UL 719 CRD-2018 UL Standard for Safety Nonmetallic-Sheathed Cables - Section Paragraph Reference Revised 3 10 4 3 2 4 4 1 4 6 1 1 4 6 2 5 6 1 5 14 5 15 5 16 7 12 2 7 15 Table 1 Ne.pdf
《UL 719 CRD-2018 UL Standard for Safety Nonmetallic-Sheathed Cables - Section Paragraph Reference Revised 3 10 4 3 2 4 4 1 4 6 1 1 4 6 2 5 6 1 5 14 5 15 5 16 7 12 2 7 15 Table 1 Ne.pdf》由会员分享,可在线阅读,更多相关《UL 719 CRD-2018 UL Standard for Safety Nonmetallic-Sheathed Cables - Section Paragraph Reference Revised 3 10 4 3 2 4 4 1 4 6 1 1 4 6 2 5 6 1 5 14 5 15 5 16 7 12 2 7 15 Table 1 Ne.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): PWVXStandard Number: UL 719Standard Title: Standard for Nonmetallic-Sheathed CablesEdition Date: September 8, 2015Edition Number: 13Section / Paragraph Reference: Revised 3.10, 4.3.2, 4.4.1, 4.6.1.1,
3、4.6.2, 5.6.1, 5.14,5.15, 5.16, 7.12.2, 7.15, Table 1; New 4.6.1.3, 4.6.2.2, 4.6.2.3, 6.1.16, 6.1.17, 6.1.18,6.2.11Subject:NM-PCS cableDECISION:3.10 SIGNAL/CONTROL CONDUCTORS Conductors installed as Class 2 and Class 3 in accordancewith Article 725 of the National Electrical Code(NEC).3.10 11THERMOPL
4、ASTIC - a polymeric material that repeatedly can be softened by heating andhardened by cooling through a temperature range characteristic of the material, and that in the softenedstate can be shaped through the application of force.4.3.2 A copper circuit conductor shall not be smaller than 14 AWG an
5、d shall not be larger than 2 AWG.An aluminum or copper-clad aluminum circuit conductor shall not be smaller than 12 AWG and shall notbe larger than 2 AWG. Signal/control conductors used within a Type NM-PCS cable shall be 18 or 16AWG copper.4.4.1 Both before and after assembly into finished cable, t
6、he insulation employed on the circuit conductorsshall comply with (a) or (b) and the insulation employed on the control/signal conductors shall comply with(c):a) THHN Construction - Jacketed insulation for a Type NM or NMC cable shall have a nylon orsimilar jacket and shall comply with the thickness
7、 and other applicable requirements for TypeTHHN thermoplastic-insulated wire without (see 6.2.4) any surface marking of THHN, -B,orany ampacity or temperature rating.b) TW Construction - Insulation without a nylon jacket shall comply with the thicknessrequirements for a Type TW thermoplastic-insulat
8、ed wire. The insulation material shall complywith (1) or (2):2) For TYPE NM only - Type NM is eligible to use a thermoplastic insulating materialother than PVC. The performance and ratings of the material as insulation shall bedetermined by investigation and shall be:ii) Mechanically comparable to t
9、he nylon or similarly jacketed PVC insulation of TypeTHHN wire, andiii) In accordance with “Physical properties of insulation of thermoplastic other than PVCfrom Type NM cables” Table in UL 1581.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL
10、(c) Insulated control/signal conductors - The insulation material shall be a dry-locations PVCthat complies with the requirements for Type TFN insulation without any surface marking of thetemperature rating. The tensile strength and elongation shall comply with the “Physicalproperties of PVC insulat
11、ion from Type TFN and TFFN fixture wires Table 50.155 in UL 1581.The deformation test is to be conducted at 121.0 1.0C (249.81.8F) with a decrease of notmore than 50 percent in the thickness of the PVC insulation. The force to be used is 300 gramsfor 18 AWG and 400 grams for 16 AWG conductors.4.6 As
12、sembly4.6.1 General4.6.1.1 At least two but not more than four circuit conductors, and an optional “-PCS” signal/controlsubassembly in accordance with 4.6.1.3 shall be used in a Type NM cable. Two or three circuit conductorsshall be used in a Type NMC cable. In a given cable all of the circuit condu
13、ctors shall be of the same size.4.6.1.2 One grounding conductor shall be used in every cable.4.6.1.3 PCS SubassembliesA round or flat NM cable may employ a -PCS” subassembly consisting of two 18 or 16 AWGsignal/control conductors for use in Class 2 and Class 3 circuits with a thermoplastic jacket ov
14、erthe two 18 or 16 AWG conductors. The thermoplastic jacket shall be a minimum of 30 mils(0.76mm) thick. The thermoplastic jacket shall meet the requirements of 5.2.Exception: A flat NM cable may employ a -PCS” subassembly consisting of two 18 or 16 AWGconductors for use in Class 2 and Class 3 circu
15、its provided with an overall thermoplastic jacketthat is a minimum of 60 mils (1.52mm) thick where the PCS subassembly is attached to thepower conductor subassembly by a web or similar means. The thermoplastic jacket shall meetthe requirements of 5.2.4.6.2 Cabling Methods4.6.2.1 In Type NM cables co
16、ntaining two circuit conductors, the circuit conductors shall either be laidparallel or shall be cabled with a length of lay that is not longer than indicated in Table 2. In Type NMcables containing more than two two or more circuit conductors, the circuit conductors shall be cabled witha length of
17、lay no longer than indicated in Table 2 except that, for sizes 14 - 10 AWG copper or 12 - 10AWG aluminum or copper-clad aluminum, whether or not a binder is employed, the circuit conductorsshall either be cabled with a length of lay which is not specified, shall be bundled together parallel to onean
18、other, or shall be laid parallel. In Type NMC cables, the circuit conductors shall be laid parallel. In around cable, the direction of lay may be changed at intervals throughout the length of the cable. Theintervals need not be uniform. In a cable in which the lay is reversed:a) Each area in which t
19、he lay is right- or left-hand for not less than 5 complete twists (full 360cycles) shall have the insulated conductors cabled with a length of lay that is not greater thanindicated in Table 2, andb) The length of each lay-transition zone (oscillated section) between these areas of right- orleft-hand
20、 lay shall not exceed 1.8 times the maximum length of lay indicated in Table 2.4.6.2.2 A flat NM-PCS cable shall consist of an NM cable where either 1) the NM cable is joined to thePCS subassembly by means of a web or similar method or 2) the power conductors and PCSsubassembly are contained under t
21、he overall jacket. One of the following constructions is acceptable.STANDARD NUMBER: UL 719 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL(a) A flat NM-PCS cable may consist of an NM cable connected in parallel to a “-PCS”subassembly with
22、 an additional jacket of not less than 30 mils over the PCS subassembly asnoted in 4.6.1.3(a) There shall be no reduction in the overall jacket thickness when the PCSportion is separated from the circuit conductor portion.(b) A flat NM-PCS cable may consist of an NM cable in parallel with the PCS su
23、bassembly.4.6.2.3 A round NM-PCS cable shall consist of circuit conductors as described in 4.6.2.1 and a “-PCS”subassembly as described in 4.6.1.3(a) all within the overall NM cable jacket. The overall jacket shall notbe less than 30 mils. The cabling of the circuit conductors and jacketed signal/co
24、ntrol cables shall meetthe requirements in 4.6.2.1.5.6 Vertical flame5.6.1 When tested in accordance with 7.6, a vertical specimen of finished Type NMC cable, of finishedType NM cable, and of the insulated circuit conductors shall not flame longer than 60 seconds followingfive 15 second applications
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL719CRD2018ULSTANDARDFORSAFETYNONMETALLICSHEATHEDCABLESSECTIONPARAGRAPHREFERENCEREVISED31043244146114625615145155167122715TABLE1NEPDF

链接地址:http://www.mydoc123.com/p-1068843.html