UL SUBJECT 1254H-2013 Outline of Investigation for Stationary and Semi-Portable Hand Hose Line Dry Chemical Extinguishing System Units (Issue 1)《固定式和半便携式手持软管干化学灭火系统装置的调查大纲 (议题1)》.pdf
《UL SUBJECT 1254H-2013 Outline of Investigation for Stationary and Semi-Portable Hand Hose Line Dry Chemical Extinguishing System Units (Issue 1)《固定式和半便携式手持软管干化学灭火系统装置的调查大纲 (议题1)》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1254H-2013 Outline of Investigation for Stationary and Semi-Portable Hand Hose Line Dry Chemical Extinguishing System Units (Issue 1)《固定式和半便携式手持软管干化学灭火系统装置的调查大纲 (议题1)》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOctober 17, 20131UL 1254HOutline of Investigation for Stationary and Semi-Portable Hand Hose LineDry Chemical Extinguishing System UnitsIssue Number: 1October 17, 2013Summary of TopicsThis is the
2、 first issue of the Outline of Investigation for Stationary andSemi-Portable Hand Hose Line Dry Chemical Extinguishing System Units,UL 1254H.COPYRIGHT 2013 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULOCTOBER 1
3、7, 2013UL 1254H2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .52 Units of Measurement .53 Reference Publications 54 Components 55 Glossary .6CONSTRUCTION6 General 66.1 Requirements 66.2 Hose 8
4、6.3 Discharge devices 86.4 Actuation devices .8PERFORMANCE7 General 98 Discharge Duration Test 109 Fire Tests .1010 Rate of Flow Test .1011 Discharge Range Test .1012 Intermittent Discharge Test 1113 Operating Temperature Limits Test .1114 Vibration Test 1114.1 General .1114.2 Mounting of test sampl
5、e .1214.3 Test orientation 1214.4 Variable frequency test .1214.5 Endurance test .1215 Abnormal Operation Test 1316 Pressure-Retention Test .1317 Servicing Tests .13MARKING18 General 14MANUFACTURING AND PRODUCTION19 General 14DESIGN, INSTALLATION, AND MAINTENANCE MANUAL20 General 14OCTOBER 17, 2013
6、UL 1254H 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAPPENDIX AStandards for ComponentsA1OCTOBER 17, 2013UL 1254H4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope
7、1.1 These requirements cover the construction and operation of stationary and semi-portable drychemical extinguishing system units. Dry chemical extinguishing system units are intended to be installed,maintained, tested and inspected in accordance with the Standard for Dry Chemical ExtinguishingSyst
8、ems, NFPA 17.1.2 Stationary and Semi-Portable extinguishing system units require a manual means of operating andfire-fighting and are intended to be used for fire-fighting in the vicinity of the hazard being protected inaccordance with the manufacturers design, installation, and maintenance instruct
9、ions. These devices are:1) not a part of a system with fixed nozzles; and2) not evaluated for fire-fighting performance and are therefore, not assigned a fire rating as forportable fire extinguishers.1.3 Hand hose line extinguishing system units are intended to supplement fixed nozzle extinguishings
10、ystem units or to supplement portable fire extinguishers for the protection of specific hazards for whichdry chemical is a suitable extinguishing agent.2 Units of Measurement2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.3 R
11、eference Publications3.1 See Annex A for a list of publications referenced in this standard. Any undated reference to a codeor standard appearing in the requirements of this standard shall be interpreted as referring to the latestedition of that code or standard. When the latest edition of a standar
12、d is not applicable, the appropriateedition is indicated accordingly in Annex A.4 Components4.1 Except as indicated in 4.2, a component of a product covered by this standard shall comply with therequirements for that component. A component shall comply with the standard for the component.4.2 A compo
13、nent is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in the application of the component in theproduct covered by this standard, orb) Is superseded by a requirement in this standard.OCTOBER 17, 2013 UL 1254H 5UL COPYRIGHTED MATERIAL NOT
14、 AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL4.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.5 Glossary5.1 For the purpose of these requirements, the following definitions and those contained in the currentedi
15、tions of UL 299 and UL 1254 apply:5.2 HAND HOSE LINE EXTINGUISHING SYSTEM UNIT A device intended to be operated by asingle person and intended to be totally or partially assembled at the installation location using thecomponents specified in the installation instructions and consists of an extinguis
16、hing agent that can bedischarged through (1) a hose and nozzle assembly connected by fixed piping or (2) a turret nozzleassembly connected directly to a supply of extinguishing agent under pressure, for the purpose ofsuppressing or completely eliminating a fire.5.3 HOSE STATION The location where a
17、hose reel and nozzle, turret nozzle, and a means foroperating the unit are located.5.4 SEMI-PORTABLE HAND HOSE LINE EXTINGUISHING SYSTEM UNIT A hand hose line fireextinguishing system unit that can be transported to a location, such as a skid mounted device, or withthe use of an auxiliary moving dev
18、ice such as a dolly or truck.5.5 STATIONARY HAND HOSE LINE EXTINGUISHING SYSTEM UNIT A hand hose line fireextinguishing system unit that is non-transportable and is permanently mounted to a structure.CONSTRUCTION6 GeneralClause 6 effective October 17, 20166.1 Requirements6.1.1 For the purpose of the
19、se requirements, the following construction requirements and those containedin the current edition of UL 1254 applyOCTOBER 17, 2013UL 1254H6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUL 1254, Ed 4, Sec 6 GENERALUL 1254, Ed 4, Sec 7 ELECTR
20、ICALLY OPERATED ALARMSUL 1254, Ed 4, Sec 8 CONTROLS AND INDICATORSUL 1254, Ed 4, Sec 9 CAPS, VALVES, AND CLOSURESUL 1254, Ed 4, Sec 10 PRESSURE VESSELS AND CYLINDERSUL 1254, Ed 4, Sec 11 GASKETS AND O-RINGSUL 1254, Ed 4, Sec 12 GAS CARTRIDGESUL 1254, Ed 4, Sec 13 PRESSURE REGULATORSUL 1254, Ed 4, Se
21、c 14 PRESSURE GAUGESUL 1254, Ed 4, Sec 15 PUNCTURING MECHANISMSUL 1254, Ed 4, Sec 16 SIPHON TUBESUL 1254, Ed 4, Sec 17 DRY CHEMICAL AGENTSUL 1254, Ed 4, Sec 18 NITROGEN AND AIR EXPELLANT GASESUL 1254, Ed 4, Sec 19 POLYMERIC MATERIALS AND NONMETALLIC PARTSUL 1254, Ed 4, Sec 20 ANTI-RECOIL DEVICESUL 1
22、254, Ed 4, Sec 22 ELECTRICALLY OPERATED DEVICESUL 1254, Ed 4, Sec 23 PRESSURE SWITCHES6.1.2 Extinguishing system units shall be constructed to be actuated at each hose station.6.1.3 Extinguishing system units with multiple hose stations where simultaneous use of two or more hoselines is possible, sh
23、all be constructed with a sufficient quantity and flow rate of dry chemical to supply themaximum number of nozzles that are likely to be used at any one time for at least 30 s.6.1.4 Extinguishing system units or hose stations intended to be stored outdoors shall be constructed withprotection against
24、 the weather.6.1.5 An extinguishing system unit shall be constructed to operate as intended from the minimum storagetemperature of -40C (- 40F) or -54C (-65F) to 49C (120F).6.1.6 The edges and surfaces of a valve, cap, closure, hose, cylinder, handle, mounting device, andsimilar items, shall be cons
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT1254H2013OUTLINEOFINVESTIGATIONFORSTATIONARYANDSEMIPORTABLEHANDHOSELINEDRYCHEMICALEXTINGUISHINGSYSTEMUNITSISSUE1

链接地址:http://www.mydoc123.com/p-1069144.html