UL 651 CRD-2014 UL Standard for Safety Schedule 40 80 Type EB and A Rigid PVC Conduit and Fittings - Section Paragraph Reference Paragraphs 1 1 1 1 2 5 5 1 1 5 4 5 4 1 5 4 1 1 5 4 .pdf
《UL 651 CRD-2014 UL Standard for Safety Schedule 40 80 Type EB and A Rigid PVC Conduit and Fittings - Section Paragraph Reference Paragraphs 1 1 1 1 2 5 5 1 1 5 4 5 4 1 5 4 1 1 5 4 .pdf》由会员分享,可在线阅读,更多相关《UL 651 CRD-2014 UL Standard for Safety Schedule 40 80 Type EB and A Rigid PVC Conduit and Fittings - Section Paragraph Reference Paragraphs 1 1 1 1 2 5 5 1 1 5 4 5 4 1 5 4 1 1 5 4 .pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): DWTTStandard Number: UL 651Standard Title: Standard for Schedule 40, 80, Type EB and A Rigid PVC Conduit andFittingsEdition Date: October 25, 2011Edition Num
3、ber: 8Section / Paragraph Reference: Paragraphs 1.1.1, 1.2.5, 5.1.1, 5.4. 5.4.1, 5.4.1.1,5.4.1.2, 5.4.1.3, 5.4.2, 5.4.3 and 9.2.4; Sections 7.4 and 7.5; Table 7.4; Figure 7.6Subject: Nonmetallic Expansion-Deflection FittingsDECISION:1.1.1 These requirements cover Schedule 40, Schedule 80, Type EB an
4、d Type A extruded rigid PVC(polyvinyl chloride) electrical conduit and fittings. These requirements also cover elbows, couplings,adapters, expansion, expansion-deflection, or deflection joints, and similar fittings that are constructed atleast in part of rigid PVC. The designations Schedule 40, Sche
5、dule 80, Type EB, Type A refer toUSA trade sizes of conduit having iron pipe-size outside diameters and specific wall thicknesses.Couplings, adapters, expansion, expansion-deflection, or deflection joints, and similar fittings are intendedto be used with Schedule 40, Schedule 80, Type EB and Type A
6、rigid PVC conduit, and elbows, inaccordance with the National Electrical Code (NEC), NFPA 70.1.2.5 The expansion joints covered by these requirements are fittings intended to compensate for linearthermal expansion of a span of Schedule 40 and Schedule 80 rigid PVC) conduit.5.1.1 A rigid PVC conduit
7、fitting shall be constructed of an unplasticized polyvinyl chloride material, withor without components made of other materials, that has been determined to be acceptable for theapplication.5.4 Expansion, expansion-deflection, or deflection joints5.4.1 An expansion joint shall be capable of being co
8、nnected to rigid PVC conduit or a coupling at bothends by means of a solvent type cement. An expansion joint is intended to compensate only for linearthermal expansion of a span of rigid PVC conduit.5.4.1.1 An expansion-deflection joint is intended to compensate for linear expansion and compensate f
9、orlateral or angular deflection in a span of rigid PVC conduit.5.4.1.2 A deflection joint intends to compensate only for lateral or angular deflection in a span of rigid PVCconduit.5.4.1.3 An expansion, expansion-deflection or deflection joint shall be capable of being connected to rigidPVC conduit
10、or a coupling at both ends by means of a solvent type cement.5.4.2 Unless an expansion joint, which allows movement between the joint and adjacent conduit lengthsis fastened at one end to rigid PVC conduit, a stop shall be provided to prevent the movable member ofthe joint from exposing either of th
11、e cut ends of the conduit lengths to which the joint is connected.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL5.4.3 The inside end or ends of rigid PVC conduit and the joint at their interface of an expansion joint,regardless of the adjust
12、ment position, shall be free of any snags that would impede fish tape or wires frombeing passed through the joint. The ends shall be beveled to remove any existing snags.7.4 Expansion, expansion-deflection, or deflection joints7.4.1 General7.4.1.1 An expansion, expansion-deflection, or deflection jo
13、int shall be assembled to conduit inaccordance with 7.4.1.7. The expansion, expansion-deflection, or deflection joint shall then be subjectedto the test sequence as appropriate for the type joint specified in Table 7.4.Table 7.4Expansion, expansion-deflection, or deflection joint test sequenceExpans
14、ion joints Expansion-deflection or deflection jointsAssembly (7.4.1.7 and 7.4.2.1) Assembly (7.4.1.7 and 7.4.2.1)Reciprocation test (7.4.3) Reciprocation test (7.4.3) Deflection test (7.4.4)Wet locations test (outdoor or wetlocations joints only, 7.3.2)Wet locations test (outdoor or wetlocations joi
15、nts only, 7.3.2)Wet locations test (outdoor or wetlocations joints only, 7.3.2)7.4.1.2 At the request of the manufacturer, the range of each full cycle of reciprocation in 7.4.3 for anexpansion-deflection joint may be increased to correspond with the declared deflection range of the joint.See 7.4.1.
16、5.7.4.1.3 An expansion-deflection joint having a declared deflection range that exceeds the range of a fullcycle of reciprocations as described in 7.4.3.2 shall be subjected to the Deflection test in 7.4.4.7.4.1.4 An expansion-deflection joint having a declared deflection limit of 3/4 in. (19.1 mm)
17、or less andtested as described in 7.4.3.2 shall not be required to be subjected to the Deflection test in 7.4.4.7.4.1.5 An expansion-deflection joint having a declared deflection limit greater than 3/4 in. (19.1 mm) shallnot be required to be subjected to the Deflection test when the range of each f
18、ull reciprocation cycle forconducting the Reciprocation test in 7.4.3.2 is increased to correspond to the maximum declareddeflection limit as permitted in 7.4.1.2.7.4.1.6 A deflection joint shall be subjected to the test in 7.4.4.7.4.1.7 For the tests in Table 7.4, a set of expansion, expansion-defl
19、ection, or deflection joints shallconsist of six samples each of the smallest, the largest, and one intermediate trade size in a line of joints,and any additional trade size that employs a construction or feature unique to that trade size.7.4.1.8 With the exception of the low-temperature handling te
20、st in 7.2.7, the tests in 7.2 shall be conductedonly on the PVC components of expansion, expansion-deflection or deflection joints. The bending test in7.2.8 and the pull test in 7.2.9 are not applicable for such joints.7.4.1.9 A component of the body of an expansion-deflection, or deflection joint c
21、onstructed of anelastomeric material shall be separately evaluated according to the requirements in 7.5.7.4.2 Assembly testSTANDARD NUMBER: UL 651 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL7.4.2.1 For all lines of expansion, expansion
22、-deflection, or deflection joints, one set of joints shall beassembled in the intended manner to PVC conduit having the dimensions specified in Tables 4.1 and 4.2.7.4.3 Reciprocation test7.4.3.1 An expansion or expansion-deflection joint shall be conditioned as described in 7.4.3.2.7.4.3.2 Each expa
23、nsion or expansion-deflection joint assembled to rigid PVC conduit as required by7.4.1.7 and 7.4.2.1 shall be subjected to 500 cycles of reciprocation. One cycle of reciprocation shallconsist of a 3/4 in (19.1 mm) insertion of the conduit into the joint, followed by withdrawal of the conduitfrom the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL651CRD2014ULSTANDARDFORSAFETYSCHEDULE4080TYPEEBANDARIGIDPVCCONDUITANDFITTINGSSECTIONPARAGRAPHREFERENCEPARAGRAPHS11112551154541541154PDF

链接地址:http://www.mydoc123.com/p-1068794.html