UL 1088 CRD-2018 UL Standard for Safety Temporary Lighting Strings - Section Paragraph Reference 18 1 4 Subject Metallic Lamp Guards that are Unlikely to Become Energized (Edition.pdf
《UL 1088 CRD-2018 UL Standard for Safety Temporary Lighting Strings - Section Paragraph Reference 18 1 4 Subject Metallic Lamp Guards that are Unlikely to Become Energized (Edition.pdf》由会员分享,可在线阅读,更多相关《UL 1088 CRD-2018 UL Standard for Safety Temporary Lighting Strings - Section Paragraph Reference 18 1 4 Subject Metallic Lamp Guards that are Unlikely to Become Energized (Edition.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): XBRT, XBRT7Standard Number: UL 1088Standard Title: Standard for Temporary Lighting StringsEdition Date: July 10, 2015Edition Number: 7Section / Paragraph Reference: 18.1.4Subject: Metallic Lamp Guards
3、 that are Unlikely to Become EnergizedDECISION:18.1.4 A metal lamp guard with or without a nonmetallic coating shall be positively bonded to theequipment grounding conductor of the string.Exception No. 1: A metal lamp guard that is shipped separate from the lampholder shall be provided withinstructi
4、ons (see 44.17) for positive connection to the equipment grounding conductor of the string unlessthe bonding connection is automatically obtained.Exception No. 2: A metal lamp guard that must be removed for relamping shall be designed so that thebonding connection is automatically provided on assemb
5、ly to the lampholder.Exception No. 3: A metal lamp guard of a temporary lighting string employing non-replaceable lightsources that is unlikely to become energized.RATIONALE FOR DECISION:Prior to the 6th Edition, UL 1088 only covered temporary lighting strings employing Edison screw baselampholders.
6、 As a result the requirements were broadly written to mitigate inherent risks of electric shockassociated with the use of replaceable lamps in a construction site environment. Now the scope of UL1088 also covers temporary lighting strings employing non-replaceable LED light sources. This allowssome
7、of the specific risk of shock conditions originally anticipated by the standard to be eliminated ormitigated by product design. While this CRD does not modify the existing requirements applicable totraditional lighting strings employing lamps with Edison screw bases, it provides an alternative appro
8、achfor grounding requirements in new temporary lighting strings with non-replaceable LED light sources.The potential risk of electric shock is addressed in ANSI/UL 1088 / CAN/ULC-S1088 by multiple layers ofconstruction requirements including minimum spacings, adequacy of insulation, grounding and bo
9、nding,as well as testing requirements including abnormal operation, dielectric voltage withstand and continuitytests.However, regardless of construction design Clause 18.1.4 of the standard requires all temporary lightingstrings provided with metal guards to have the guard bonded to the equipment gr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL1088CRD2018ULSTANDARDFORSAFETYTEMPORARYLIGHTINGSTRINGSSECTIONPARAGRAPHREFERENCE1814SUBJECTMETALLICLAMPGUARDSTHATAREUNLIKELYTOBECOMEENERGIZEDEDITIONPDF

链接地址:http://www.mydoc123.com/p-1067320.html