UL 1004-5 CRD-2017 UL Standards for Safety Fire Pump Motors - Section Paragraph Reference 8 3 10 3 11 5 Subject Requirements for motors rated above 600V and greater than 500 hp (E.pdf
《UL 1004-5 CRD-2017 UL Standards for Safety Fire Pump Motors - Section Paragraph Reference 8 3 10 3 11 5 Subject Requirements for motors rated above 600V and greater than 500 hp (E.pdf》由会员分享,可在线阅读,更多相关《UL 1004-5 CRD-2017 UL Standards for Safety Fire Pump Motors - Section Paragraph Reference 8 3 10 3 11 5 Subject Requirements for motors rated above 600V and greater than 500 hp (E.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): QXZFStandard Number: UL 1004-5Standard Title: Standard for Fire pump MotorsEdition Date: May 9, 2014Edition Number: 2Section / Paragraph Reference: 8.3, 10.3, 11.5Subject: Requirements for motors rate
3、d above 600V and greater than 500 hp.DECISION:8.3 Motors rated above 600V or greater than 500 hp are energized with the rotor locked at rated voltageand frequency for 3 seconds or until the locked-rotor current begins to decrease, whichever occurs first.The locked-rotor current is to be measured at
4、the conclusion of the test (see Clause 11.5). After thelocked-rotor test, and while still in a heated condition, the motor shall be subjected to the DielectricVoltage-Withstand Test of UL 1004-1 without evidence of electrical breakdown. The motor shall operateas intended after the application of the
5、 dielectric test potential.10.3 Motors rated above 600V or greater than 500 hp shall have locked-rotor, breakdown, and pull-uptorques equal to or greater than the values in Table 10.4.Table 10.4*Torque values for motors rated greater than 600V or over 500 hpTorque Percentage of Rated Full-load Torqu
6、eLocked-rotor 60%Pull-up 60%Breakdown175%*Per NEMA MG-1 (Table 20.10.1)11.5 Motors rated above 600V or greater than 500 hp exceeding the locked-rotor limits in Tables 8.1 or8.2, as applicable, shall be marked with the measured locked-rotor current; see Clause 8.3.RATIONALE FOR DECISION:Motors rated
7、above 600V and greater than 500 hp are considered “large motors (machines)” and coveredunder Section 20 of NEMA MG-1. These motors are normally built for custom installations and thereforedo not necessarily follow Design B (general purpose) performance characteristics.The CRD clarifies the performan
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL10045CRD2017ULSTANDARDSFORSAFETYFIREPUMPMOTORSSECTIONPARAGRAPHREFERENCE83103115SUBJECTREQUIREMENTSFORMOTORSRATEDABOVE600VANDGREATERTHAN500HPEPDF

链接地址:http://www.mydoc123.com/p-1067234.html