UL 508A CRD-2016 UL Standard for Safety Industrial Control Panels - Section Paragraph Reference Sections 29 3 4 29 3 5 1 (New) SB3 1 and SB4 2 - Subject Wiring Ferrules for use in.pdf
《UL 508A CRD-2016 UL Standard for Safety Industrial Control Panels - Section Paragraph Reference Sections 29 3 4 29 3 5 1 (New) SB3 1 and SB4 2 - Subject Wiring Ferrules for use in.pdf》由会员分享,可在线阅读,更多相关《UL 508A CRD-2016 UL Standard for Safety Industrial Control Panels - Section Paragraph Reference Sections 29 3 4 29 3 5 1 (New) SB3 1 and SB4 2 - Subject Wiring Ferrules for use in.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): NITWStandard Number: UL 508AStandard Title: Standard for Industrial Control PanEdition Date: December 20, 2013Edition Number: 2Section / Paragraph Reference: Sections 29.3.4, 29.3.5.1 (New), SB3.1 and
3、 SB4.2Subject: Wiring Ferrules for use in Industrial Control PanelsDECISION:29.3.4 A connection to a terminal of a component shall be made by:a) Wire inserted directly into a pressure wire terminal of the component;b) Quick-connect terminal of the component, where the mating part is provided with a
4、dimple,depression, or spring-type connection such that a mechanical snap-action connection is madethat does not rely solely upon friction between the two parts;c) Crimped-on pressure terminal connector or closed-loop eyelet;d) Solder terminal specified in 29.3.2;e) Wire-binding screw specified in 29
5、.3.3; orf) Open-type eyelet specified in 29.3.5.g) Wiring ferrule specified in 29.3.5.1.29.3.5.1 A wiring ferrule shall be:a) Used with stranded copper wire(s) onlyb) Terminated in a connector rated for copper wire and rated for the number and size of wire(s)crimped to the ferrule.c) Crimped with an
6、 appropriate tool as recommended by the ferrule manufacturer beforeterminating in a terminal of a component.d) Sized in diameter appropriate for the number of wires and wire size(s) as recommended bythe ferrule manufacturer.e) Crimped to the wires such that the length of the uninsulated portion of t
7、he wires does notresult in the reduction of electrical spacings when the ferrule is installed.SB3.1 Internal wiring connectionsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSB3.1.1 All terminals of power circuit wiring connectors, wiring fer
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL508ACRD2016ULSTANDARDFORSAFETYINDUSTRIALCONTROLPANELSSECTIONPARAGRAPHREFERENCESECTIONS293429351NEWSB31ANDSB42SUBJECTWIRINGFERRULESFORUSEINPDF

链接地址:http://www.mydoc123.com/p-1068269.html