UL 2127 CRD-2018 UL Standard for Safety Inert Gas Clean Agent Extinguishing System Units - Section Paragraph Reference 52 Subject Aging Tests - Plastic Materials (Edition 3 May 9 .pdf
《UL 2127 CRD-2018 UL Standard for Safety Inert Gas Clean Agent Extinguishing System Units - Section Paragraph Reference 52 Subject Aging Tests - Plastic Materials (Edition 3 May 9 .pdf》由会员分享,可在线阅读,更多相关《UL 2127 CRD-2018 UL Standard for Safety Inert Gas Clean Agent Extinguishing System Units - Section Paragraph Reference 52 Subject Aging Tests - Plastic Materials (Edition 3 May 9 .pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): GAQF, GKEC2, GKEE2, GKEH2, GKEK2, GKEP2, GKET2,GKEV2, GKEY2, GKEZ2, GKEC8, GKEE8, GKEH8, GKEK8, GKEP8, GKET8,GKEV8, GKEY8, GKEZ8, GOYW, VKYP, VKYP7Standard Number: UL/ULC 2127Standard Title: Standard
3、for Inert Gas Clean Agent Extinguishing System UnitsEdition Date: May 9, 2017Edition Number: 3Section / Paragraph Reference: 52Subject: Aging Tests - Plastic MaterialsDECISION:52 Aging Tests - Plastic Materials52.1 Air-oven aging test52.1.1 There shall be no cracking of a plastic part subjected to t
4、he flow of clean agent, or bracket, afterair-oven aging for 180 days at 100C (212F). Aged samples of the valve, valve part, bracket, or containershall perform as intended when tested as specified in 26.4 (valves and parts); Hydrostatic Pressure Test,Section 26 (containers); 34.1 (brackets); High Pre
5、ssure Discharge Test, Section 29 (nozzles); or the BurstStrength Test - Gauges, Section 45 (pressurized gauge components). See 52.1.4 - 52.2.4.52.1.2 Following air-oven aging for 90 days at 100C (212F), there shall be no cracking of a plasticsiphon tube, and aged samples of the siphon tube shall per
6、form as intended. Ring samples cut from theaged tube shall not exhibit a degradation in excess of 40 percent of the original tensile or ring crushingstrength values.52.1.3 When a plastic material is not capable of withstanding the temperature specified in 52.1.1 and52.1.2 without excessive softening
7、, distortion, or deterioration, an air-oven aging test at a lowertemperature for a longer period of time meets the intent of this requirement. The equivalent time andtemperature for 180 days at 100C (212F) is to be 430 days at 87.0C (188.6F). The equivalent timeand temperature for 90 days at 100C (2
8、12F) is to be 210 days at 87.0C (188.6F).52.1.3 When a plastic material is unable to withstand the temperature specified in 52.1.1 and 52.1.2without excessive softening, distortion, or deterioration, an air-oven aging test at a lower temperature fora longer period of time is permitted to be used. Wh
9、en a plastic material is able to withstand a highertemperature than specified in 52.1.1 and 52.1.2 without excessive softening, distortion, or deterioration,an air-oven aging test at a higher temperature for a shorter period of time is permitted to be used.For 52.1.1,t = 146040 e-0.067 TFor 52.1.2,t
10、 = 60930 e-0.0652 TUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULwhere:t = Aging duration in days; t 25 daysT = Aging temperature in C; T 87C52.1.4 When plastic parts are attached to other parts or assemblies, the securement of the parts sha
11、ll notbe impaired after air-oven aging.52.1.5 To determine the degradation of a plastic material used in a siphon tube, ring samples 12.7 mm(1/2 inch) wide are to be cut from the tube and subjected to air-oven aging. See 52.1.6. The ring samplesthen are to be subjected to a crush test between parall
12、el flat plates using a machine that applies acompression load at a uniform rate of 5 mm (0.2 inch) per min and records the load applied as a functionof the deflection. The test also is to be conducted on unaged parts of identical size for comparativepurposes. When the nature of the material is such
13、that meaningful test results are unobtainable, othertests, such as a tension test, are to be conducted.52.1.6 The plastic valve parts and plastic siphon tube samples to be aged are to be supported in afull-draft, circulating-air oven that has been preheated at full draft to 100 1.0C (212 1.8F). Samp
14、lesare not to touch one another or the sides of the oven. The samples of the plastic valve parts and siphontube are to be aged for 180 and 90 days, respectively, at full draft and then cooled in air at 23.0 2.0C(73.4 3.6F) for at least 24 h before conducting any test or dimensional measurement. As u
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL2127CRD2018ULSTANDARDFORSAFETYINERTGASCLEANAGENTEXTINGUISHINGSYSTEMUNITSSECTIONPARAGRAPHREFERENCE52SUBJECTAGINGTESTSPLASTICMATERIALSEDITION3MAY9PDF

链接地址:http://www.mydoc123.com/p-1067810.html