1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSEPTEMBER 10, 20151UL 2582Outline of Investigation for Hip and Ridge VentsIssue Number: 3September 10, 2015Summary of TopicsThis third issue of the Outline of Investigation for Hip and Ridge Vent
2、s, UL2582, was issued to clarify that hip or ridge shingles are covered by thisoutline. The title was also changed from Outline of Investigation forRidge Vents to the Outline of Investigation for Hip and Ridge Vents.ULs Outlines of Investigation are copyrighted by UL. Neither a printed norelectronic
3、 copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MA
4、TERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSEPTEMBER 10, 2015UL 25822No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Units of Measurement .5PERFOR
5、MANCE3 General 54 Preparation of Samples 54.1 Spread of flame test samples 54.2 Burning brand and wind test samples .84.3 Conditioning 125 Spread of Flame Fire Test 136 Burning Brand Test 147 Wind-Driven Rain Test .147.1 Test apparatus 147.2 Test .14CONDITIONS OF ACCEPTANCE8 General .15SEPTEMBER 10,
6、 2015 UL 2582 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This Outline of Investigation covers requirements intended to evaluate the fire and wind-driven rainperformance of roof hip or ridge vents. These requirement
7、s are intended to evaluate a hip or ridge ventsresistance to:a) Flame spread due to exposure to fire sources external to a building;b) Flame penetration resulting in flaming droplets; andc) Resistance to water infiltration to the interior attic space.1.2 Class A hip or ridge vents are considered eff
8、ective against severe fire test exposures. Under suchexposures, shingles of this class, afford a high degree of fire protection to the roof deck, do not sip fromposition, and are not expected to produce flying brands.1.3 Class B hip or ridge vents are considered effective against moderate fire test
9、exposures. Under suchexposures, shingles of this class, afford a moderate degree of fire protection to the roof deck, do not slipfrom position, and are not expected to produce flying brands.1.4 Class C hip or ridge vents are considered effective against light fire test exposures. Under suchexposures
10、, shingles of this class, afford a light degree of fire protection to the roof deck, do not slip fromposition, and are not expected to produce flying brands.1.5 Fire tests conducted in accordance with these requirements are intended to demonstrate theperformance of hip or ridge vents during the type
11、s and periods of exposure involved, but are not intendedto determine the acceptability of hip or ridge vents for use after exposure to fire. These fire test methodsdo not provide a basis to compare expected performance under all actual fire conditions but they doprovide a basis for comparison of the
12、 response of hip or ridge vents when subjected to fire sources thatare described herein.1.6 Hip or Ridge vents complying with the requirements for wind-driven rain are not expected to withstandthe wind forces of tornadoes, cyclones, or hurricanes.1.7 Hip or Ridge vents are required to comply also wi
13、th the requirements for construction, materialspecifications, and performance as applicable to specific types, designs, sizes, and arrangements. Allsuch applicable additional requirements are not considered to be within the scope of these requirementsfor fire and wind-driven rain tests, but are incl
14、uded in the applicable standards covering the material inquestion.SEPTEMBER 10, 2015UL 25824UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2 Units of Measurement2.1 Values stated without parentheses are the requirement. Values in parentheses
15、are explanatory orapproximate information.PERFORMANCE3 General3.1 Representative samples of ridge vents shall be subjected to the following tests:a) One Spread of Flame Test;b) One Burning Brand Test; andc) One Wind Driven Rain Test.4 Preparation of Samples4.1 Spread of flame test samples4.1.1 Sprea
16、d of flame test deck construction and conditioning4.1.1.1 Representative samples of ridge vents are to be applied, as described in 4.1.2, Application ofshingles and ridge vents, to test decks constructed as specified in 4.1.1.2.4.1.1.2 The spread of flame fire test deck is to consist of plywood fast
17、ened to trade size 2- by 4-innominal 1-1/2 by 3-1/2 in (38.1 by 89 mm) battens. The battens are to be placed along each side of thetest deck, with the long dimension of the battens perpendicular to the plywood, leaving a 1-3/4 in (44.4mm) overhang of the plywood on one end. Additional battens, perpe
18、ndicular to the two battens along eachside of the deck, are to be used when required for additional support. The test deck dimensions are asfollows:a) Class A shingles and ridge vent test deck 40 in (1.02 m) wide by 8 ft (2.4 m) long;b) Class B shingles and ridge vent test deck 40 in (1.02 m) wide b
19、y 9 ft (2.7 m) long; andc) Class C shingles and ridge vent test deck 40 in (1.02 m) wide by 13 ft (3.9 m) long.SEPTEMBER 10, 2015 UL 2582 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4.1.2 Application of shingles and ridge vents General4.1
20、.2.1 Ridge vents of the same composition and Class rating as the ridge vents to be evaluated are tobe applied to the test deck in accordance with the manufacturers installation instructions. Shingles of atleast the same Class rating as the ridge vents to be evaluated shall be used to construct the t
21、est deck.The long dimension of the shingles for the deck are to be oriented diagonally from bottom-left toupper-right with the ridge vent placed along the approximate diagonal center of the test deck. The spreadof flame test deck construction is illustrated in Figure 4.1. The application is to be su
22、ch that specifiedexposures are maintained and, where applicable, all interlocking mechanisms are in place.This is generated text for figtxt.SEPTEMBER 10, 2015UL 25826UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULFigure 4.1Spread of flame tes
23、t deck constructionSEPTEMBER 10, 2015 UL 2582 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4.2 Burning brand and wind test samples4.2.1 Burning brand and wind-driven rain test deck construction and conditioning4.2.1.1 Representative sample
24、s of ridge vents are to be applied, as described in 4.2.2, Application ofshingles and ridge vents to test decks constructed as specified in 4.2.1.2.4.2.1.2 The ridge test deck is to consist of plywood, tightly matched sheathing boards, or equivalentdecking material, constructed to simulate a roof ri
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT25822015ULOUTLINEFORINVESTIGATIONHIPANDRIDGEVENTSISSUE3PDF

链接地址:http://www.mydoc123.com/p-1069317.html