UL 1741 CRD-2016 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources - Section Paragraph Referen.pdf
《UL 1741 CRD-2016 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources - Section Paragraph Referen.pdf》由会员分享,可在线阅读,更多相关《UL 1741 CRD-2016 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources - Section Paragraph Referen.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): QIKHStandard Number: UL 1741Standard Title: Standard for Inverters, Converters, Controllers and InterconnectionSystem Equipment for Use With Distributed Energy ResourcesEdition Date: January 28, 2010E
3、dition Number: 2Section / Paragraph Reference: New Sections 40B1- 40B2Subject: Additional Requirements for Single Phase 2 Wire Utility InteractiveInverters Connected to Single Phase 3 Wire EPS Circuits.DECISION:The requirements below include new definitions and a new Section 40B, to be used for the
4、evaluation ofinverters with single phase two wire power output circuits (L1-L2) that are rated for connection to singlephase 3 wire (L1-N-N2) EPS circuits. These requirements do not apply to single phase 2 wire invertersrated for connection to three phase EPS circuits.DefinitionsSingle Phase 2 Wire
5、Utility Interactive InverterAsinglephase inverter with only two outputterminals/conductors that are rated to be connected to EPS L1 and L2 (line to line connection). Theseinverters do not include an ungrounded / neutral conductor in the power export or EPS measurementcircuit.Single Phase 3 wire Util
6、ity Interactive Inverter A single phase inverter with two output powerterminals/conductors and a neutral/grounded terminal/conductor. These inverters are rated for connectionto EPS L1, L2 and Neutral or Ground. These inverters may export power Line to Line (L-L) or Line toNeutral to Line (L-N-L). Th
7、ese inverters monitor voltage between L1 and L2 and the neutral or groundedconductor.Add the following Sections to UL 1741.40B1 Two Wire Inverters connected to 3 Wire SystemsGeneral single phase 2 wire inverters rated for connection to single phase 3 wire EPS systems shallcomply with the performance
8、 criteria for single phase 3 wire inverters including response to abnormalvoltages including line to line and line to neutral. Single phase 3 wire protection provides both utilityprotective functions and overvoltage protection for local connected loads wired between each line andneutral. Single phas
9、e 2 wire inverters rated for connection to 3 wire single phase systems shall respondto single phase 3 wire abnormal voltage conditions that can differ between each line and neutral.40B1.1 The requirements in Sections 40B1 40B2 supplement and, in some cases, amend therequirements in Section 40.40B1.2
10、 The requirements in Sections 40B1 40B are designed to represent worst case conditions thatcould potentially generate Line to Neutral voltage imbalances where single phase 2 wire inverters areconnected to single phase 3 wire single phase EPS circuits.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHE
11、R REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL40B2 Testing Procedures40B2.1 Over and under Voltage Trip Tests40B2.1.1 Single phase 2 wire inverter shall comply with the Test for Response to Abnormal VoltageConditions as described in Section 5.2 of IEEE 1547.1 (2005) line to neutral and lin
12、e to line. The invertershall comply with the test requirements within the inverters rated Manufacture Stated Accuracy (MSA) forall L-L and L-N voltage measurements.Note: this test shall be applied in the same manner as if the inverter is a single phase, 3 wire inverter eventhough the EUT is a single
13、 phase, 2 wire inverter that is connected line to line.40B2.2 Open Phase Test40B2.2.1 The Single phase 2 wire inverter shall comply with Test for Response to Abnormal VoltageConditions as described in Section 5.9 of IEEE 1547.1 (2005) with the below modifications to step c) andd) of the IEEE 1547.1
14、test method:c) Open one phase conductor disconnect while the EUT is operating at 100%*, 66%*, 33%* ofunit rated output current and at greater of a) 5% of rated output current or b) the EUTsminimum output current.* The power output shall be adjusted to the target level 5%.d) Record the clearing time
15、and maximum RMS voltage at the unit output terminals andbetween the unit output terminals and load circuit neutral shown in Figure 40B2.40B2.2.2 Two Wire Voltage Imbalance Trip TestThis test uses the balanced load anti-islanding test setup1in Section 5.7 IEEE 1547.1 2005 as modifiedin Figure 40B2 be
16、low:1While this test uses the anti-islanding test setup it is not intended to demonstrate compliance with Section 5.7.This is generated text for figtxt.STANDARD NUMBER: UL 1741 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULThe single resi
17、stive element used in Section 5.7 of IEEE 1547.1 (2005) is connected from Line 1 to Line2. This single element is replaced with two resistive elements connected Line 1 to Neutral and Line 2 toNeutral to allow creation of imbalanced voltages between Line 1 to Neutral and Line 2 to Neutral loadswhen t
18、he test circuit is separated from the EPS by opening S1.Conduct the following test sequence:a) Record all relevant unit operating parameters.b) Adjust Simulated Utility to nominal voltage (Example: 120Vac/120Vac = 240Vac) andfrequency (60 Hz).c) Close Switch S1.d) Adjust power of EUT to 100% (5%) of
19、 rated output.e) The first test iteration shall be performed at the 50%-50% condition where R150%+R250%=RTotaland R1= R2 (2%) Adjust R1 and R2 to null the active current flowing through switch S1within 2% of unit rating. Record the value of RTotal. This RTotalvalue will be used as the basisfor all o
20、ther non 50% -50% load conditions defined for R1 and R2 in the table below.Note: The intention is that the RLC circuit will be balanced against the EUT outputpower after the S1 switch is opened. The RLC circuit current will only be balanced priorto opening the S1 switch for the R150%+R250%load condi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1741CRD2016ULSTANDARDFORSAFETYINVERTERSCONVERTERSCONTROLLERSANDINTERCONNECTIONSYSTEMEQUIPMENTFORUSEWITHDISTRIBUTEDENERGYRESOURCESSECTIONPARAGRAPHREFERENPDF

链接地址:http://www.mydoc123.com/p-1067664.html