《UL 1660 CRD-2018 UL Standard for Safety Liquid-Tight Flexible Nonmetallic Conduit - Section Paragraph Reference 5 10 1 5 10 4 6 1 3 and Table 9 Subject Increase of the Wet Limitat.pdf》由会员分享,可在线阅读,更多相关《UL 1660 CRD-2018 UL Standard for Safety Liquid-Tight Flexible Nonmetallic Conduit - Section Paragraph Reference 5 10 1 5 10 4 6 1 3 and Table 9 Subject Increase of the Wet Limitat.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): DXOQStandard Number: UL 1660Standard Title: Standard for Liquid-Tight Flexible Nonmetallic ConduitEdition Date: July 2, 2014Edition Number: 5Section / Paragraph Reference: 5.10.1, 5.10.4, 6.1.3 and Ta
3、ble 9Subject: Increase of the Wet Limitation for LFNC above 60C*This Certification Requirement Decision (CRD) supersedes prior CRD issued May 2,2018.DECISION:5.10.1 Specimens of the jacket of Type LFNC-A or Type LFNC-C conduit and specimens of the flexibleintegral lining or jacket of Type LFNC-B con
4、duit shall not absorb any more than 3.9 milligrams mass ofwater per square centimeter (25.0 milligrams mass of water per square inch) of immersed surface duringimmersion in tap water for 168 h at a temperature of 70.0 1.0C (158.0 1.8F) for insulation having atemperature rating of 60C (140F), at 82.0
5、 1.0C (179.6 1.8F) for insulation having a temperaturerating of 75C (167F) and at 94.0 1.0C (201.2 1.8F) for insulation having a temperature rating of90C (194F).A PVC or other material known to be non-hygroscopic and intended to have a LFNC conduit temperaturerating of 60C (140F) need not be subject
6、ed to this test.5.10.4 The water bath shall consist of a vitreous-enameled-steel or glass vessel containing tap water andshall be automatically controlled to maintain the water at 70.0 1.0C (158.0 1.8F) the specifiedtemperature. The vessel shall be provided with a close-fitting sheet-metal cover pla
7、te of brass or othernonferrous metal.6.1.3 The outside surface of conduit shall be marked with each of the following:a) Liquid-tight flexible nonmetallic conduit Type _ or LFNC-_ (use A, B,orC for thetype of LFNC conduit used). The means of reinforcement (fibrous or rigid) need not be markedb) The t
8、rade size and metric designator of the conduit, for example, 1/2 (16).c) The manufacturers name, trade name, or trademark or other descriptive marking thatidentifies the organization responsible for the conduit.d) 80C dry, 90C dry,or105C dry may be marked on conduit whose separate jacket orintegral
9、lining and jacket complies with the 113C (for the 80C rating), 121C (for the 90Crating), or 136C (for the 105C rating) oven aging requirements in Table 9. Conduit thatcomplies with one of these oven aging requirements but is not marked shall be acceptable foronly 60C dry use. Conduit may be marked 6
10、0C dry, but this use is understood without themarking.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULe) 70C oil res or 70C oil resistant may be marked on 80C or 105C dry use conduitwhose separate jacket or integral lining or jacket complies w
11、ith the 70C oil requirements inTable 9. Conduit, which complies and is not marked shall be acceptable for 60C oil resistantuse only. 60C dry use conduit shall not be so marked.f) SR, Sun Res,orSunlight Resistant may be marked on conduit whose separate jacket orintegral lining or jacket complies with
12、 the weather resistance test requirements in Clauses5.12.1 and 5.12.2. Conduit that complies but is not marked shall not be acceptable for usewhere exposed to direct rays of the sun.In the United States, Outdoor may be additionally marked.g) 75C wet or 90C wet may be marked on 80C or 105C dry use co
13、nduit whose separatejacket or integral lining or jacket complies with the 75C or 90C wet requirements in Table 9.Conduit, which complies and is not marked shall be acceptable for 60C wet use only. 60C dryuse conduit shall not be so marked. Conduit may be marked 60C wet, although this isunderstood wi
14、thout the marking.h) Conduit may be marked 60C oil res or 60C oil resistant, although this is understoodwithout the marking.i) Finished conduit that complies with the Direct-Burial Stiffness Test, in Clause 5.16, may besurface marked Direct Burial, Burial, Dir Burial,orDir Bur.j) Finished conduit th
15、at complies with the Flame Test in Cable Trays - FT4 per Clause 5.3 maybe marked FT4.Table 9Physical properties of jacket from Type LFNC-A or Type LFNC-C conduit and of flexible lining orjacket from Type LFNC-B conduit(See Clauses 5.13.1 and 6.1.3)Rating Condition of specimens attime of measurementM
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1660CRD2018ULSTANDARDFORSAFETYLIQUIDTIGHTFLEXIBLENONMETALLICCONDUITSECTIONPARAGRAPHREFERENCE51015104613ANDTABLE9SUBJECTINCREASEOFTHEWETLIMITATPDF

链接地址:http://www.mydoc123.com/p-1067605.html