent relative humidity, the 100 g sample is to be placed in a desiccator jarcontaining anhydrous calcium chloride for a minimum of 48 hours (2 days) and then returned
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT299C2016OUTLINEOFINVESTIGATIONFORFIREEXTINGUISHINGDRYCHEMICALFORSPECIALAPPLICATIONSISSUE3PDF

链接地址:http://www.mydoc123.com/p-1069389.html