UL 1821 CRD-2018 UL Standard for Safety Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service - Section Paragraph Reference New Clauses 1 4 and 29A Subject Pipe an.pdf
《UL 1821 CRD-2018 UL Standard for Safety Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service - Section Paragraph Reference New Clauses 1 4 and 29A Subject Pipe an.pdf》由会员分享,可在线阅读,更多相关《UL 1821 CRD-2018 UL Standard for Safety Thermoplastic Sprinkler Pipe and Fittings for Fire Protection Service - Section Paragraph Reference New Clauses 1 4 and 29A Subject Pipe an.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): VIWT, VIXR, VIWF, VIXO, VIXHStandard Number: UL 1821Standard Title: Standard for Thermoplastic Sprinkler Pipe and Fittings for FireProtection ServiceEdition Date: August 25, 2015Edition Number: 3Secti
3、on / Paragraph Reference: New Clauses 1.4 and 29ASubject: Pipe and Fittings Embedded in ConcreteDECISION:(NEW)1.4 The requirements covered by this standard do not address compatibility of plastic pipe and fittings withmaterials or products that they may be in contact with in storage, handling, or us
4、e.29A Concrete Embedment Test29A.1 Pipe and fittings intended to be embedded in concrete shall be evaluated to the following testmethod described in 29A.2 through 29A.5.29A.2 A straight test assembly shall be assembled with pipe, a fitting, and a cap using the assemblymethods in the manufacturers in
5、stallation instructions. The distance between the fitting and cap of the testassembly shall be a minimum of 10 pipe outside diameters (ODs) of exposed pipe length. The distancebetween the fitting and the concrete edge, where the pipe extends outside of the concrete, shall be aminimum of 2 pipe ODs o
6、f exposed pipe length.29A.3 The concrete used for embedment shall be made from a mixture of one part Portland cement, twoparts torpedo sand, and four parts crushed limestone or gravel, or of a mixture of these proportioned sothat a minimum compressive strength of 2500 psi is achieved. The concrete i
7、s to be reinforced with wiremesh or steel rods and formed with the assembly embedded in the concrete and cured for 28 days.Samples of the concrete in the form of test cylinders shall be prepared at the same time as the testassembly for measuring the compressive strength on day 28 in accordance with
8、ASTM C39.29A.4 After the test assembly has properly cured, the assembly shall pressure tested with water at 2 timesthe rated pressure for 5 minutes to verify that there are no leaks. This test assembly shall then beembedded in concrete, in accordance with the manufacturers installation instructions,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1821CRD2018ULSTANDARDFORSAFETYTHERMOPLASTICSPRINKLERPIPEANDFITTINGSFORFIREPROTECTIONSERVICESECTIONPARAGRAPHREFERENCENEWCLAUSES14AND29ASUBJECTPIPEANPDF

链接地址:http://www.mydoc123.com/p-1067698.html