UL 1004-4 CRD-2017 UL Standard for Safety Electric Generators - Section Paragraph Reference 6A (new) Table 6A 1 7 2 7 3 Subject Maximum temperatures requirements for standby gener.pdf
《UL 1004-4 CRD-2017 UL Standard for Safety Electric Generators - Section Paragraph Reference 6A (new) Table 6A 1 7 2 7 3 Subject Maximum temperatures requirements for standby gener.pdf》由会员分享,可在线阅读,更多相关《UL 1004-4 CRD-2017 UL Standard for Safety Electric Generators - Section Paragraph Reference 6A (new) Table 6A 1 7 2 7 3 Subject Maximum temperatures requirements for standby gener.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): JZGZ/2Standard Number: UL 1004-4Standard Title: Standard for Electric GeneratorsEdition Date: October 25, 2011Edition Number: 2Section / Paragraph Reference: 6A (new), Table 6A.1, 7.2, 7.3Subject: Max
3、imum temperatures requirements for standby generatorsDECISION:(New Section)6A Temperature Test for Standby Generators6A.1 STANDBY GENERATOR Electrical generator intended to provide temporary power duringemergency conditions.6A.2 When tested in accordance with the Temperature Test of UL 1004-1, the w
4、indings of a standbygenerator shall not exceed the limits specified in Table 6A.1, when adjusted to a 40C ambient.Table 6A.1Maximum winding temperature for standby generators(thermocouple or resistance method)Materials and components C (F)Class A (105) 125 (257)Class B (130) 145 (293)Class F (155) 1
5、70 (338)Class H (180) 190 (374)6A.3 For standby generators, during the temperature test, when the temperature on a field-installed leador on any part within the wiring compartment that can be contacted by a lead is more than 60C (140F)when adjusted to the rated ambient, the standby generator shall b
6、e marked at or near the point where fieldconnections shall be made, and so located that the marking is readily visible during installation inaccordance with 7.3. The temperature value to be used in the marking shall be in accordance with Table6A.2.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER R
7、EPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 6A Terminal box markingMaximum temperatureaattained in terminal box or compartmentduring temperature testTemperature markingC (F) C (F)61 75 (142 167) 75 (167)76 90 (169 194) 90 (194)aCorrected to an ambient temperature of 40C (77F).(New)7.2
8、 A standby generator shall be marked “Standby Service”.(New)7.3 When the temperature within a terminal box exceeds the 60C at a point where field installed leadscan contact, a standby generator shall be additionally marked with the following: CAUTION: Use supplywires suitable for _C or equivalent wo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL10044CRD2017ULSTANDARDFORSAFETYELECTRICGENERATORSSECTIONPARAGRAPHREFERENCE6ANEWTABLE6A17273SUBJECTMAXIMUMTEMPERATURESREQUIREMENTSFORSTANDBYGENERPDF

链接地址:http://www.mydoc123.com/p-1067230.html