《UL 1004-5-2014 UL Standards for Safety Fire Pump Motors (Second Edition Reprint with revisions through and including September 1 2016)《消防泵电动机的UL安全标准 (第二版)》.pdf》由会员分享,可在线阅读,更多相关《UL 1004-5-2014 UL Standards for Safety Fire Pump Motors (Second Edition Reprint with revisions through and including September 1 2016)《消防泵电动机的UL安全标准 (第二版)》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1004-5 Fire Pump MotorsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTI
2、ON OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Fire Pump Motors, UL 1004-5 Second Edition, Dated May 9, 2014 Summary of Topics This Second Edition of ANSI/UL 1004-5 has been issued as an editorial update only. No changes in requirements have been made. All rights reserved.
3、No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied
4、, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use
5、of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versio
6、ns of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the pu
7、rchasers computer system. The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or other elements of the Standard having future effective dates as indicated in the note following the affected item. The prior text for requirements that have bee
8、n revised and that have a future effective date are located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. MAY 9, 2014 UL 1004-5 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 9, 2014 UL 1004-5 tr2 No Text
9、on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 9, 2014 1 UL 1004-5 Standard for Fire Pump Motors First Edition September, 2008 Second Edition May 9, 2014 This ANSI/UL Standard for Safety consists of the Second Edition. The m
10、ost recent designation of ANSI/UL 1004-5 as an American National Standard (ANSI) occurred on September 19, 2011. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, Title Page, or effective date information. Comments or proposals for revisions on any part of the Standard
11、 may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All
12、of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2014 UNDERWRITERS LABORATORIES INC. ANSI/UL 1004-5-2011UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSIO
13、N FROM UL MAY 9, 2014 FIRE PUMP MOTORS - UL 1004-5 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .4 2 Glossary .4 CONSTRUCTION 3 General 5 4 Frame and Enclosure 5 PERFORMANCE 5 General 6
14、6 Variation from Rated Voltage Test 6 7 Temperature Test .6 8 Locked Rotor Test for Fire Pump Motors .6 9 Duty Cycle Test .9 10 Design B Compliance Tests 10 MARKINGS 11 General 12 INSTRUCTIONS 12 General 12 MAY 9, 2014 FIRE PUMP MOTORS - UL 1004-5 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER
15、REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 This Standard is intended to be read together with the Standard for Rotating Electrical Machines General Requirements, UL 1004-1. The requirements in this Standard supplement or amend the requirements in UL 1004-1. The
16、requirements of UL 1004-1 apply unless modied by this Standard. 1.2 This Standard covers Design B polyphase motors, as dened in NEMA MG 1, Motors and Generators, rated 500 horsepower (373 kW) or less, 600 volts or less, that are intended for use in accordance with NFPA 20, the Standard for the Insta
17、llation of Centrifugal Fire Pumps. 1.3 This Standard does not cover the re pump controller. These controllers are covered by the Standard for Fire Pump Controllers, UL 218. 1.4 These requirements do not cover motors intended for use in hazardous locations as dened in the National Electrical Code, NF
18、PA 70. The National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA 02169. 2 Glossary 2.1 For the purpose of this Standard, the following denitions apply. 2.2 BREAKDOWN TORQUE Maximum torque developed when a motor is run at rated voltag
19、e and frequency, without an abrupt loss in speed. 2.3 DESIGNBAsquirrel-cage motor designed to certain minimum torque values and a maximum locked-rotor current with a slip of less than 5 percent at rated load. 2.4 DRIPPROOF A motor intended for indoor use and designed to provide a degree of protectio
20、n against a limited amount of falling water and dirt. 2.5 LOCKED-ROTOR TORQUE Minimum torque developed when a motor with the rotor locked is operated at rated voltage and frequency. 2.6 MODELING A process to simulate an actual load under laboratory conditions. This is usually used when testing a mot
21、or for the Duty Cycle Test, Section 9. The loading device may have more severe starting conditions than the re pump. In order to avoid overheating the motor during testing, it is required to reduce the number of starts and stops. 2.7 PULL-UP TORQUE Minimum torque developed at any speed between zero
22、and the speed corresponding to the breakdown torque, when the motor is operated at rated voltage and frequency. 2.8 RADIUS OF GYRATION The distance from an axis that one could put a single particle of weight equal to the weight of a rigid body and have this particle have the same total weight (force
23、) moment of inertia as the original body. The radius of gyration is expressed in the units of distance (meters or feet) squared, i.e., m 2 or ft 2 . 2.9 SLIP SPEED The difference between the synchronous speed and the measured speed of a motor. MAY 9, 2014 FIRE PUMP MOTORS - UL 1004-5 4UL COPYRIGHTED
24、 MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2.10 SLIP Dened as Slip Speed divided by Synchronous Speed. 2.11 SYNCHRONOUS SPEED (of a motor) Dened by the equation, h s = 120 f/p in which: h s = the synchronous speed in revolutions per minute f = the li
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL100452014ULSTANDARDSFORSAFETYFIREPUMPMOTORSSECONDEDITIONREPRINTWITHREVISIONSTHROUGHANDINCLUDINGSEPTEMBER12016

链接地址:http://www.mydoc123.com/p-1067235.html