UL 183 CRD-2015 UL Standard for Safety Manufactured Wiring Systems - Section Paragraph Reference 15 6 7 1 Exception No 2 Subject MC-PCS cables with non Class 2 power conductors (E.pdf
《UL 183 CRD-2015 UL Standard for Safety Manufactured Wiring Systems - Section Paragraph Reference 15 6 7 1 Exception No 2 Subject MC-PCS cables with non Class 2 power conductors (E.pdf》由会员分享,可在线阅读,更多相关《UL 183 CRD-2015 UL Standard for Safety Manufactured Wiring Systems - Section Paragraph Reference 15 6 7 1 Exception No 2 Subject MC-PCS cables with non Class 2 power conductors (E.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): QQVXStandard Number: UL 183Standard Title: Standard for Manufactured Wiring SystemsEdition Date: September 22, 2009Edition Number: 4Section / Paragraph Refer
3、ence: 15.6, 7.1 Exception No. 2Subject: MC-PCS cables with non Class 2 power conductors.DECISION:15.6 Class 2 or 3 powered conductors shall not be run in AC, MC cables, flexible metal conduit or cordswith non Class 2 or 3 powered conductors. Class 2 or 3 powered conductors may be run in MC-PCScables
4、 with non Class 2 or 3 powered conductors.7.1 Exception No. 2: Conductors for use in remote control, signaling, or communications circuits may besmaller than 12 AWG. Class 2 or 3 powered conductors may be run in MC-PCS cables with non Class 2or 3 powered conductors.RATIONALE FOR DECISION:The rationa
5、le for the revision included with the December 5, 2014 Subject 183 proposal to add a newClause 15.6 was as follows:“To address the issue of Class 2 and 3 circuit conductors being placed within the same raceway (AC, MC,FMC or S cord) as the electric light and power conductors clause 15.6 is proposed.
6、 Refer to NEC Article725.136(A) of the National Electrical Code, NFPA 70.”At the time that the Subject 183 proposal was issued, there was a Subject 1569 (MC Cable) CRD in affectthat permitted Class 2 and 3 circuit conductors to be placed within the same cable as the electric light andpower conductor
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL183CRD2015ULSTANDARDFORSAFETYMANUFACTUREDWIRINGSYSTEMSSECTIONPARAGRAPHREFERENCE15671EXCEPTIONNO2SUBJECTMCPCSCABLESWITHNONCLASS2POWERCONDUCTORSEPDF

链接地址:http://www.mydoc123.com/p-1067700.html