《UL SUBJECT 2579-2013 OUTLINE OF INVESTIGATION FOR LOW-VOLTAGE FUSES C FUSES FOR PHOTOVOLTAIC SYSTEMS (Issue 9)《低压熔断器-光伏系统用熔断器的调查大纲 (议题9)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 2579-2013 OUTLINE OF INVESTIGATION FOR LOW-VOLTAGE FUSES C FUSES FOR PHOTOVOLTAIC SYSTEMS (Issue 9)《低压熔断器-光伏系统用熔断器的调查大纲 (议题9)》.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 4, 20131UL 2579OUTLINE OF INVESTIGATIONFORLOW-VOLTAGE FUSES FUSES FOR PHOTOVOLTAIC SYSTEMSISSUE NO: 9June 4, 2013Summary of TopicsThis ninth issue of the Outline of Investigation for Low-Vol
2、tage Fuses -Fuses for Photovoltaic Systems, UL 2579, includes the addition of aconstruction to allow integral wire terminations.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 4, 2013UL 25792No
3、 Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSLow-Voltage Fuses Fuses for Photovoltaic Systems1 General 41.1 Scope .44 Classification .45 Characteristics 45.2 Voltage rating 45.4 Frequency .45.5 Interrupting rating
4、.56.1 Marking of fuses 57 Construction 58 Tests 58.2 Verification of temperature rise and current-carrying capacity 68.3 Verification of overload operation .68.4 Verification of operation rated voltage .68.5 Verification of peak let-through characteristics and I2t. 69.0 Service Environment Condition
5、s .79.1 Verification of freedom from unacceptable levels of thermally induced drift 79.2 Verification of functionality at temperature extremes 710.0 Current Cycling 7JUNE 4, 2013 UL 2579 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULLow-Vol
6、tage Fuses Fuses for Photovoltaic Systems1 GeneralNote: This Outline of Investigation is intended to be read together with the Standard for Low-VoltageFuses - Part 1: General Requirements, UL 248-1, hereafter referred to as UL 248-1. The numbering ofthe Clauses in this Outline of Investigation corre
7、sponds to like numbered Clauses in UL 248-1. Therequirements of UL 248-1 apply unless modified by this Outline of Investigation.1.1 ScopeThis Outline of Investigation applies to Fuses for Photovoltaic Systems rated up to 1500 V dc.Fuses for Photovoltaic Systems are intended to be used for the protec
8、tion of strings or arrays ofPhotovoltaic cells and their associated wiring to provide protection against overloads or low-level shortcircuits. These types of fuses are not intended to protect downstream inverter components, such ascapacitors or the discharge of such capacitors back into the arrays o
9、r the array wiring above the fuseinterrupting rating.These fuses may also have integral wiring terminations intended for in-line connection in a photovoltaicsystem, such as connection to or between PV modules or panels.4 ClassificationFuses for Photovoltaic Systems are non-renewable, are not current
10、-limiting and have an interrupting ratingof 10ka. Time-delay ratings are optional.5 Characteristics5.2 Voltage ratingThe voltage rating may be up to 1500 V dc. Preferred ratings are 600 V, 750 V, 1000 V, 1250 V and 1500V.5.4 FrequencyNot applicableJUNE 4, 2013UL 25794UL COPYRIGHTED MATERIAL NOT AUTH
11、ORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.5 Interrupting rating10 ka minimum6.1 Marking of fusesIn addition to the markings required in UL 248-1, the fuse must be marked with the letters “PV” or “gPV”or the text, “Photovoltaic Fuse”.Fuses with integral wiring termina
12、tions shall also be marked in accordance with the Standard for WireConnectors, UL 486A-486B. The marking may be on the fuse, a unit container, or an information sheet.7 ConstructionIn addition to meeting the construction requirements of UL 248-1, a fuse with integral wiring terminationsshall also me
13、et the construction requirements of the Standard for Wire Connectors, UL 486A-486B.8 Tests8.1 A fuse with integral wiring terminations shall additionally be investigated to the mechanical sequencerequirements of the Standard for Wire Connectors, UL 486A-486B.For fuses with integral wiring terminatio
14、ns, all test samples shall be wired based on the instructions of themanufacturer.Table 1Number of Fuses to be testedTest Test Temperature50 C Ambient Total iftime delayTotal if nottime delay8.2 Verification of temperature rise and In3338.3 Verification of overload operationa) tmax(1.35 In)3b) tmax(2
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT25792013OUTLINEOFINVESTIGATIONFORLOWVOLTAGEFUSESCFUSESFORPHOTOVOLTAICSYSTEMSISSUE9 低压 熔断器 系统

链接地址:http://www.mydoc123.com/p-1069313.html