UL 705 CRD-2016 UL Standard for Safety Power Ventilators - Section Paragraph Reference New Section 11A (Edition 6 January 14 2004).pdf
《UL 705 CRD-2016 UL Standard for Safety Power Ventilators - Section Paragraph Reference New Section 11A (Edition 6 January 14 2004).pdf》由会员分享,可在线阅读,更多相关《UL 705 CRD-2016 UL Standard for Safety Power Ventilators - Section Paragraph Reference New Section 11A (Edition 6 January 14 2004).pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): ZACT, ZACZ, ZAJS, ZAXHStandard Number: UL 705Standard Title: Standard for Power VentilatorsEdition Date: January 14, 2004Edition Number: 6Section / Paragraph Reference: New Section 11ADECISION:2.XXX C
3、ircuit, Class2Anlowvoltage circuit with a power of 100 VA or less; or has 30 V dc suppliedby a primary battery; or is supplied by a Class 2 transformer; or is supplied by a combination of atransformer and fixed impedance that, as a unit, complies with all the performance requirements for aClass 2 tr
4、ansformer, or is supplied by a power supply (such as a switching power supply) whose outputmeets the requirements of a Class 2 circuit.A circuit that is derived from a circuit that exceeds 30 V by connecting resistance or impedance, or both,in series with the supply circuit to limit the voltage and
5、current, is not considered to be a class 2 circuit.2.1XXX Circuit, low-voltage A circuit that has an ac potential of not more than 30 V rms (42.4 V peakor 30 V dc).2.2XXX Circuit, hazardous voltage A circuit of any voltage exceeding those of an low-voltage circuit.2.4 MOTORS a) Open Motor A motor ha
6、ving ventilating openings that permit passage of external cooling airover and around the windings of the motor.b) Totally Enclosed Motor A motor that is enclosed so as to prevent the free exchange of airbetween the inside and outside of the case but not sufficiently enclosed to be termed airtight.c)
7、 Totally Enclosed Fan-Cooled Motor A totally enclosed motor with external cooling by a fanor fans integral with the motor but external to the enclosing parts.d) Electronically Commutated Motor (ECM) A motor assembly consisting of the motor and acontrol. The control provides an AC electric signal (ty
8、pically non-sinusoidal) to the motor by aninverter/switching power supply. The sensors and other electronics on the control adjustwaveform and output levels of the signal. The control is often used to provide protectivefunctions to prevent overheating or mitigate other hazardous conditions.11A Separ
9、ation of circuits11A.1 Unless having insulation suitable for the highest voltage involved, insulated conductors of differentcircuits (internal wiring, including wires in a junction box or compartment) shall be separated by barriers,or shall be segregated, and shall, in any case, be separated or segr
10、egated from uninsulated live partsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULconnected to different circuits. Segregation of insulated conductors may be accomplished by clamping,routing, or equivalent means that ensures permanent separati
11、on from insulated or uninsulated live partsof a different circuit.11A.2 There shall be provision for segregating or separating by barriers field-installed conductors of anycircuit from field-installed and factory-installed conductors connected to any other circuit, unless theconductors of both circu
12、its are or will be insulated for the maximum voltage of either circuit.11A.3 Within a compartment that is not a control enclosure junction box or its equivalent, field-installedlow-voltage (including Class 2) circuit conductors may be segregated from factory-installed conductors ofdifferent circuits
13、 by locating field wiring openings, routing factory wiring, and locating electricalcomponents so that the factory conductors are maintained at least 127 mm (5 in) from a line representingintended routing of the low-voltage (including Class 2) circuit conductors. The line shall allow for droop,and sh
14、all connect the opening provided for entrance of the low-voltage (including Class 2) conductors tothe terminals or leads to which the conductors are attached.11A.4 There shall be provision for segregating or separating by barriers field-installed conductors of ahazardous voltage circuit froma) unins
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL705CRD2016ULSTANDARDFORSAFETYPOWERVENTILATORSSECTIONPARAGRAPHREFERENCENEWSECTION11AEDITION6JANUARY142004PDF

链接地址:http://www.mydoc123.com/p-1068831.html