1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 21, 20061SUBJECT 2049OUTLINE OF INVESTIGATIONFORRESIDENTIAL PIPE HEATING CABLEIssue Number: 4June 21, 2006Summary of TopicsThis fourth issue of the Subject 2049 Outline of Investigation forR
2、esidential Pipe Heating Cable includes revisions to the Flexing Test forthe heating section of the cable.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Forewor
3、d is located onULStandardsInfoNet at: http:/ 2006 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 21, 2006SUBJECT 20492No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDIS
4、TRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .4CONSTRUCTION2 Heating Conductors .43 Grounding Component .44 Jacket .55 Nonheating Leads .56 Thermostats 5PERFORMANCE7 Heating Section Tests .58 Complete Cable Tests .69 Permanence of Cord Tag and Marking Tests .7MARKING10 Details 811
5、 Installation Instructions 11JUNE 21, 2006 SUBJECT 2049 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 This outline covers residential pipe heating cable intended to reduce the likelihood of water freezingin exposed pi
6、pes of residences. These devices are considered appliances in accordance with Article 422of the National Electrical Code, NFPA 70.1.2 Cable units employing different heating conductors, insulation, or other forms of construction may beexamined and tested in accordance with the intent of this outline
7、, and if found to be substantiallyequivalent, may be covered.1.3 Residential pipe heating cables may be installed on metal or rigid plastic pipes. Plastic pipes areconsidered to have a maximum long-term thermal exposure limit of 50C absolute.1.4 These heating cables are limited to applications where
8、 they are not exposed to weather unlessadditionally evaluated for outdoor use.CONSTRUCTION2 Heating Conductors2.1 The heating conductors shall be insulated with a suitable insulating compound acceptable for use at75C (167F) or higher in wet locations. The minimum thickness of the insulation shall no
9、t be less than1/32 inch (0.8 mm) when not provided with a nylon jacket and not less than 1/64 inch (0.4 mm) whenprovided with a 4 mil or thicker nylon jacket.2.2 Heating cables which utilize self-regulating positive temperature coefficient (PTC) materials shall beevaluated in accordance with the req
10、uirements for such materials. Reference is made to the Appendix tothe Subject 1434 bulletin dated February 9, 1978, or to more current PTC requirements as appropriate.3 Grounding Component3.1 The heating section shall be provided with a grounding component that consists of a metallic sheathor braid.
11、 If the heating section consists of more than one conductor, the grounding component may beincorporated on each conductor or all conductors may be enclosed with a common sheath or braid. If thegrounding component consists of the braid, it shall provide at least 80 percent coverage and shall employma
12、terial that is corrosion resistant. The grounding component shall have a current-carrying capacity equalto or greater than that of the unit but not less than that of an 18 AWG (0.82 mm2) copper conductor. Thegrounding braid shall be connected to the grounding lead of the non-heating leads.JUNE 21, 2
13、006SUBJECT 20494UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4 Jacket4.1 An optional insulating jacket may be employed over the grounding component.5 Nonheating Leads5.1 The heating section shall be connected to nonheating leads consisting
14、of Type SJ or heavier flexiblecord acceptable for outdoor use that are at least 2 feet (0.61 m) in length. The flexible cord shall not bemore than 6 feet (1.8 m) in length and shall be terminated by a grounding type attachment plug.6 Thermostats6.1 A thermostat for temperature control may be include
15、d in the cable assembly. The thermostat shallcomply with the applicable requirements of the Standard for Temperature-Indicating and -RegulatingEquipment, UL 873.PERFORMANCE7 Heating Section Tests7.1 The heating section of the cable shall be subjected to the tests specified in Table 7.1.Table 7.1Test
16、s for heating section of the cableTest ResultsFlexing test The heating cable shall comply with the Flexing of ShieldedCable Test of the Reference Standard for Electrical Wires,Cables, and Flexible Cords, UL 1581.Conductors shall not open in fewer than 15, 000 cycles.Impact test A. With flat plate, 5
17、 pounds, 1-1/4 inch diameter cylindricalweight, 3 feet height.Shall withstand ten impacts at different locations.B. On 3/4 inch drill rod, 5 pounds, 1-1/4 inch diametercylindrical weight, 1 foot height.Shall withstand ten impacts at different locations.Crushing test 500 pounds: reference Subject 158
18、8, Outline ofInvestigation for Roof and Gutter De-Icing Cable Units.Shall withstand the crushing force specified.Abrasion testaConducted only when insulating jacket is employed overgrounding component. Samples abraded by No. 1/2 emerycloth mounted on a curved plate, 3-1/2 inch radius, withsample sup
19、porting a 3/4 pound weight.Shall withstand 4000 cycles.Ground component ampacity The ground component shall be caused to carry a currentof (1) 135 percent of the branch circuit overload protectionfor 1 hour, and (2) 200 percent of the branch circuitoverload protection for 2 minutes.There shall be no
20、 damage to the insulation on the heatingsection.Cold bend The heating section shall be cooled to minus 35C (minus31F) for 1 hour and then wrapped around a metal mandrel3/8 inch (9.5 mm) in diameter.The insulation shall not crack.Flame test JUNE 21, 2006 SUBJECT 2049 5Table 7.1 Continued on Next Page
21、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 7.1 ContinuedTest ResultsThe heating section shall be subjected to the flame test inaccordance with the Standard for Thermoplastic-InsulatedWires and Cables, UL 83.The insulation shall not
22、flame more than 1 minute after thefinal application of the test flame nor shall flame beconveyed during, between, or after any application of thetest flame.aMay be omitted for units having outer braid or metallic sheath.8 Complete Cable Tests8.1 The complete cable shall be subjected to the tests spe
23、cified in Table 8.1. Tests on PVC pipe areconsidered representative of metal pipe as well.Table 8.1Tests for complete cablesTest ResultsInput The input shall be within 5 percent of the rated input valueof the unit when in the normal operating air temperature.Temperature Installed per manufacturers i
24、nstructions with minimum wrapspacing, tested at operating temperature on 1/2 inch PVCpipe filled with stagnant water.No material shall be exposed to a temperature over itsrating. References to be made to the Standard for ElectricHeating Appliances, UL 499. Temperature on the pipe shallnot exceed 50C
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT20492006OUTLINEOFINVESTIGATIONFORRESIDENTIALPIPEHEATINGCABLEISSUE4 住宅 管道 加热 电缆 调查 纲要 版本号 PDF

链接地址:http://www.mydoc123.com/p-1069222.html