UL 1741 CRD-2015 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources -Section Paragraph Referenc.pdf
《UL 1741 CRD-2015 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources -Section Paragraph Referenc.pdf》由会员分享,可在线阅读,更多相关《UL 1741 CRD-2015 UL Standard for Safety Inverters Converters Controllers and Interconnection System Equipment for Use With Distributed Energy Resources -Section Paragraph Referenc.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): QIJW, QIJW2, QIJSStandard Number: UL 1741Standard Title: Standard for Inverters, Converters, Controllers and InterconnectionSystem Equipment for Use With Dis
3、tributed Energy ResourcesEdition Date: January 28, 2010Edition Number: 2Section / Paragraph Reference: New paragraphs 2.35A 2.35J, New Section 10A,13A, 31A, 47A, 63.35 and 65.3.Subject: PV Rapid Shutdown SystemsDECISION:New Definitions -2.49A Actuator (Initiator) (s) one or more manual or automatic
4、switching device(s), input port(s) orsignal(s) that will result in the activation of the rapid shutdown system function(s) to disable the PV array.An actuator is intended to meet the function of the NEC defined initiator.2.49B Controlled conductor PV system conductors which are subject to the Rapid
5、Shutdown Systemrequirements in NEC 690.12. A controlled conductor is intended to be the same as the NEC definedcontrolled conductor.2.49C Electrical Isolation System (EIS) System intended to take action and electrically isolate acircuit(s) from other sources, circuits, and loads etc. These systems a
6、re intended to perform this isolationin response to an actuator signal.2.49D Electrical Output Attenuation Systems (EOAS) System intended to limit the available output ofan electrical energy source or circuit to a level that reduces the exposure to high voltage and current riskof electric shock and
7、fire. These systems are intended to perform this attenuation in response to anactuator signal.Note: Semi-conductor switching devices without air-gap switching, disconnecting or isolating devices are considered to beattenuating devices.2.49E High Reliability Equipment A single piece of equipment that
8、 has been investigated to becompliant with defined functional safety requirements so as to provide an increased level of reliability withregards to the likelihood of single point failures that could negatively affect the intended operation of theequipment.2.49F High Reliability System A system that
9、has been found compliant with defined requirements soas to provide an increased level of reliability with regards to single point failures that could negativelyaffect the intended operation of the system.2.49G PV Rapid Shutdown Equipment (PVRSE) Equipment intended to be used in a PVRSS todisconnect,
10、 isolate or attenuate the output controlled conductors of a PV array within 10 second of anactuator signal.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2.49H PV Rapid Shutdown System (PVRSS) System made up of PVRSE intended to disconnect,is
11、olate or attenuate the output controlled conductors of a PV array within 10 second of an actuator signal.2.49I Reset Device a device or signal used to re-enable the power generation capability of the PVsystem.2.49J Status Indicator Visual Indication device located at an actuator or other location th
12、at provides avisual signal and confirmation to the operator that the actuator function command has been effectivelyimplemented. In the case of an isolation indicator, it will indicate that the intended circuits have beenisolated. An attenuation indicator will indicate that the intended circuit has b
13、een attenuated.(Addition of New Section)10A Protection of Emergency Personnel10A.1 The requirements in this Section apply to PVRSE and PVRSS intended to reduce hazards fromelectric shock and energy hazards for emergency personnel or first responders, who may need to work inthe vicinity of a PV syste
14、m.10A.2 Within 10.0 seconds of an actuator signal a PVRSS shall maintain controlled conductors at a limitof not more than 30 Vdc, or 15 Vac, 8A and may not exceed 240 volt-amperes, PVRSE are evaluated toperform specific functions within PVRSS as defined by their specified functions and ratings.Note:
15、 PVRSS and PVRSE are required and defined by NEC 690.12.10A.3 An uninsulated live part involving a risk of electric shock or electrical energy-high current levelsshall be located, guarded, or enclosed to protect against unintentional contact by personnel who may becalled on to activate the actuating
16、 device while the equipment is energized.10A.4 A complete system that performs PVRSS functionality shall:A. Include at least one actuator as defined in 2.49AB. Provide one or more of the status indicators as detailed in Section 13C.C. Comply with either Section 13A, Electrical Isolation Systems or S
17、ection 13B, ElectricalOutput Attenuation Systems.D. Be marked as described in clause 63.35.1, and the installation instructions shall include theinformation in clause 65.3.1.10A.5 A complete PVRSS shall be marked as described in clause 63.35.1. The installation instructionsmay include the informatio
18、n in clause 65.3.1.10A.6 PVRSS and PVRSE which have not been found compliant with the requirements in section 31A“High Reliability Equipment and Systems” shall not be marked as “High Reliability” described in clause63.35.5.10A.7 Components used in the creation of PVRSS and PVRSE shall comply with th
19、e applicablerequirements for that component as well as the requirements within this standard. They shall be rated forsystem electrical and environmental operating conditions including foreseeable abnormal systemconditions.STANDARD NUMBER: UL 1741 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
20、 REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL10A.8 Mechanical devices having dual use as an AC or DC system disconnect in an electrical outputattenuation or isolation system shall comply with the requirements in section 13, and also be evaluated tothe applicable requirements of at least on
21、e of the following UL 508, UL 508I, UL 98, UL 98A, UL 98B, UL489, UL 489A, or UL 489B.10A.9 EOAS or EIS that include and rely upon multiple distributed switching devices or equipment thatare intended to operate as a group to perform PVRSS function shall be evaluated considering the effectof individu
22、al equipment failures with respect to the overall system functionality and operation. This shallinclude, but not be limited to:A. The possibility that failure of one component to operate may cause operative failures in othersystem equipment or components,B. The possible effects of an incomplete inst
23、allation (not a full complement of system equipmentor components being used) upon the operation of the system as a whole. Possible failuremodes shall be simulated during evaluation testing.C. The effects of delayed switching of multiple independent electrical and electrical/mechanicalswitching eleme
24、nts in the context of a system.D. The effects on the ability of multiple units to simultaneously receive and respond to theactuator signal including but not limited to signal loss or signal attenuation from conductorlength and impedance.10A.10 In addition to the applicable requirements and tests in
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1741CRD2015ULSTANDARDFORSAFETYINVERTERSCONVERTERSCONTROLLERSANDINTERCONNECTIONSYSTEMEQUIPMENTFORUSEWITHDISTRIBUTEDENERGYRESOURCESSECTIONPARAGRAPHREFERENCPDF

链接地址:http://www.mydoc123.com/p-1067663.html