1、October 13, 20041SUBJECT 2446OUTLINE OF INVESTIGATIONFORUNITARY BOILER ROOM SYSTEMSIssue Number 1October 13, 2004Summary of TopicsThis is the first issue of the Outline of Investigation for Unitary BoilerRoom Systems.The UL Foreword is no longer located within the UL Standard. For informationconcern
2、ing the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2004 UNDERWRITERS LABORATORIES INC.OCTOBER 13, 2004SUBJECT 24462No Text on This PageCONTENTSINTRODUCTION1 Scope .52 Components 53 Units of Meas
3、urement .64 Undated References 65 Glossary .6STRUCTURE CONSTRUCTION6 General 67 Outdoor Structures 78 Structure Base 89 Walls 810 Roof Panels .811 Doors 912 Ventilation and Combustion Air 9INSTALLED EQUIPMENT13 Equipment Location .1014 Working Space .1015 Structure Electrical Circuits 1116 Panelboar
4、ds .1117 Lighting Circuits 1218 Attachment-Plug Receptacles 1319 HVAC Circuits 1319.1 General .1319.2 Room type air conditioners 1419.3 Structure type air conditioning systems .1420 Fixed Electric Heating Equipment .1521 Emergency Lighting/Exit Signage .1522 Intrusion Alarms 1623 Smoke/Fire Detectio
5、n/Protection 1624 Piping, Tubing And Fittings 16ELECTRICAL ASSEMBLY25 General 1826 Spacings 1827 Field Wiring 1928 Grounding .2029 Internal Wiring 2130 Cable Trays 2331 Intermediate Metal Conduit (IMC) and Rigid Metal Conduit 2432 Electrical Metallic Tubing (EMT) 2533 Flexible Metal Conduit .2534 Li
6、quid Tight Flexible Metal Conduit 2635 Boxes and Fittings 2636 Transformer Protection 28OCTOBER 13, 2004 SUBJECT 2446 337 Main Disconnect 2938 Service Equipment Services Rated 600 V or Less 2939 Motors And Motor Overload Protection 3140 Control Cabinets 3241 Securement Of Components .3942 Fuses and
7、Fuse Holders .40PERFORMANCE43 General 4044 Test Voltage .4045 Power Input Test .4146 Rain Test 4147 Wind Test 4448 Dielectric Voltage-Withstand Test .46MANUFACTURING AND PRODUCTION TESTS49 General 47MARKING50 General 47INSTRUCTIONS51 General 50OCTOBER 13, 2004SUBJECT 24464INTRODUCTION1 Scope1.1 Thes
8、e requirements apply to unitary boiler room systems intended for general use rated 600 volts orless. The structure of the system is not intended for occupancy by personnel for other than operating thecontrolled equipment or performing equipment maintenance.1.2 These products consist of an overall en
9、closure, with related lighting and control power circuits, andelectrical equipment together with the associated piping and wiring between equipment.1.3 The systems as covered by these requirements are intended for installation in accordance with theStandards for Installation of Oil-Burning Equipment
10、, NFPA 31, and other codes such as the National FuelGas Code, NFPA 54, the National Electrical Code, NFPA 70, International Mechanical Code (ICC), andthe Uniform Mechanical Code (IAPMO).1.4 Equipment covered by these requirements may be operated without a qualified attendantcontinuously on duty.2 Co
11、mponents2.1 Except as indicated in 2.2, a component of a product covered by this Outline of Investigation shallcomply with the requirements for that component.2.2 A component need not comply with a specific requirement that:a) Involves a feature or characteristic not needed in the application of the
12、 component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or restricted in performance
13、 capabilities.Such components are intended for use only under limited conditions, such as certain temperatures notexceeding specified limits, and shall be used only under those specific conditions.OCTOBER 13, 2004 SUBJECT 2446 53 Units of Measurement3.1 Values stated without parentheses are the requ
14、irement. Values in parentheses are explanatory orapproximate information.3.2 Unless indicated otherwise, all voltage and current values mentioned in this standard are rms.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shall deinterpr
15、eted as referring to the latest edition of that code or standard.5 Glossary5.1 For the purpose of this Outline the following definitions apply.5.2 COMBUSTIBLE MATERIAL Material made of or surfaced with wood, compressed paper, plantfibers, plastics, or other material that can ignite and burn, whether
16、 flameproofed or not, or whetherplastered or unplastered.5.3 STRUCTURE A General cargo container that is totally enclosed and weather-resistant, having arigid roof, rigid side walls, rigid end wall and a floor, having at least one of its end walls equipped withdoors. Identification marking Type Code
17、 “GO”.STRUCTURE CONSTRUCTION6 General6.1 An ISO Series 1 General Purpose Container covered by International Standards ISO 668, Parts 1 to5 of ISO 1496, ISO 8323, marked in accordance with ANSI/ISO 6346, sometimes referred to as“Intermodal freight container” meets the intent of these requirements.6.2
18、 Structures shall be made and finished with the degree of uniformity and grade of workmanshippracticable in a well equipped factory.6.3 Completed structures shall be supplied with all necessary component parts, including provisions forlifting, if required.6.4 Structures shall be fully assembled, inc
19、luding all walls, floors and roofs.6.5 Complete drawings shall be provided that show sidewall, endwall, cross sections, base details andrecommended anchoring methods.6.6 Unless the structure is of a material that will resist corrosion, both inside and outside surfaces shallbe protected by painting,
20、galvanizing, or plating, or a combination thereof.OCTOBER 13, 2004SUBJECT 244666.7 A part of the structure, such as a door or cover, that, when opened, provides access to exposed liveelectrical parts, shall be provided with a means, such as latches, locks, interlocks, or captive fasteners,for firmly
21、 securing it in place. Such fasteners shall be so located or used in multiple so as to hold the dooror cover closed over its entire length. A hinged cover more than 48 inches (1219 mm) long on the hingedside shall have at least a two point latch operated by a single knob or handle, or shall have at
22、least twocaptive fasteners.6.8 Cover plates intended to be removed for inspection purposes shall not exceed 12 ft2(1.11 m2) in areaor 60 lb (27.2 kg) in weight unless equipped with lifting means or hinges.7 Outdoor Structures7.1 A structure intended for outdoor installation shall comply with 7.2 7.7
23、.7.2 Hinges and other attachments shall be resistant to corrosion. Metals shall not be used incombinations that result in galvanic action that adversely affects any part of the device.7.3 Copper, bronze, brass containing not less than 80 percent copper or stainless steel may be usedwithout additiona
24、l protection against corrosion. Aluminum (sheet, extrusion, or cast), die-cast zinc, or othermetal shall be of a grade of alloy known to be corrosion resistant.7.4 Outdoor sheet steel surfaces shall be protected against corrosion by one of the following coatings:a) Hot-dipped mill galvanizing confor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT24462004OUTLINEOFINVESTIGATIONFORUNITARYBOILERROOMSYSTEMSISSUE1 单元 锅炉房 系统 调查 大纲 发布 编号 PDF

链接地址:http://www.mydoc123.com/p-1069285.html