UL 98 CRD-2016 UL Standard for Safety Enclosed and Dead-Front Switches - Section Paragraph Reference 7 2 8 8 2 Tables 16 19 and 22 Subject Add Requirements for Class CA AB and G F.pdf
《UL 98 CRD-2016 UL Standard for Safety Enclosed and Dead-Front Switches - Section Paragraph Reference 7 2 8 8 2 Tables 16 19 and 22 Subject Add Requirements for Class CA AB and G F.pdf》由会员分享,可在线阅读,更多相关《UL 98 CRD-2016 UL Standard for Safety Enclosed and Dead-Front Switches - Section Paragraph Reference 7 2 8 8 2 Tables 16 19 and 22 Subject Add Requirements for Class CA AB and G F.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): WHXS, WIAX, WIZZ, WHTY2Standard Number: UL 98Standard Title: Standard for Enclosed and Dead-Front SwitchesEdition Date: February 25, 2004Edition Number: 13Se
3、ction / Paragraph Reference: 7.2.8, 8.2, Tables 16, 19 and 22Subject: Add Requirements for Class CA, AB and G FusesDECISION:The following revisions address missing requirements for Class CA, CB and G fuses to UL 98, whichpresently allows their use:Table 16Maximum acceptable temperature risesMaterial
4、 and components CA. Terminals for field-installed conductors:1. Unfused switches 502. Fused switches for use with 60C wire and tested with dummy fuses 303. Fused switches for use with 75C wire and tested with dummy fusesa454. Class CA, CC, G, and T fused switches rated 100 A or less for use with 60C
5、 wire 505. Class CA, CC, G, and T fused switches rated 100 A or less for use with 75C wirea656. Class J (rated more than 200 A), Class T (rated more than 100 A), Class L and Class C fusedswitches60B. All other current-carrying parts:1. Unfused switches 502. Fused switches for use with 60C wire and t
6、ested with dummy fuses 303. Fused switches for use with 75C wire and tested with dummy fusesa504. Class J (rated more than 200 A), Class T, Class L, and Class C fused switches 85C. Other materials and components:1. Wire insulation or insulating tubing 352. Electrical tape 553. Varnished cloth insula
7、tion 604. Fiber used as electrical insulation 655. Sealing compound 506. Phenolic composition used as electrical insulation or as a part whose failure would result in anundesired condition1257. Other insulating materials. baApplicable to a connector for copper wire. Also applicable to a connector fo
8、r aluminum wire or an aluminum-bodiedconnector, if the connector has a temperature rating of 90C.bRated temperature limit of material minus test ambient temperature.7.2.8 A switch employing the following fuse Classes shall be tested with fuses in place and when carrying80 percent of its rated curren
9、t continuously:1. C, CA, CB, G, L, or T;, or C fuses orUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2. Class J rated 400 or 600 A Class J fuses shall be tested with fuses in place and whencarrying 80 percent of its rated current continuousl
10、y.Table 17Overload-test currents in amperes for alternating-current switchesSwitch inrating120 V 240 V 480 V 600 VkW hp 1 24-Wire3 1 24-Wire3 1 24-Wire3 1 24-Wire30.125 1/6 26.4 13.2 0.187 1/4 34.8 17.4 0.248 1/3 43.2 21.6 0.373 1/2 58.8 40 29.4 20 10 80.56 3/4 82.8 28.8 50 41.4 14.4 25 21 7.2 12.5
11、16.8 6 100.746 1 96 38.4 60 48 19.2 30 24 9.6 15 19.2 7.8 121.119 1-1/2 120 54 80 60 27 40 30 13.8 20 24 10.8 161.492 2 144 70.8 100 72 35.4 50 36 18 25 28.8 14.4 202.238 3 204 99.6 102 49.8 64 51 25.2 32 40.8 19.8 25.63.73 5 336 158 168 79.2 92 84 39.6 46 67.2 31.8 36.85.6 7-1/2 480 228 240 114 127
12、 126 54 63.5 96 48 50.87.46 10 600 288 300 144 162 156 72 81 120 60 64.811.19 15 432 216 232 108 116 84 9314.92 20 564 282 290 138 145 114 11618.65 25 708 354 365 174 183 144 14622.38 30 828 414 435 210 218 168 17429.84 40 1 080 540 580 270 290 216 23237.3 50 1 360 678 725 336 363 270 29044.76 60 87
13、0 435 34855.95 75 1 085 543 43474.6 100 1 450 725 58093.25 125 1 815 908 726111.9 150 2 170 1 085 868149.2 200 2 900 1 450 1 160186.5 250 1 825 1 460223.8 300 2 200 1 760261.1 350 2 550 2 040298.4 400 2 900 2 320335.7 450 3 250 2 600373.0 500 3 625 2 900STANDARD NUMBER: UL 98 -2-UL COPYRIGHTED MATER
14、IAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 18Overload test currents in amperes for direct-current switchesRating 125 V 250 V 600 VkW hp0.373 1/2 32.4 16.2 0.56 3/4 45.6 22.8 9.60.746 1 38 19 71.119 1-1/2 53 26 101.492 2 68 34 142.238 3 100 49 203.730 5
15、 160 80 335.600 7-1/2 232 116 487.460 10 304 152 6411.19 15 448 220 9214.92 20 592 288 12418.65 25 356 15222.38 30 424 18429.84 40 560 24437.30 50 692 300Table 19Endurance test cyclesSwitch rating inamperesNumber of cycles ofoperation per minuteaNumber of cycles of operationWith current Without curr
16、ent Total30 100 and less 6 6 000 4 000 10 000200 5 6 000 2 000 8 000400 4 1 000 5 000 6 000600 3 1 000 4 000 5 000800 2 500b3 000 3 5001 200 1 500b2 000 2 5001 600 2 500 1 500 2 000 2 500c3 000 4 000 1d400 1 100 1 500caThe indicated number of cycles of operation per minute applies only to that part
17、of the test made with current. When nocurrent is used, the switch may be operated at any convenient speed.bFor a switch marked For isolating use only (see 9.2.10) the switch is not operated with current in the endurance test.cFor switches rated over 1 200 A at 250 V or less and marked in accordance
18、with 9.2.10, the total number of operations is1000 without current.dRate of operation: 1 cycle per minute for first ten operations; thereafter in groups of five (at 1 cycle per minute) with aninterval between groups that is agreeable to all concerned.STANDARD NUMBER: UL 98 -3-UL COPYRIGHTED MATERIAL
19、 NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 20Endurance-test currents in amperes for alternating-current switchesSwitch ratingin120 Va240 V 480 V 600 VkW hp 1 24-Wire3 1 24-Wire3 1 24-Wire3 1 24-Wire30.125 1/6 4.4 2.2 0.187 1/4 5.8 2.8 0.248 1/3 7.2 3.6 0.
20、373 1/2 9.8 4.0 4.4 4.9 2.0 2.2 1.0 1.1 0.8 0.90.560 3/4 13.8 4.8 6.4 6.9 2.4 3.2 3.5 1.2 1.6 2.8 1.0 1.30.746 1 16 6.4 8.4 8 3.2 4.2 4.0 1.6 2.1 3.2 1.3 1.71.119 1-1/2 20 9.0 12 10 4.5 6 5.0 2.3 3 4.0 1.8 2.41.492 2 24 11.8 13.6 12 5.9 6.8 6.0 3.0 3.4 4.8 2.4 2.72.238 3 34 16.6 19.2 17 8.3 9.6 8.5
21、4.2 4.8 6.8 3.3 3.93.73 5 56 26.4 30.4 28 13.2 15.2 14. 6.6 7.6 11.2 5.3 6.15.60 7-1/2 80 38 44 40 19 22 21 9 11 16 8 97.46 10 100 48 56 50 24 28 26 12 14 20 10 1111.19 15 135 72 84 68 36 42 34 18 21 27 14 1714.92 20 94 108 88 47 54 44 23 27 25 19 2218.65 25 118 136 110 59 68 55 29 34 44 24 2722.38
22、30 138 160 136 69 80 68 35 40 54 28 3222.84 40 180 208 176 90 104 88 45 52 70 36 4137.30 50 226 260 216 113 130 108 56 65 86 45 5244.76 60 154 77 6255.95 75 192 96 7774.60 100 248 124 9993.25 125 312 156 125111.9 150 360 180 144149.2 200 480 240 192186.5 250 302 242223.8 300 361 289261.1 350 414 336
23、298.4 400 477 382335.7 450 515 412373.0 500 590 472aFor 127 V ratings, the test is conducted at rated voltage with the currents in this column.STANDARD NUMBER: UL 98 -4-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 21Endurance-test cur
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL98CRD2016ULSTANDARDFORSAFETYENCLOSEDANDDEADFRONTSWITCHESSECTIONPARAGRAPHREFERENCE72882TABLES1619AND22SUBJECTADDREQUIREMENTSFORCLASSCAABANDGFPDF

链接地址:http://www.mydoc123.com/p-1069102.html